SINAMICS alarms
Cause:
An error was detected when downloading a project using the commissioning software (e.g. incorrect parameter value). It
is possible that the parameter limits are dependent on other parameters.
The detailed cause of the fault can be determined using the fault value.
Fault value (r0949, interpret hexadecimal):
ccbbaaaa hex
aaaa = Parameter
bb = Index
cc = fault cause
0: Parameter number illegal.
1: Parameter value cannot be changed.
2: Lower or upper value limit exceeded.
3: Sub-index incorrect.
4: No array, no sub-index.
5: Data type incorrect.
6: Setting not permitted (only resetting).
7: Descriptive element cannot be changed.
9: Descriptive data not available.
11: No master control.
15: No text array available.
17: Task cannot be executed due to operating state.
20: Illegal value.
21: Response too long.
22: Parameter address illegal.
23: Format illegal.
24: Number of values not consistent.
25: Drive object does not exist.
101: Presently deactivated.
104: Illegal value.
107: Write access not permitted when controller enabled.
108: Unit unknown.
109: Write access only in the commissioning state, encoder (p0010 = 4).
110: Write access only in the commissioning state, motor (p0010 = 3).
111: Write access only in the commissioning state, power unit (p0010 = 2).
112: Write access only in the quick commissioning mode (p0010 = 1).
113: Write access only in the ready mode (p0010 = 0).
114: Write access only in the commissioning state, parameter reset (p0010 = 30).
115: Write access only in the Safety Integrated commissioning state (p0010 = 95).
116: Write access only in the commissioning state, technological application/units (p0010 = 5).
117: Write access only in the commissioning state (p0010 not equal to 0).
118: Write access only in the commissioning state, download (p0010 = 29).
119: Parameter may not be written in download.
120: Write access only in the commissioning state, drive basic configuration (device: p0009 = 3).
121: Write access only in the commissioning state, define drive type (device: p0009 = 2).
122: Write access only in the commissioning state, data set basic configuration (device: p0009 = 4).
123: Write access only in the commissioning state, device configuration (device: p0009 = 1).
124: Write access only in the commissioning state, device download (device: p0009 = 29).
125: Write access only in the commissioning state, device parameter reset (device: p0009 = 30).
126: Write access only in the commissioning state, device ready (device: p0009 = 0).
127: Write access only in the commissioning state, device (device: p0009 not equal to 0).
129: Parameter may not be written in download.
130: Transfer of the master control is inhibited via binector input p0806.
131: Required BICO interconnection not possible because BICO output does not supply floating value
Alarms
768
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
132: Free BICO interconnection inhibited via p0922.
133: Access method not defined.
200: Below the valid values.
201: Above the valid values.
202: Cannot be accessed from the Basic Operator Panel (BOP).
203: Cannot be read from the Basic Operator Panel (BOP).
204: Write access not permitted.
Remedy:
- correct the parameterization in the commissioning tool and download the project again.
- enter the correct value in the specified parameter.
- identify the parameter that restricts the limits of the specified parameter.
201043
<location>Fatal error at project download
Drive object:
All objects
Message value:
Fault cause: %1
Reaction:
Infeed: NONE (OFF1, OFF2)
Servo: NONE (OFF1, OFF2, OFF3)
Vector: NONE (OFF1, OFF2, OFF3)
Hla: NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
A fatal error was detected when downloading a project using the commissioning tool.
Fault value (r0949, interpret decimal):
1: Device status cannot be changed to Device Download (drive object ON?).
2: Incorrect drive object number.
3: A drive object that has already been deleted is deleted again.
4: Deleting a drive object that has already been registered for generation.
5: Deleting a drive object that does not exist.
6: Generating an undeleted drive object that already existed.
7: Regenerating a drive object already registered for generation.
8: Maximum number of drive objects that can be generated exceeded.
9: Error while generating a device drive object.
10: Error while generating target topology parameters (p9902 and p9903).
11: Error when generating a drive object (global component).
12: Error when generating a drive object (drive component).
13: Unknown drive object type.
14: Drive status cannot be changed to "ready for operation" (r0947 and r0949).
15: Drive status cannot be changed to drive download.
16: Device status cannot be changed to "ready for operation".
17: It is not possible to download the topology. The component wiring should be checked, taking into account the various
messages/signals.
18: A new download is only possible if the factory settings are restored for the drive unit.
19: The slot for the option module has been configured several times (e.g. CAN and COMM BOARD)
20: The configuration is inconsistent (e.g. CAN for Control Unit, however no CAN configured for drive objects A_INF, SERVO
or VECTOR).
21: Error when accepting the download parameters.
22: Software-internal download error.
23: download not possible when know-how protection is activated.
24: download not possible during a partial power up after inserting a component.
25: The configuration is inconsistent. Know-how protection is either not activated or only partially.
Additional values:
Only for internal Siemens troubleshooting.
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
769
SINAMICS alarms
Remedy:
- use the current version of the commissioning tool.
- modify the offline project and carry out a new download (e.g. compare the number of drive objects, motor, encoder, power
unit in the offline project and at the drive).
- change the drive state (is a drive rotating or is there a message/signal?).
- Observe additional active messages/signals and remove their cause (e.g. correct any incorrectly set parameters).
- automatically calculate the control parameters (p0340). Then set p0010 = 0.
- boot from previously saved files (switch-off/switch-on or p0976).
- before a new download, restore the factory setting if the know-how protection was not activated on all drive objects.
201044
<location>CU: Descriptive data error
Drive object:
All objects
Message value:
%1
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
An error was detected when loading the descriptive data saved in the non-volatile memory.
Remedy:
Replace the memory card or Control Unit.
201045
<location>CU: Configuring data invalid
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
An error was detected when evaluating the parameter files PSxxxyyy.ACX, PTxxxyyy.ACX, CAxxxyyy.ACX, or CCxxxyyy.ACX
saved in the non-volatile memory. Because of this, under certain circumstances, several of the saved parameter values were
not able to be accepted.
Also see r9406 up to r9408.
Alarm value (r2124, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- check the parameters displayed in r9406 up to r9408, and correct these if required.
- Restore the factory setting (p0976 = 1) and reload the project into the converter.
Then save the parameterization in STARTER using the function "Copy RAM to ROM" or with p0977 = 1. This overwrites the
incorrect parameter files in the non-volatile memory - and this alarm is withdrawn.
See also: r9406, r9407, r9408
201049
<location>CU: It is not possible to write to file
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
It is not possible to write into a write-protected file (PSxxxxxx.acx). The write request was interrupted.
Alarm value (r2124, interpret decimal):
Drive object number.
Remedy:
Check whether the "write protected" attribute has been set for the files in the non-volatile memory under .../USER/SINAMICS/
DATA/...
When required, remove write protection and repeat the save operation (e.g. set p0977 = 1).
201050
<location>Memory card and device incompatible
Drive object:
All objects
Message value:
-
Alarms
770
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Reaction:
Infeed: OFF2 (NONE, OFF1)
Servo: OFF2 (NONE, OFF1, OFF3)
Vector: OFF2 (NONE, OFF1, OFF3)
Hla: OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The memory card and the device type do not match (e.g. a memory card for SINAMICS S is inserted in SINAMICS G).
Remedy:
- insert the matching memory card.
- use the matching Control Unit or power unit.
201054
<location>CU: System limit exceeded
Drive object:
All objects
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
At least one system overload has been identified.
Fault value (r0949, interpret decimal):
1: Computing time load too high (r9976[1]).
5: Peak load too high (r9976[5]).
Note:
As long as this fault is present, it is not possible to save the parameters (p0971, p0977).
See also: r9976 (System utilization)
Remedy:
For fault value = 1, 5:
- reduce the computing time load of the drive unit (r9976[1] and r9976[5]) to under 100 %.
- check the sampling times and adjust if necessary (p0115, p0799, p4099).
- deactivate function modules.
- deactivate drive objects.
- remove drive objects from the target topology.
- note the DRIVE-CLiQ topology rules and if required, change the DRIVE-CLiQ topology.
When using the Drive Control Chart (DCC) or free function blocks (FBLOCKS), the following applies:
- the computing time load of the individual runtime groups on a drive object can be read out in r21005 (DCC) or r20005
(FBLOCKS).
- if necessary, the assignment of the runtime group (p21000, p20000) can be changed in order to increase the sampling
time (r21001, r20001).
- if necessary, reduce the number of cyclically calculated blocks (DCC) and/or function blocks (FBLOCKS).
201055
<location>CU: Internal error (SYNO of port and application not identical)
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
All applications that operate with slaves at one port must be derived from the same SYNO clock cycle.
The first application whose registration (log-on) connects a slave to a port defines the SYNO clock cycle that will be used as
basis for the port.
Fault value (r0949, interpret hexadecimal):
Method ID.
Note:
Only for internal Siemens troubleshooting.
Remedy:
Contact Technical Support.
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
771
SINAMICS alarms
201056
<location>CU: Internal error (clock cycle of parameter group already assigned differently)
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The requested parameter group (IREG, NREG, ...) is already being used in a different clock cycle.
Fault value (r0949, interpret hexadecimal):
Method ID.
Note:
Only for internal Siemens troubleshooting.
Remedy:
Contact Technical Support.
201057
<location>CU: Internal error (different DRIVE-CLiQ type for the slave)
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The requested DRIVE-CLiQ type (hps_ps, hps_enc, ...) has been specified differently for the same slave component.
Fault value (r0949, interpret hexadecimal):
Method ID.
Note:
Only for internal Siemens troubleshooting.
Remedy:
Contact Technical Support.
201058
<location>CU: Internal error (slave missing in topology)
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The requested slave component does not exist in the topology.
Fault value (r0949, interpret hexadecimal):
Method ID.
Note:
Only for internal Siemens troubleshooting.
Remedy:
Contact Technical Support.
201059
<location>CU: Internal error (port does not exist)
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The port object assigned according to the topology of the requested slave component does not exist.
Fault value (r0949, interpret hexadecimal):
Method ID.
Note:
Only for internal Siemens troubleshooting.
Alarms
772
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Remedy:
Contact Technical Support.
201060
<location>CU: Internal error (parameter group not available)
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The requested parameter group (IREG, NREG, ...) is not offered by this slave type.
Fault value (r0949, interpret hexadecimal):
Method ID.
Note:
Only for internal Siemens troubleshooting.
Remedy:
Contact Technical Support.
201061
<location>CU: Internal error (application not known)
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
An application that is not registered with TSM has attempted to register with registerSlaves().
The cause can be an unsuccessful TSM registration or an incorrect registration sequence. It is always necessary to log in to
the TSM before registerSlaves() can be used.
Fault value (r0949, interpret hexadecimal):
Method ID.
Note:
Only for internal Siemens troubleshooting.
Remedy:
Contact Technical Support.
201063
<location>CU: Internal error (PDM)
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
An internal software error has occurred.
Fault value (r0949, interpret hexadecimal):
Method ID.
Note:
Only for internal Siemens troubleshooting.
Remedy:
Contact Technical Support.
201064
<location>CU: Internal error (CRC)
Drive object:
All objects
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
A checksum error (CRC error) has occurred in the Control Unit program memory
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
773
SINAMICS alarms
Remedy:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade firmware to later version.
- contact Technical Support.
201068
<location>CU: Data memory memory overflow
Drive object:
All objects
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The utilization for a data memory area is too large.
Fault value (r0949, interpret binary):
Bit 0 = 1: High-speed data memory 1 overloaded
Bit 1 = 1: High-speed data memory 2 overloaded
Bit 2 = 1: High-speed data memory 3 overloaded
Bit 3 = 1: High-speed data memory 4 overloaded
Remedy:
- deactivate the function module.
- deactivate drive object.
- remove the drive object from the target topology.
201069
<location>Parameter backup and device incompatible
Drive object:
All objects
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The parameter backup on the memory card and the drive unit do not match.
The module boots with the factory settings.
Example:
Devices A and B. are not compatible and a memory card with the parameter backup for device A is inserted in device B.
Remedy:
- insert a memory card with compatible parameter backup and carry out a POWER ON.
- insert a memory card without parameter backup and carry out a POWER ON.
- save the parameters (p0977 = 1).
201070
<location>Project/firmware is being downloaded to the memory card
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_PN, ENC, ENC_840,
HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO,
TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
An upgrade (project/firmware download) was initiated on the memory card.
While this fault is present, the corresponding update takes place with plausibility and consistency checks. After this,
depending on the command option, a new boot (reset) for the Control Unit is initiated.
Caution:
During the upgrade and while this fault is present, it is not permissible to switch off the Control Unit.
If the operation is interrupted, this can destroy the file system on the memory card. The memory card will then no longer
work properly and must be repaired.
Remedy:
Not necessary.
The fault is automatically withdrawn after the upgrade has been completed.
Alarms
774
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
201072
<location>Memory card restored from the backup copy
Drive object:
All objects
Message value:
-
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The Control Unit was switched-off while writing to the memory card. This is why the visible partition became defective.
After switching on, the data from the non-visible partition (backup copy) were written to the visible partition.
Remedy:
Check that the firmware and parameterization is up-to-date.
201073
<location>POWER ON required for backup copy on memory card
Drive object:
All objects
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The parameter assignment on the visible partition of the memory card has changed.
In order that the backup copy on the memory card is updated on the non-visible partition, it is necessary to carry out a
POWER ON or hardware reset (p0972) of the Control Unit.
Note:
It is possible that a new POWER ON is requested via this alarm (e.g. after saving with p0971 = 1).
Remedy:
- carry out a POWER ON (switch-off/switch-on) for the Control Unit.
- carry out a hardware reset (RESET button, p0972).
201082
<location>Parameter error when powering up from data backup
Drive object:
All objects
Message value:
Parameter: %1, index: %2, fault cause: %3
Reaction:
Infeed: OFF2 (NONE, OFF1)
Servo: OFF2 (NONE, OFF1, OFF3)
Vector: OFF2 (NONE, OFF1, OFF3)
Hla: OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
775
SINAMICS alarms
Cause:
Parameterizing errors have been detected (e.g. incorrect parameter value). It is possible that the parameter limits are
dependent on other parameters.
The detailed cause of the fault can be determined using the fault value.
Fault value (r0949, interpret hexadecimal):
ccbbaaaa hex
aaaa = Parameter
bb = Index
cc = fault cause
0: Parameter number illegal.
1: Parameter value cannot be changed.
2: Lower or upper value limit exceeded.
3: Sub-index incorrect.
4: No array, no sub-index.
5: Data type incorrect.
6: Setting not permitted (only resetting).
7: Descriptive element cannot be changed.
9: Descriptive data not available.
11: No master control.
15: No text array available.
17: Task cannot be executed due to operating state.
20: Illegal value.
21: Response too long.
22: Parameter address illegal.
23: Format illegal.
24: Number of values not consistent.
25: Drive object does not exist.
101: Presently deactivated.
104: Illegal value.
107: Write access not permitted when controller enabled.
108: Unit unknown.
109: Write access only in the commissioning state, encoder (p0010 = 4).
110: Write access only in the commissioning state, motor (p0010 = 3).
111: Write access only in the commissioning state, power unit (p0010 = 2).
112: Write access only in the quick commissioning mode (p0010 = 1).
113: Write access only in the ready mode (p0010 = 0).
114: Write access only in the commissioning state, parameter reset (p0010 = 30).
115: Write access only in the Safety Integrated commissioning state (p0010 = 95).
116: Write access only in the commissioning state, technological application/units (p0010 = 5).
117: Write access only in the commissioning state (p0010 not equal to 0).
118: Write access only in the commissioning state, download (p0010 = 29).
119: Parameter may not be written in download.
120: Write access only in the commissioning state, drive basic configuration (device: p0009 = 3).
121: Write access only in the commissioning state, define drive type (device: p0009 = 2).
122: Write access only in the commissioning state, data set basic configuration (device: p0009 = 4).
123: Write access only in the commissioning state, device configuration (device: p0009 = 1).
124: Write access only in the commissioning state, device download (device: p0009 = 29).
125: Write access only in the commissioning state, device parameter reset (device: p0009 = 30).
126: Write access only in the commissioning state, device ready (device: p0009 = 0).
127: Write access only in the commissioning state, device (device: p0009 not equal to 0).
129: Parameter may not be written in download.
130: Transfer of the master control is inhibited via binector input p0806.
131: Required BICO interconnection not possible because BICO output does not supply floating value
Alarms
776
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
132: Free BICO interconnection inhibited via p0922.
133: Access method not defined.
200: Below the valid values.
201: Above the valid values.
202: Cannot be accessed from the Basic Operator Panel (BOP).
203: Cannot be read from the Basic Operator Panel (BOP).
204: Write access not permitted.
Remedy:
- correct the parameterization in the commissioning tool and download the project again.
- enter the correct value in the specified parameter.
- identify the parameter that restricts the limits of the specified parameter.
201097
<location>NTP server cannot be accessed
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_PN, ENC, ENC_840,
HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO,
TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected NTP server (p3105[0...3]) cannot be accessed. Time synchronization cannot be performed.
Note:
NTP: Network Time Protocol
See also: p3105 (NTP server IP address)
Remedy:
Correctly set the IP address of the NTP server, and check the connection to the NTP server.
See also: p3105 (NTP server IP address)
201099
<location>UTC synchronization tolerance violated
Drive object:
All objects
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The tolerance (p3109) set for UTC synchronization was violated.
Note:
UTC: Universal Time Coordinates
See also: p3109 (UTC synchronization tolerance)
Remedy:
Select the synchronization intervals shorter so that the deviation between the time of day master and drive system lies
within the tolerance.
Note:
The deviation when synchronizing is shown in r3107.
See also: r3107 (UTC synchronization time out of tolerance)
201100
<location>CU: Memory card withdrawn
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM41,
VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The memory card (non-volatile memory) was withdrawn during operation.
Notice:
It is not permissible for the memory card to be withdrawn or inserted under voltage.
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
777
SINAMICS alarms
Remedy:
- switch off the drive system.
- re-insert the memory card that was withdrawn - this card must match the drive system.
- switch on the drive system again.
201104
<location>CU: Do not switch off. File system being optimized.
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, ENC, ENC_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO,
SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR,
VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The file system is currently being optimized in the non-volatile device memory of the Control Unit. This process may take
several minutes.
Notice:
The Control Unit must not be switched off during optimization, as this can lead to user data being lost.
Remedy:
Leave the Control Unit switched on during optimization.
Note:
The alarm is automatically withdrawn once the file system has been optimized.
201105
<location>CU: Insufficient memory
Drive object:
All objects
Message value:
%1
Reaction:
OFF1
Acknowledge:
POWER ON
Cause:
Too many functions have been configured on this Control Unit (e.g. too many drives, function modules, data sets,
Technology Extensions, blocks, etc).
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- change the configuration on this Control Unit (e.g. fewer drives, function modules, data sets, Technology Extensions,
blocks, etc).
- use an additional Control Unit.
201106
<location>CU: Insufficient memory
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
There is not sufficient free memory space available.
Remedy:
Not necessary.
201107
<location>CU: Save to memory card unsuccessful
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Alarms
778
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
A data save in the non-volatile memory was not able to be successfully carried out.
- non-volatile memory is defective.
- insufficient space in the non-volatile memory.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- try to save again.
- replace the memory card or Control Unit.
201110
<location>CU: More than one SINAMICS G on one Control Unit
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
More than one SINAMICS G type power unit is being operated from the Control Unit.
Fault value (r0949, interpret decimal):
Number of the second drive with a SINAMICS G type power unit.
Remedy:
Only one SINAMICS G drive type is permitted.
201111
<location>CU: Mixed operation of drive units illegal
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
Illegal operation of various drive units on one Control Unit:
- SINAMICS S together with SINAMICS G
- SINAMICS S together with SINAMICS S Value or Combi
Fault value (r0949, interpret decimal):
Number of the first drive object with a different power unit type.
Remedy:
Only power units of one particular drive type may be operated with one Control Unit.
201112
<location>CU: Power unit not permissible
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The connected power unit cannot be used together with this Control Unit.
Fault value (r0949, interpret decimal):
1: Power unit is not supported (e.g. PM240).
2: DC/AC power unit connected to CU310 not permissible.
3: Power unit (S120M) not permitted for vector control.
Remedy:
Replace the power unit that is not permissible by a component that is permissible.
201120
<location>Terminal initialization has failed
Drive object:
All objects
Message value:
%1
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY (POWER ON)
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
779
SINAMICS alarms
Cause:
An internal software error occurred while the terminal functions were being initialized.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade firmware to later version.
- contact Technical Support.
- replace the Control Unit.
201122
<location>Frequency at the measuring probe input too high
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_I_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_PN, ENC,
ENC_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, TB30, TM120, TM15, TM150, TM15DI_DO,
TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR
Message value:
%1
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
The frequency of the pulses at the measuring probe input is too high.
Fault value (r0949, interpret decimal):
1: DI/DO 9 (X122.8)
2: DI/DO 10 (X122.10)
4: DI/DO 11 (X122.11)
8: DI/DO 13 (X132.8)
16: DI/DO 14 (X132.10)
32: DI/DO 15 (X132.11)
64: DI/DO 8 (X122.7)
128: DI/DO 12 (X132.7)
Remedy:
Reduce the frequency of the pulses at the measuring probe input.
201122
<location>Frequency at the measuring probe input too high
Drive object:
CU_NX_840, SERVO_AC, VECTOR_AC
Message value:
%1
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
The frequency of the pulses at the measuring probe input is too high.
Fault value (r0949, interpret decimal):
1: DI/DO 9 (X122.8)
2: DI/DO 10 (X122.10)
4: DI/DO 11 (X122.11)
64: DI/DO 8 (X122.7)
Remedy:
Reduce the frequency of the pulses at the measuring probe input.
201123
<location>Power unit does not support digital inputs/outputs
Drive object:
SERVO, SERVO_840
Message value:
-
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
Power unit does not support the activated "digital inputs/outputs" function module
Remedy:
Deactivate the function module.
201150
<location>CU: Number of instances of a drive object type exceeded
Drive object:
All objects
Alarms
780
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Message value:
Drive object type: %1, number permitted: %2, actual number: %3
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The maximum permissible number of instances of a drive object type was exceeded.
Drive object type:
Drive object type (p0107), for which the maximum permissible number of instances was exceeded.
Number permitted:
Max. permissible number of instances for this drive object type.
Actual number:
Current number of instances for this drive object type.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
ddccbbaa hex: aa = drive object type, bb = number limited, cc = actual number, dd = no significance
Remedy:
- switch off the unit.
- suitably restrict the number of instances of a drive object type by reducing the number of inserted components.
- re-commission the unit.
201151
<location>CU: Number of drive objects of a category exceeded
Drive object:
All objects
Message value:
Drive object category: %1, number permitted: %2, actual number: %3
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The maximum permissible number of drive objects of a category was exceeded.
Drive object category:
Drive object category, for which the maximum permissible number of drive objects was exceeded.
Number permitted:
Max. permissible number for this drive object category.
Actual number:
Actual number for this drive object category.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
ddccbbaa hex: aa = drive object category, bb = number limited, cc = actual number, dd = no significance
Remedy:
- switch off the unit.
- suitably restrict the number of drive objects of the specified category by reducing the number of inserted components.
- re-commission the unit.
201152
<location>CU: Invalid constellation of drive object types
Drive object:
All objects
Message value:
-
Reaction:
NONE
Acknowledge:
POWER ON
Cause:
It is not possible to simultaneously operate drive object types SERVO, VECTOR and HLA.
A maximum of 2 of these drive object types can be operated on a Control Unit.
Remedy:
- switch off the unit.
- restrict the use of drive object types SERVO, VECTOR, HLA to a maximum of 2.
- re-commission the unit.
201200
<location>CU: Time slice management internal software error
Drive object:
All objects
Message value:
%1
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
781
SINAMICS alarms
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
A time slice management error has occurred.
It is possible that the sampling times have been inadmissibly set.
Fault value (r0949, interpret hexadecimal):
998:
Too many time slices occupied by technology functions (e.g. DCC).
999:
Too many time slices occupied by the basic system. Too many different sampling times may have been set.
Additional values:
Only for internal Siemens troubleshooting.
Remedy:
- check the sampling time setting (p0112, p0115, p4099, p9500, p9511).
- contact Technical Support.
201205
<location>CU: Time slice overflow
Drive object:
All objects
Message value:
%1
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
Insufficient processing time is available for the existing topology.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- reduce the number of drives.
- increase the sampling times.
201221
<location>CU: Basic clock cycle too low
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The closed-loop control / monitoring cannot maintain the envisaged clock cycle.
The runtime of the closed-loop control/monitoring is too long for the particular clock cycle or the computing time remaining
in the system is not sufficient for the closed-loop control/monitoring.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
Increase the basic clock cycle of DRIVE-CLiQ communication.
See also: p0112 (Sampling times pre-setting p0115)
201222
<location>CU: Basic clock cycle too low (computing time for communication not available)
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A time slice has not been defined that fulfills the requirements.
The port cannot be correctly operated as the alternating cyclic clock cycle cannot be maintained.
Fault value (r0949, interpret hexadecimal):
Method ID.
Note:
Only for internal Siemens troubleshooting.
Alarms
782
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Remedy:
Contact Technical Support.
201223
<location>CU: Sampling time inconsistent
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
783
SINAMICS alarms
Cause:
When changing a sampling time (p0115[0], p0799 or p4099), inconsistency between the clock cycles has been identified.
Alarm value (r2124, interpret decimal):
1: Value lower than minimum value.
2: Value higher than maximum value.
3: Value not a multiple of 1.25 µs.
4: Value does not match isochronous PROFIBUS operation.
5: Value not a multiple of 125 µs.
6: Value not a multiple of 250 µs.
7: Value not a multiple of 375 µs.
8: Value not a multiple of 400 µs.
10: Special restriction of the drive object violated.
20: On a SERVO with a sampling time of 62.5 µs, more than two drive objects or one drive object of a type other than SERVO
have been detected on the same DRIVE-CLiQ line (a maximum of two SERVO type drive objects are permitted).
21: Value can be a multiple of the current controller sampling time of a servo or vector drive in the system (e.g. for TB30,
the values of all of the indices should be taken into account).
30: Value less than 31.25 µs.
31: Value less than 62.5 µs (31.25 µs is not supported for SMC10, SMC30, SMI10 and Double Motor Modules).
32: Value less than 125 µs.
33: Value less than 250 µs.
40: Nodes have been identified on the DRIVE-CLiQ line whose highest common denominator of the sampling times is less
than 125 µs. Further, none of the nodes has a sampling time of less than 125 µs.
41: A chassis unit was identified on the DRIVE-CLiQ line as a node. Further, the highest common denominator of the
sampling times of all of the nodes connected to the line is less than 250 µs.
42: An Active Line Module was identified on the DRIVE-CLiQ line as a node. Further, the highest common denominator of
the sampling times of all of the nodes connected to the line is less than 125 µs.
43: A Voltage Sensing Module (VSM) was identified on the DRIVE-CLiQ line as a node. Further, the highest common
denominator of the sampling times of all of the nodes connected to the line is not equal to the current controller sampling
time of the drive object of the VSM.
44: The highest common denominator of the sampling times of all of the components connected to the DRIVE-CLiQ line is
not the same for all components of this drive object (e.g. there are components on different DRIVE-CLiQ lines on which
different highest common denominators are generated).
45: A chassis parallel unit was identified on the DRIVE-CLiQ line as a node. Further, the highest common denominator of the
sampling times of all of the nodes connected to the line is less than 162.5 µs or 187.5 µs (for a 2x or 3x parallel connection).
46: A node has been identified on the DRIVE-CLiQ line whose sampling time is not a multiple of the lowest sampling time
on this line.
52: Nodes have been identified on the DRIVE-CLiQ line whose highest common denominator of the sampling times is less
than 31.25 µs.
54: Nodes have been identified on the DRIVE-CLiQ line whose highest common denominator of the sampling times is less
than 62.5 µs.
56: Nodes have been identified on the DRIVE-CLiQ line whose highest common denominator of the sampling times is less
than 125 µs.
58: Nodes have been identified on the DRIVE-CLiQ line whose highest common denominator of the sampling times is less
than 250 µs.
99: Inconsistency of cross drive objects detected.
116: Recommended clock cycle in r0116[0...1].
General note:
The topology rules should be noted when connecting up DRIVE-CLiQ (refer to the appropriate product documentation).
The parameters of the sampling times can also be changed with automatic calculations.
Example for highest common denominator: 125 s, 125 µs, 62.5 µs --> 62.5 µs
Remedy:
- check the DRIVE-CLiQ cables.
- set a valid sampling time.
See also: p0115, p0799, p4099
Alarms
784
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
201224
<location>CU: Pulse frequency inconsistent
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
When changing the minimum pulse frequency (p0113) inconsistency between the pulse frequencies was identified.
Alarm value (r2124, interpret decimal):
1: Value lower than minimum value.
2: Value higher than maximum value.
3: Resulting sampling time is not a multiple of 1.25 µs.
4: Value does not match isochronous PROFIBUS operation.
10: Special restriction of the drive object violated.
99: Inconsistency of cross drive objects detected.
116: Recommended clock cycle in r0116[0...1].
Remedy:
Set a valid pulse frequency.
See also: p0113 (Minimum pulse frequency, selection)
201250
<location>CU: CU-EEPROM incorrect read-only data
Drive object:
All objects
Message value:
%1
Reaction:
NONE (OFF2)
Acknowledge:
POWER ON
Cause:
Error when reading the read-only data of the EEPROM in the Control Unit.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- replace the Control Unit.
201251
<location>CU: CU-EEPROM incorrect read-write data
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
Error when reading the read-write data of the EEPROM in the Control Unit.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
For alarm value r2124 < 256, the following applies:
- carry out a POWER ON (switch-off/switch-on).
- replace the Control Unit.
For alarm value r2124 >= 256, the following applies:
- for the drive object with this alarm, clear the fault memory (p0952 = 0).
- as an alternative, clear the fault memory of all drive objects (p2147 = 1).
- replace the Control Unit.
201255
<location>CU: Option Board EEPROM read-only data error
Drive object:
All objects
Message value:
%1
Reaction:
NONE (OFF2)
Acknowledge:
POWER ON
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
785
SINAMICS alarms
Cause:
Error when reading the read-only data of the EEPROM in the Option Board.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- replace the Control Unit.
201256
<location>CU: Option Board EEPROM read-write data error
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
Error when reading the read-write data of the EEPROM in the Option Board.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- replace the Control Unit.
201260
<location>Software not released
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_I_840, CU_LINK, CU_NX_840, ENC, ENC_840, HLA, HLA_840, HUB, R_INF, S_INF,
S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA,
TM54F_SL, VECTOR, VECTOR_AC
Message value:
-
Reaction:
Infeed: OFF1
Servo: OFF3
Vector: OFF3
Hla: OFF3
Acknowledge:
POWER ON
Cause:
The runtime software (RT-SW) has not been released.
Remedy:
Only for internal Siemens troubleshooting.
201275
<location>Hardware description error
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_I_840, CU_LINK, CU_NX_840, ENC, ENC_840, HLA, HLA_840, HUB, R_INF, S_INF,
S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA,
TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
Infeed: OFF2
Servo: OFF3
Vector: OFF3
Hla: OFF3
Acknowledge:
POWER ON
Alarms
786
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
An error has occurred while accessing the hardware description file on the CompactFlash card.
Directory and file name: ADDON/SINAMICS/DATA/HW_DESC/<DOType>/DESC0000
Fault value (r0949, interpret decimal):
22: File not found.
24: File read access error.
26: Format error.
28: Version error.
30: Internal reader error.
40: Contents error.
45: Hardware description not consistent.
60: Inconsistency: Number of Power Stack Adapters (PSA).
61: Inconsistency: Number of Sensor Module Cabinets (SMC).
62: Inconsistency: Number of Voltage Sensing Modules (VSM).
63: Inconsistency: Number of Terminal Modules (TM).
64: Inconsistency: Number of Terminal Boards (TB).
Remedy:
Only for internal Siemens troubleshooting.
201276
<location>Hardware description not fully compatible
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_I_840, CU_LINK, CU_NX_840, ENC, ENC_840, HLA, HLA_840, HUB, R_INF, S_INF,
S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA,
TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The hardware description file contains more data than the firmware requires.
Remedy:
Not necessary.
201302
<location>Error in the component trace
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
An error has occurred in the component trace.
The message appears in the following cases:
- upload trace data (p7792 = 1).
- change factory setting (p7790, p7791) for missing property "component trace" (r0193.1 = 0).
Alarm value (r2124, interpret decimal):
1: The DRIVE-CLiQ component does not support the component trace (r0193.1 = 0).
101: Data from trace 1 cannot be read.
102: Data from trace 2 cannot be read.
103: Data from trace 3 cannot be read.
104: Data from trace 4 cannot be read.
105: Data from trace 5 cannot be read.
Remedy:
For alarm value = 1:
Upgrade the firmware of the DRIVE-CLiQ component involved.
201303
<location>Component does not support the required function
Drive object:
All objects
Message value:
%1
Reaction:
OFF2
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
787
SINAMICS alarms
Acknowledge:
IMMEDIATELY
Cause:
A function requested by the Control Unit is not supported by a DRIVE-CLiQ component.
Fault value (r0949, interpret decimal):
1: The component does not support the deactivation.
101: The Motor Module does not support an internal armature short-circuit.
102: The Motor Module does not support the deactivation.
201: The Sensor Module does not support actual value inversion (p0410.0 = 1) when using a Hall sensor (p0404.6 = 1) for
the commutation.
202: The Sensor Module does not support parking/unparking.
203: The Sensor Module does not support the deactivation.
204: The firmware of this Terminal Module 15 (TM15) does not support the application TM15DI/DO.
205: The Sensor Module does not support the selected temperature evaluation (r0458, r0459).
206: The firmware of this Terminal Modules TM41/TM31/TM15 refers to an old firmware version. It is urgently necessary to
upgrade the firmware to ensure disturbance-free operation.
207: The power unit with this hardware version does not support operation with device supply voltages of less than 380 V.
208: The Sensor Module does not support deselection of commutation with zero mark (via p0430.23).
211: The Sensor Module does not support single-track encoders (r0459.10).
212: The Sensor Module does not support LVDT sensors (p4677.0).
213: The Sensor Module does not support the characteristic type (p4662).
214: The power unit does not support the temperature evaluation via PT1000 (r0193).
215: The Terminal Module does not support the temperature evaluation via PT1000
216: The Voltage Sensing Module (VSM) does not support operation with a PT1000 temperature sensor.
Remedy:
Upgrade the firmware of the DRIVE-CLiQ component involved.
For fault value = 205, 214, 215:
- check parameter p0600 and p0601 and if required, adapt.
For fault value = 207:
- replace the power unit or if required set the device supply voltage higher (p0210).
For fault value = 208:
- check parameter p0430.23 and reset if necessary.
For fault value = 216:
- check the setting of the sensor type (p3665).
- use a Voltage Sensing module that supports operation with PT1000 (MLFB ...-xxx1).
201304
<location>Firmware version of DRIVE-CLiQ component is not up-to-date
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The non-volatile memory has a more recent firmware version than the one in the connected DRIVE-CLiQ component.
Alarm value (r2124, interpret decimal):
Component number of the DRIVE-CLiQ component involved.
Remedy:
Update the firmware (p7828, p7829 - or commissioning tool).
201305
<location>Topology: Component number missing
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Alarms
788
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
The component number from the topology was not parameterized (p0121 (for power unit, refer to p0107), p0131 (for
servo/vector drives, refer to p0107), p0141, p0151, p0161).
Fault value (r0949, interpret decimal):
Data set number.
Note:
The fault also occurs if encoders have been configured (p0187 to p0189) but no component numbers exist for them.
In this case, the fault value includes the drive data set number plus 100 * encoder number (e.g. 3xx, if a component number
was not entered in p0141 for encoder 3 (p0189)).
See also: p0121, p0131, p0141, p0142, p0151, p0161, p0185, p0186, p0187, p0188, p0189
Remedy:
- enter missing component number.
- if required, remove the component and restart commissioning.
See also: p0121, p0131, p0141, p0142, p0151, p0161, p0185, p0186, p0187, p0188, p0189
201306
<location>Firmware of the DRIVE-CLiQ component being updated
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
Firmware update is active for at least one DRIVE-CLiQ component.
Alarm value (r2124, interpret decimal):
Component number of the DRIVE-CLiQ component.
Remedy:
Not necessary.
This alarm is automatically withdrawn after the firmware update has been completed.
201314
<location>Topology: Component must not be present
Drive object:
All objects
Message value:
%1, to %2, %3, connection: %4
Reaction:
NONE
Acknowledge:
NONE
Cause:
For a component, "deactivate and not present" is set but this component is still in the topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
aa = component number
bb = component class of the component
cc = connection number
Note:
Component class and connection number are described in F01375.
Remedy:
- remove the corresponding component.
- change the setting "deactivate and not present".
Note:
Under "Topology --> Topology view", the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
See also: p0105, p0125, p0145, p0155, p0165
201317
<location>Deactivated component again present
Drive object:
All objects
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
789
SINAMICS alarms
Cause:
If a component of the target topology for an active drive object is inserted and the associated parameter of the component
is set to "deactivate" (p0125, p0145, p0155, p0165).
Note:
This is the only message that is displayed for a deactivated component.
Remedy:
The alarm is automatically withdrawn for the following actions:
- activate the components involved (p0125 = 1, p0145 = 1, p0155 = 1, p0165 = 1).
- again withdraw the component involved.
See also: p0125, p0145, p0155, p0165
201318
<location>BICO: Deactivated interconnections present
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
This alarm is used in the following cases:
- if an inactive/non-operational drive object is active again/ready for operation
- if there are items in the list of BI/CI parameters (r9498[0...29], r9499[0...29])
- if the BICO interconnections saved in the list of BI/CI parameters (r9498[0...29], r9499[0...29]) have actually been changed
Remedy:
Reset alarm:
- set p9496 to 1 or 2
or
- deactivate the drive object again.
201319
<location>Inserted component not initialized
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, ENC, ENC_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO,
SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR,
VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
Initialization is required for at least one inserted component.
This is only possible if the pulses are inhibited for all the drive objects.
Remedy:
Activate pulse inhibit for all drive objects.
201320
<location>Topology: Drive object number does not exist in configuration
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
A drive object number is missing in p0978
Alarm value (r2124, interpret decimal):
Index of p0101 under which the missing drive object number can be determined.
Remedy:
Set p0009 to 1 and change p0978:
Rules:
- p0978 must include all of the drive object numbers (p0101).
- it is not permissible for a drive object number to be repeated.
- by entering a 0, the drive objects with PZD are separated from those without PZD.
- only 2 partial lists are permitted. After the second 0, all values must be 0.
- dummy drive object numbers (255) are only permitted in the first partial list.
Alarms
790
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
201321
<location>Topology: Drive object number does not exist in configuration
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
p0978 contains a drive object number that does not exist.
Alarm value (r2124, interpret decimal):
Index of p0978 under which the drive object number can be determined.
Remedy:
Set p0009 to 1 and change p0978:
Rules:
- p0978 must include all of the drive object numbers (p0101).
- it is not permissible for a drive object number to be repeated.
- by entering a 0, the drive objects with PZD are separated from those without PZD.
- only 2 partial lists are permitted. After the second 0, all values must be 0.
- dummy drive object numbers (255) are only permitted in the first partial list.
201322
<location>Topology: Drive object number present twice in configuration
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
A drive object number is present more than once in p0978.
Alarm value (r2124, interpret decimal):
Index of p0978 under which the involved drive object number is located.
Remedy:
Set parameter p0009 = 1 and change p0978:
Rules:
- p0978 must include all of the drive object numbers (p0101).
- it is not permissible for a drive object number to be repeated.
- by entering a 0, the drive objects with PZD are separated from those without PZD.
- only 2 partial lists are permitted. After the second 0, all values must be 0.
- dummy drive object numbers (255) are only permitted in the first partial list.
201323
<location>Topology: More than two partial lists created
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
Partial lists are available more than twice in p0978. After the second 0, all must be 0.
Alarm value (r2124, interpret decimal):
Index of p0978 under which the illegal value is located.
Remedy:
Set p0009 to 1 and change p0978:
Rules:
- p0978 must include all of the drive object numbers (p0101).
- it is not permissible for a drive object number to be repeated.
- by entering a 0, the drive objects with PZD are separated from those without PZD.
- only 2 partial lists are permitted. After the second 0, all values must be 0.
- dummy drive object numbers (255) are only permitted in the first partial list.
201324
<location>Topology: Dummy drive object number incorrectly created
Drive object:
All objects
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
791
SINAMICS alarms
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
In p0978, dummy drive object numbers (255) are only permitted in the first partial list.
Alarm value (r2124, interpret decimal):
Index of p0978 under which the illegal value is located.
Remedy:
Set p0009 to 1 and change p0978:
Rules:
- p0978 must include all of the drive object numbers (p0101).
- it is not permissible for a drive object number to be repeated.
- by entering a 0, the drive objects with PZD are separated from those without PZD.
- only 2 partial lists are permitted. After the second 0, all values must be 0.
- dummy drive object numbers (255) are only permitted in the first partial list.
201325
<location>Topology: Component number not present in target topology
Drive object:
All objects
Message value:
Component number: %1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The component configured in a parameter (e.g. p0121, p0131, etc.) is not present in the target topology.
Fault value (r0949, interpret decimal):
Configured component number that is not present in target topology.
Remedy:
Establish topology and DO configuration consistency.
201330
<location>Topology: Quick commissioning not possible
Drive object:
All objects
Message value:
Fault cause: %1, supplementary information: %2, preliminary component number: %3
Reaction:
NONE
Acknowledge:
NONE
Alarms
792
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
Unable to carry out a quick commissioning. The existing actual topology does not fulfill the requirements.
Alarm value (r2124, interpret hexadecimal):
ccccbbaa hex: cccc = preliminary component number, bb = supplementary information, aa = fault cause
aa = 01 hex = 1 dec:
On one component illegal connections were detected.
- bb = 01 hex = 1 dec: For a Motor Module, more than one motor with DRIVE-CLiQ was detected.
- bb = 02 hex = 2 dec: For a motor with DRIVE-CLiQ, the DRIVE-CLiQ cable is not connected to a Motor Module.
aa = 02 hex = 2 dec:
The topology contains too many components of a particular type.
- bb = 01 hex = 1 dec: There is more than one master Control Unit.
- bb = 02 hex = 2 dec: There is more than 1 infeed (8 for a parallel circuit configuration).
- bb = 03 hex = 3 dec: There are more than 10 Motor Modules (8 for a parallel circuit configuration).
- bb = 04 hex = 4 dec: There are more than 9 encoders.
- bb = 05 hex = 5 dec: There are more than 8 Terminal Modules.
- bb = 07 hex = 7 dec: Unknown component type
- bb = 08 hex = 8 dec: There are more than 6 drive slaves.
- bb = 09 hex = 9 dec: Connection of a drive slave not permitted.
- bb = 0a hex = 10 dec: There is no drive master.
- bb = 0b hex = 11 dec: There is more than one motor with DRIVE-CLiQ for a parallel circuit.
- bb = 0c hex = 12 dec: Different power units are being used in a parallel connection.
- cccc: Not used.
aa = 03 hex = 3 dec:
More than 16 components are connected at a DRIVE-CLiQ socket of the Control Unit.
- bb = 0, 1, 2, 3 means e.g. detected at the DRIVE-CLiQ socket X100, X101, X102, X103.
- cccc: Not used.
aa = 04 hex = 4 dec:
The number of components connected one after the other is greater than 125.
- bb: Not used.
- cccc = preliminary component number of the first component and component that resulted in the fault.
aa = 05 hex = 5 dec:
The component is not permissible for SERVO.
- bb = 01 hex = 1 dec: SINAMICS G available.
- bb = 02 hex = 2 dec: Chassis available.
- cccc = preliminary component number of the first component and component that resulted in the fault.
aa = 06 hex = 6 dec:
On one component illegal EEPROM data was detected. These must be corrected before the system continues to boot.
- bb = 01 hex = 1 dec: The Article No. [MLFB] of the power unit that was replaced includes a space retainer. The space retainer
(*) must be replaced by a correct character.
- cccc = preliminary component number of the component with illegal EEPROM data.
aa = 07 hex = 7 dec:
The actual topology contains an illegal combination of components.
- bb = 01 hex = 1 dec: Active Line Module (ALM) and Basic Line Module (BLM).
- bb = 02 hex = 2 dec: Active Line Module (ALM) and Smart Line Module (SLM).
- bb = 03 hex = 3 dec: SIMOTION control (e.g. SIMOTION D445) and SINUMERIK component (e.g. NX15).
- bb = 04 hex = 4 dec: SINUMERIK control (e.g. SINUMERIK 730.net) and SIMOTION component (e.g. CX32).
- cccc: Not used.
aa = 08 hex = 8 dec:
The motor is not completely connected.
- bb: Not used.
- cccc: Not used.
Note:
Connection type and connection number are described in F01375.
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
793
SINAMICS alarms
See also: p0097, r0098, p0099
Remedy:
- adapt the output topology to the permissible requirements.
- commission the device using the commissioning tool.
- for motors with DRIVE-CLiQ, connect the power and DRIVE-CLiQ cable to the same Motor Module (Single Motor Module:
DRIVE-CLiQ at X202, Double Motor Module: DRIVE-CLiQ from motor 1 (X1) to X202, from motor 2 (X2) to X203).
For aa = 06 hex = 6 dec and bb = 01 hex = 1 dec:
Correct the Article No. when commissioning using the commissioning tool.
See also: p0097, r0098, p0099
201331
<location>Topology: At least one component not assigned to a drive object
Drive object:
All objects
Message value:
Component number: %1
Reaction:
NONE
Acknowledge:
NONE
Cause:
At least one component is not assigned to a drive object.
- when commissioning, a component was not able to be automatically assigned to a drive object.
- the parameters for the data sets are not correctly set.
Alarm value (r2124, interpret decimal):
Component number of the unassigned component.
Remedy:
This component is assigned to a drive object.
Check the parameters for the data sets.
Examples:
- power unit (p0121).
- motor (p0131, p0186).
- encoder interface (p0140, p0141, p0187 ... p0189).
- encoder (p0140, p0142, p0187 ... p0189).
- Terminal Module (p0151).
- option board (p0161).
201340
<location>Topology: Too many components on one line
Drive object:
All objects
Message value:
Component number or connection number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Alarms
794
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
For the selected communications clock cycle, too many DRIVE-CLiQ components are connected to one line of the Control
Unit.
Fault value (r0949, interpret hexadecimal):
xyy hex: x = fault cause, yy = component number or connection number.
1yy:
The communications clock cycle of the DRIVE-CLiQ connection on the Control Unit is not sufficient for all read transfers.
2yy:
The communications clock cycle of the DRIVE-CLiQ connection on the Control Unit is not sufficient for all write transfers.
3yy:
Cyclic communication is fully utilized.
4yy:
The DRIVE-CLiQ cycle starts before the earliest end of the application. An additional dead time must be added to the control.
Sign-of-life errors can be expected.
The conditions of operation with a current controller sampling time of 31.25 µs have not been maintained.
5yy:
Internal buffer overflow for net data of a DRIVE-CLiQ connection.
6yy:
Internal buffer overflow for receive data of a DRIVE-CLiQ connection.
7yy:
Internal buffer overflow for send data of a DRIVE-CLiQ connection.
8yy:
The component clock cycles cannot be combined with one another
900:
The lowest common multiple of the clock cycles in the system is too high to be determined.
901:
The lowest common multiple of the clock cycles in the system cannot be generated with the hardware.
Remedy:
- check the DRIVE-CLiQ wiring.
- reduce the number of components on the DRIVE-CLiQ line involved and distribute these to other DRIVE-CLiQ sockets of the
Control Unit. This means that communication is uniformly distributed over several lines.
For fault value = 1yy - 4yy in addition:
- increase the sampling times (p0112, p0115, p4099). If necessary, for DCC or FBLOCKS, change the assignment of the
runtime group (p21000, p20000) so that the sampling time (r21001, r20001) is increased.
- if necessary, reduce the number of cyclically calculated blocks (DCC) and/or function blocks (FBLOCKS).
- reduce the function modules (r0108).
- establish the conditions for operation with a current controller sampling time of 31.25 µs (at the DRIVE-CLiQ line, only
operate Motor Modules and Sensor Modules with this sampling time and only use a permitted Sensor Module (e.g. SMC20,
this means a 3 at the last position of the Article No.)).
- For an NX, the corresponding Sensor Module for a possibly existing second measuring system should be connected to a
free DRIVE-CLiQ socket of the NX.
- for BSR Motor Modules, the following applies: If Safety Extended Functions is enabled, and 6 axes are operated on the
DRIVE-CLiQ line, then the clock cycle for the actual value sensing must be set as follows: p9511 >= 8 * current controller
sampling time (p0115[0]).
For fault value = 8yy in addition:
- check the clock cycles settings (p0112, p0115, p4099). Clock cycles on a DRIVE-CLiQ line must be perfect integer multiples
of one another. As clock cycle on a line, all clock cycles of all drive objects in the previously mentioned parameters apply,
which have components on the line involved.
For fault value = 9yy in addition:
- check the clock cycles settings (p0112, p0115, p4099). The lower the numerical value difference between two clock cycles,
the higher the lowest common multiple. This behavior has a significantly stronger influence, the higher the numerical
values of the clock cycles.
201341
<location>Topology: Maximum number of DRIVE-CLiQ components exceeded
Drive object:
All objects
Message value:
-
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
795
SINAMICS alarms
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
Too many DRIVE-CLiQ components were defined in the actual topology.
Note:
Pulse enable is withdrawn and prevented.
Remedy:
- check the DRIVE-CLiQ wiring.
- reduce the number components on the DRIVE-CLiQ line involved in order to maintain the maximum quantity structure.
201354
<location>Topology: Actual topology indicates an illegal component
Drive object:
All objects
Message value:
Fault cause: %1, component number: %2
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The actual topology indicates at least one illegal component.
Fault value (r0949, interpret hexadecimal):
yyxx hex: yy = component number, xx = cause.
xx = 1: Component at this Control Unit not permissible.
xx = 2: Component in combination with another component not permissible.
Note:
Pulse enable is prevented.
Remedy:
Remove the illegal components and restart the system.
201355
<location>Topology: Actual topology changed
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The device target topology (p0099) does not correspond to the device actual topology (r0098).
The fault only occurs if the topology was commissioned using the automatic internal device mechanism and not using the
commissioning tool.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
See also: r0098 (Actual device topology), p0099 (Device target topology)
Alarms
796
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Remedy:
One of the following counter-measures can be selected if no faults have occurred in the topology detection itself:
If commissioning is still not completed:
- carry out a self-commissioning routine (starting from p0009 = 1).
In general:
Set p0099 = r0098, set p0009 = 0; for existing Motor Modules, this results in servo drives being automatically generated
(p0107).
Generating servo drives: Set p0097 to 1, set p0009 to 0.
Generating vector drives: Set p0097 to 2, set p0009 to 0.
Generating vector drives with parallel connection: set p0097 to 12, set p0009 to 0.
In order to set configurations in p0108, before setting p0009 to 0, it is possible to first set p0009 to 2 and modify p0108. The
index corresponds to the drive object (p0107).
If commissioning has already been completed:
- re-establish the original connections and re-connect power to the Control Unit.
- restore the factory setting for the complete equipment (all of the drives) and allow automatic self-commissioning again.
- change the device parameterization to match the connections (this is only possible using the commissioning tool).
Notice:
Topology changes that result in this fault being generated cannot be accepted by the automatic function in the device, but
must be transferred using the commissioning tool and parameter download. The automatic function in the device only
allows constant topology to be used. Otherwise, when the topology is changed, all of the previous parameter settings are
lost and replaced by the factory setting.
See also: r0098 (Actual device topology)
201356
<location>Topology: There is a defective DRIVE-CLiQ component
Drive object:
All objects
Message value:
Fault cause: %1, Component number: %2, Connection number: %3
Reaction:
NONE (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
The actual topology indicates at least one defective DRIVE-CLiQ component.
Fault value (r0949, interpret hexadecimal):
zzyyxx hex:
zz = connection number of the component at which the defective component is connected
yy = component number of the component at which the defective component is connected
xx = fault cause
xx = 1: Component at this Control Unit not permissible.
xx = 2: component with communication defect.
Note:
Pulse enable is withdrawn and prevented.
Remedy:
Replace the defective component and restart the system.
201357
<location>Topology: Two Control Units identified on the DRIVE-CLiQ line
Drive object:
All objects
Message value:
component number: %1, connection number: %2
Reaction:
NONE (OFF2)
Acknowledge:
IMMEDIATELY
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
797
SINAMICS alarms
Cause:
In the actual topology, 2 Control Units are connected with one another through DRIVE-CLiQ.
As standard, this is not permitted.
This is only permitted if the Technology Extension OALINK has already been installed on the two Control Units and has been
commissioned online.
Fault value (r0949, interpret hexadecimal):
yyxx hex:
yy = connection number of the Control Unit at which the second Control Unit is connected
xx = component number of the Control Unit at which the second Control Unit is connected
Note:
Pulse enable is withdrawn and prevented.
Remedy:
In general:
- remove the connection to the second Control Unit and restart.
- for the S120M component DRIVE-CLiQ extension, interchange the hybrid cable (IN/OUT).
When using OALINK:
- remove the DRIVE-CLiQ connection and restart the systems.
- install OALINK on both Control Units and activate.
- Check the configuration of the DRIVE-CLiQ sockets in OALINK.
201358
<location>Topology: Line termination not available
Drive object:
All objects
Message value:
CU connection number: %1, component number: %2, connection number: %3
Reaction:
NONE
Acknowledge:
NONE
Cause:
At least one line with distributed drives is not terminated. The last participant on the line must be terminated with a line
termination connector.
This therefore ensures the degree of protection of the distributed drives.
Alarm value (r2124, interpret hexadecimal):
zzyyxx hex:
zz = connection number of the distributed drive where there is no terminating connector
yy = component number
xx = CU connection number
Remedy:
Install the line terminating connector for the last distributed drive.
201359
<location>Topology: DRIVE-CLiQ performance not sufficient
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The DRIVE-CLiQ performance is not sufficient at one line in order to identify an inserted component.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- Distribute components across several DRIVE-CLiQ lines.
Note:
For this topology, do not withdraw and insert components in operation.
201360
<location>Topology: Actual topology not permissible
Drive object:
All objects
Message value:
Fault cause: %1, preliminary component number: %2
Reaction:
NONE
Alarms
798
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Acknowledge:
IMMEDIATELY
Cause:
The detected actual topology is not permissible.
Fault value (r0949, interpret hexadecimal):
ccccbbaa hex:
cccc = preliminary component number, bb = no significance, aa = fault cause
aa = 01 hex = 1 dec:
Too many components were detected at the Control Unit. A maximum of 199 components is permissible.
aa = 02 hex = 2 dec:
The component type of a component is not known.
aa = 03 hex = 3 dec:
It is illegal to combine ALM and BLM.
aa = 04 hex = 4 dec:
It is illegal to combine ALM and SLM.
aa = 05 hex = 5 dec:
It is illegal to combine BLM and SLM.
aa = 06 hex = 6 dec:
A CX32 was not directly connected to a permitted Control Unit.
aa = 07 hex = 7 dec:
An NX10 or NX15 was not directly connected to a permitted Control Unit.
aa = 08 hex = 8 dec:
A component was connected to a Control Unit that is not permitted for this purpose.
aa = 09 hex = 9 dec:
A component was connected to a Control Unit with out-of-date firmware.
aa = 0A hex = 10 dec:
Too many components of a particular type detected.
aa = 0B hex = 11 dec:
Too many components of a particular type detected on a single line.
Note:
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
For fault cause = 1:
Change the configuration. Connect less than 199 components to the Control Unit.
For fault cause = 2:
Remove the component with unknown component type.
For fault cause = 3, 4, 5:
Establish a valid combination.
For fault cause = 6, 7:
Connect the expansion module directly to a permitted Control Unit.
For fault cause = 8:
Remove component or use a permissible component.
For fault cause = 9:
Upgrade the firmware of the Control Unit to a later version.
For fault cause = 10, 11:
Reduce the number of components.
201361
<location>Topology: Actual topology contains SINUMERIK and SIMOTION components
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
799
SINAMICS alarms
Cause:
The detected actual topology contains SINUMERIK and SIMOTION components.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex: cc = fault cause, bb = component class of the actual topology, aa = component number of the component
cc = 01 hex = 1 dec:
An NX10 or NX15 was connected to a SIMOTION control.
cc = 02 hex = 2 dec:
A CX32 was connected to a SINUMERIK control.
Remedy:
For alarm value = 1:
Replace all NX10 or NX15 by a CX32.
For alarm value = 2:
Replace all CX32 by an NX10 or NX15.
201362
<location>Topology: Topology rule(s) broken
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Alarms
800
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
At least one topology rule for the SINAMICS S120 Combi has been broken.
In the event of a fault, the ramping up of the drive system is aborted and closed-loop drive control is not enabled.
Alarm value (r2124, interpret decimal):
The alarm value indicates which rule has been violated.
1: The S120 Combi may only be wired via DRIVE-CLiQ socket X200 to X100 on the NCU.
2: In DRIVE-CLiQ socket X101 on the NCU, only one Single Motor Module (SMM) may be connected via X200, one Double
Motor Module (DMM) via X200, one Terminal Module 54F (TM54F) via X500 or one DRIVE-CLiQ Hub Module (DMC20,
DME20) via X500.
3: In DRIVE-CLiQ socket X102 on the NCU, only one Terminal Module 54F (TM54F) may be connected via X500, one DRIVE-
CLiQ Hub Module (Hub) via X500 or one NX15 via X100.
4: Only Sensor Modules may be connected to DRIVE-CLiQ sockets X201 up to X203 (3-axis) or X204 (4-axis) on the S120
Combi.
5: In DRIVE-CLiQ socket X205 (X204 is not available for 3 axes), only SMC / SME Sensor Modules and DRIVE-CLiQ encoders
may be connected.
6: In the case of a Single Motor Module as first expansion axis, only one additional Single Motor Module may be connected
in the DRIVE-CLiQ socket X201 via X200, one Terminal Module 54F (TM54F) via X500 or one DRIVE-CLiQ Hub Module
(DMC20, DME20) via X500.
7: Only Sensor Modules or DRIVE-CLiQ encoders may be connected in the DRIVE-CLiQ socket X202 on possibly available
Single Motor Modules.
8: For a second Single Motor Module or for a Double Motor Module, at X201 a 54F Terminal Module (TM54F) or a DRIVE-CLiQ
Hub Module (DMC 20, DME 20) may be connected via X500.
9: If a Double Motor Module is used as an expansion axis, only Sensor Modules may be connected to X202 and X203.
10: If a Terminal Module 54F (TM54F) is configured, only one DRIVE-CLiQ Hub Module (DMC20, DME20) may be connected
to X501 of the TM54F module via DRIVE-CLiQ socket X500. In this case, it is not permissible that an existing Hub Module is
connected elsewhere.
11: For DRIVE-CLiQ Hub Modules, only Sensor Modules (SMC, SME) and DRIVE-CLiQ encoders may be connected to X501
to X505.
12: Only certain Motor Modules may be used for expansion axes.
13: For an S120 Combi with 3 axes, nothing must be connected at the DRIVE-CLiQ Hub Module at X503.
14: A maximum of one Terminal Module 54F (TM54F) is permitted.
15: A maximum of one DRIVE-CLiQ Hub Module (DMC20, DME20) is permitted.
16: DRIVE-CLiQ socket X100 of NX15 must be connected with the NCU via X102.
17: The S120 Combi may only be connected to X101 of the NX15 via the DRIVE-CLiQ socket X200.
18: In DRIVE-CLiQ socket X102 on the NX15, only one Single Motor Module (SMM) may be connected via X200, one Double
Motor Module (DMM) via X200, one Terminal Module 54F (TM54F) via X500 or one DRIVE-CLiQ Hub Module (DMC20,
DME20) via X500.
19: It is not permissible that anything is connected at DRIVE-CLiQ socket X103 on the NX15.
Remedy:
Evaluate the alarm value and ensure compliance with the corresponding topology rule(s).
201375
<location>Topology: Connection duplicated between two components
Drive object:
All objects
Message value:
Component: %1, %2, connection: %3
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
801
SINAMICS alarms
Cause:
When checking the actual topology, a ring-type connection was detected.
The fault value describes a component contained in the ring.
Fault value (r0949, interpret hexadecimal):
ccbbaaaa hex:
cc = connection number (%3)
bb = component class (% 2)
aaaa = preliminary component number (%1)
Component class:
0: Component unknown.
1: Control Unit
2: Motor Module
3: Line Module
4: Sensor Module
5: Voltage Sensing Module
6: Terminal Module
7: DRIVE-CLiQ Hub Module
8: Controller Extension
9: Filter Module
10: Hydraulic Module.
49: DRIVE-CLiQ component
50: Option slot
60: Encoder
70: DRIVE-CLiQ motor
71: Hydraulic cylinder
72: Hydraulic valve
80: Motor
Connection number:
0: Port 0, 1: Port 1, 2: Port 2, 3: Port 3, 4: Port 4, 5: Port 5
10: X100, 11: X101, 12: X102, 13: X103, 14: X104, 15: X105
20: X200, 21: X201, 22: X202, 23: X203
50: X500, 51: X501, 52: X502, 53: X503, 54: X504, 55: X505
Remedy:
Output the fault value and remove the specified connection.
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
201380
<location>Topology: Actual topology EEPROM defective
Drive object:
All objects
Message value:
Preliminary component number: %1
Reaction:
NONE
Acknowledge:
POWER ON
Cause:
When detecting the actual topology, a component with a defective EEPROM was detected.
Fault value (r0949, interpret hexadecimal):
bbbbaaaa hex:
bbbb = reserved
aaaa = preliminary component number of the defective components
Remedy:
Output the fault value and remove the defected component.
201381
<location>Topology: Line Module incorrectly inserted
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840
Message value:
Component: %1, to %2, %3, connection: %4
Alarms
802
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a Line Module in the actual topology that has been incorrectly inserted with respect
to the target technology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
bb = component class (% 2)
aa = component number of the incorrectly inserted component (% 1)
Note:
The component is described in dd, cc and bb, where the component involved is incorrectly inserted.
Component class and connection number are described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
- automatically remove the topology error (p9904).
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
201381
<location>Topology: power unit incorrectly inserted
Drive object:
CU_I_840, CU_LINK, CU_NX_840, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_PN, ENC, ENC_840, HLA, HLA_840,
HUB, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM54F_MA, TM54F_SL
Message value:
Component: %1, to %2, %3, connection: %4
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a power unit in the actual topology that has been incorrectly inserted.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
bb = component class (% 2)
aa = component number of the incorrectly inserted component (% 1)
Note:
The component is described in dd, cc and bb, where the component involved is incorrectly inserted.
Component class and connection number are described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
- automatically remove the topology error (p9904).
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
201381
<location>Topology: Motor Module incorrectly inserted
Drive object:
SERVO, SERVO_840, SERVO_AC, TM41, VECTOR, VECTOR_AC
Message value:
Component: %1, to %2, %3, connection: %4
Reaction:
NONE
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
803
SINAMICS alarms
Acknowledge:
NONE
Cause:
The topology comparison has detected a Motor Module in the actual topology that has been incorrectly inserted with
respect to the target technology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
bb = component class (% 2)
aa = component number of the incorrectly inserted component (% 1)
Note:
The component is described in dd, cc and bb, where the component involved is incorrectly inserted.
Component class and connection number are described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
- automatically remove the topology error (p9904).
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
201382
<location>Topology: Sensor Module incorrectly inserted
Drive object:
All objects
Message value:
Component: %1, to %2, %3, connection: %4
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a Sensor Module in the actual topology that has been incorrectly inserted with
respect to the target technology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
bb = component class (% 2)
aa = component number of the incorrectly inserted component (% 1)
Note:
The component is described in dd, cc and bb, where the component involved is incorrectly inserted.
Component class and connection number are described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
- automatically remove the topology error (p9904).
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
201383
<location>Topology: Terminal Module incorrectly inserted
Drive object:
All objects
Message value:
Component: %1, to %2, %3, connection: %4
Reaction:
NONE
Acknowledge:
NONE
Alarms
804
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
The topology comparison has detected a Terminal Module in the actual topology that has been incorrectly inserted with
respect to the target technology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
bb = component class (% 2)
aa = component number of the incorrectly inserted component (% 1)
Note:
The component is described in dd, cc and bb, where the component involved is incorrectly inserted.
Component class and connection number are described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
- automatically remove the topology error (p9904).
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
201384
<location>Topology: DRIVE-CLiQ Hub Module incorrectly inserted
Drive object:
All objects
Message value:
Component: %1, to %2, %3, connection: %4
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a DRIVE-CLiQ Hub Module in the actual topology that has been incorrectly inserted
with respect to the target topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
bb = component class (% 2)
aa = component number of the incorrectly inserted component (% 1)
Note:
The component is described in dd, cc and bb, where the component involved is incorrectly inserted.
Component class and connection number are described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
- automatically remove the topology error (p9904).
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
201385
<location>Topology: Controller Extension incorrectly inserted
Drive object:
All objects
Message value:
Component: %1, to %2, %3, connection: %4
Reaction:
NONE
Acknowledge:
NONE
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
805
SINAMICS alarms
Cause:
The topology comparison has detected a controller extension 32 (CX32) in the actual topology that has been incorrectly
inserted with respect to the target topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
bb = component class (% 2)
aa = component number of the incorrectly inserted component (% 1)
Note:
The component is described in dd, cc and bb, where the component involved is incorrectly inserted.
Component class and connection number are described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
- automatically remove the topology error (p9904).
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
201386
<location>Topology: DRIVE-CLiQ component incorrectly inserted
Drive object:
All objects
Message value:
Component: %1, to %2, %3, connection: %4
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a DRIVE-CLiQ component in the actual topology that has been incorrectly inserted
with respect to the target topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
bb = component class (% 2)
aa = component number of the incorrectly inserted component (% 1)
Note:
The component is described in dd, cc and bb, where the component involved is incorrectly inserted.
Component class and connection number are described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
- automatically remove the topology error (p9904).
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
201389
<location>Topology: Motor with DRIVE-CLiQ incorrectly inserted
Drive object:
All objects
Message value:
Component: %1, to %2, %3, connection: %4
Reaction:
NONE
Acknowledge:
NONE
Alarms
806
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
The topology comparison has detected a motor with DRIVE-CLiQ in the actual topology that has been incorrectly inserted
with respect to the target topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
bb = component class (% 2)
aa = component number of the incorrectly inserted component (% 1)
Note:
The component is described in dd, cc and bb, where the component involved is incorrectly inserted.
Component class and connection number are described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
- automatically remove the topology error (p9904).
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
201416
<location>Topology: Component additionally inserted
Drive object:
All objects
Message value:
%1, to %2, %3, connection: %4
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has found a component in the actual topology which is not specified in the target topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = component class (% 2)
cc = connection number (%4)
bb = component class of the additional component (%1)
aa = component number (%3)
Note:
The component class of the additional component is contained in bb.
The component is described in dd, cc and aa, where the additional component is inserted.
Component class and connection number are described in F01375.
Remedy:
Adapting topologies:
- remove the additional component (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
201420
<location>Topology: Component different
Drive object:
All objects
Message value:
Component: %1, target: %2, actual: %3, difference: %4
Reaction:
NONE
Acknowledge:
NONE
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
807
SINAMICS alarms
Cause:
The topology comparison has detected differences in the actual topology and target topologies in the electronic rating plate.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex: aa = component number (%1), bb = component class of the target topology (%2), cc = component class of
the actual topology (%3), dd = difference (%4)
dd = 01 hex = 1 dec:
Different component type.
dd = 02 hex = 2 dec:
Different article number.
dd = 03 hex = 3 dec:
Different manufacturer.
dd = 04 hex = 4 dec:
For a multi-component slave, the incorrect subcomponent (index) is connected (e.g. Double Motor Module X201 instead
of X200) - or only a part of a multi-component slave is set to "deactivate and not available".
dd = 05 hex = 5 dec:
NX10 or NX15 used instead of CX32.
dd = 06 hex = 6 dec:
NX10 or NX15 used instead of CX32.
dd = 07 hex = 7 dec:
Different number of connections.
Note:
The component class is described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Adapting topologies:
- connect the expected component (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
Topology comparison - if required, adapt the comparison level:
- parameterize the topology comparison of all components (p9906).
- parameterize the topology comparison of one components (p9907, p9908).
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
201425
<location>Topology: Serial number different
Drive object:
All objects
Message value:
Component: %1, %2, differences: %3
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected differences in the actual and target topologies in relation to one component. The
serial number is different.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = reserved
cc = number of differences (%3)
bb = component class (% 2)
aa = component number (%1)
Note:
The component class is described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Alarms
808
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Remedy:
Adapting topologies:
- change over the actual topology to match the target topology.
- load the target topology that matches the actual topology (commissioning tool).
For byte cc:
cc = 1 --> can be acknowledged using p9904 or p9905.
cc > 1 --> can be acknowledged using p9905 and can be deactivated using p9906 or p9907/p9908.
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
See also: p9904, p9905, p9906, p9907, p9908
201428
<location>Topology: Incorrect connection used
Drive object:
All objects
Message value:
Component: %1, %2, connection (actual): %3, connection (target): %4
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected differences in the actual and target topologies in relation to one component. For a
component, another connection was used.
The different connections of a component are described in the alarm value.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number of the target topology (%4)
cc = connection number of the actual topology (%3)
bb = component class (% 2)
aa = component number (%1)
Note:
Component class and connection number are described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Adapting topologies:
- reinsert the DRIVE-CLiQ cable to the component (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
- automatically remove the topology error (p9904).
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
See also: p9904 (Topology comparison acknowledge differences)
201451
<location>Topology: Target topology is invalid
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
809
SINAMICS alarms
Cause:
An error was detected in the target topology.
The target topology is invalid.
Fault value (r0949, interpret hexadecimal):
ccccbbaa hex: cccc = index error, bb = component number, aa = fault cause
aa = 1B hex = 27 dec: Error not specified.
aa = 1C hex = 28 dec: Value illegal.
aa = 1D hex = 29 dec: Incorrect ID.
aa = 1E hex = 30 dec: Incorrect ID length.
aa = 1F hex = 31 dec: Too few indices left.
aa = 20 hex = 32 dec: component not connected to Control Unit.
Remedy:
Download the target topology again using the commissioning tool.
201481
<location>Topology: power unit not connected
Drive object:
CU_I_840, CU_LINK, CU_NX_840, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_PN, ENC, ENC_840, HLA, HLA_840,
HUB, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM54F_MA, TM54F_SL
Message value:
Component: %1, to %2, %3, connection: %4
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a power unit that is missing in the actual topology with respect to the target topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
bb = component class (% 2)
aa = component number of the component that has not been inserted (% 1)
Note:
The component is described in dd, cc and bb, where the component has not been inserted.
Component class and connection number are described in F01375.
Remedy:
Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
Check the hardware:
- check the 24 V supply voltage.
- check DRIVE-CLiQ cables for interruption and contact problems.
- check that the component is working properly.
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
201481
<location>Topology: Line Module not connected
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840
Message value:
Component: %1, to %2, %3, connection: %4
Reaction:
NONE
Acknowledge:
NONE
Alarms
810
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
The topology comparison has detected a Line Module that is missing in the actual topology with respect to the target
topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
bb = component class (% 2)
aa = component number of the component that has not been inserted (% 1)
Note:
The component is described in dd, cc and bb, where the component has not been inserted.
Component class and connection number are described in F01375.
Remedy:
Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
Check the hardware:
- check the 24 V supply voltage.
- check DRIVE-CLiQ cables for interruption and contact problems.
- check that the component is working properly.
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
201481
<location>Topology: Motor Module not connected
Drive object:
SERVO, SERVO_840, SERVO_AC, TM41, VECTOR, VECTOR_AC
Message value:
Component: %1, to %2, %3, connection: %4
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a Motor Module that is missing in the actual topology with respect to the target
topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
bb = component class (% 2)
aa = component number of the component that has not been inserted (% 1)
Note:
The component is described in dd, cc and bb, where the component has not been inserted.
Component class and connection number are described in F01375.
Remedy:
Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
Check the hardware:
- check the 24 V supply voltage.
- check DRIVE-CLiQ cables for interruption and contact problems.
- check that the component is working properly.
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
201482
<location>Topology: Sensor Module not connected
Drive object:
All objects
Message value:
Component: %1, to %2, %3, connection: %4
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
811
SINAMICS alarms
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a Sensor Module that is missing in the actual topology with respect to the target
topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
bb = component class (% 2)
aa = component number of the component that has not been inserted (% 1)
Note:
The component is described in dd, cc and bb, where the component has not been inserted.
Component class and connection number are described in F01375.
Remedy:
Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
Check the hardware:
- check the 24 V supply voltage.
- check DRIVE-CLiQ cables for interruption and contact problems.
- check that the component is working properly.
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
201483
<location>Topology: Terminal Module not connected
Drive object:
All objects
Message value:
Component: %1, to %2, %3, connection: %4
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a Terminal Module that is missing in the actual topology with respect to the target
topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
bb = component class (% 2)
aa = component number of the component that has not been inserted (% 1)
Note:
The component is described in dd, cc and bb, where the component has not been inserted.
Component class and connection number are described in F01375.
Remedy:
Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
Check the hardware:
- check the 24 V supply voltage.
- check DRIVE-CLiQ cables for interruption and contact problems.
- check that the component is working properly.
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
Alarms
812
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
201484
<location>Topology: DRIVE-CLiQ Hub Module not connected
Drive object:
All objects
Message value:
Component: %1, to %2, %3, connection: %4
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a DRIVE-CLiQ Hub Module missing in the actual topology with respect to the target
topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
bb = component class (% 2)
aa = component number of the component that has not been inserted (% 1)
Note:
The component is described in dd, cc and bb, where the component has not been inserted.
Component class and connection number are described in F01375.
Remedy:
Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
Check the hardware:
- check the 24 V supply voltage.
- check DRIVE-CLiQ cables for interruption and contact problems.
- check that the component is working properly.
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
201485
<location>Topology: Controller Extension not connected
Drive object:
All objects
Message value:
Component: %1, to %2, %3, connection: %4
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a Control Extension (CX32) missing in the actual topology with respect to the target
topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
bb = component class (% 2)
aa = component number of the component that has not been inserted (% 1)
Note:
The component is described in dd, cc and bb, where the component has not been inserted.
Component class and connection number are described in F01375.
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
813
SINAMICS alarms
Remedy:
Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
Check the hardware:
- check the 24 V supply voltage.
- check DRIVE-CLiQ cables for interruption and contact problems.
- check that the component is working properly.
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
201486
<location>Topology: DRIVE-CLiQ component not connected
Drive object:
All objects
Message value:
Component: %1, to %2, %3, connection: %4
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a DRIVE-CLiQ component missing in the actual topology with respect to the target
topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
bb = component class (% 2)
aa = component number of the component that has not been inserted (% 1)
Note:
The component is described in dd, cc and bb, where the component has not been inserted.
Component class and connection number are described in F01375.
Remedy:
Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
Check the hardware:
- check the 24 V supply voltage.
- check DRIVE-CLiQ cables for interruption and contact problems.
- check that the component is working properly.
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
201487
<location>Topology: Option slot component not inserted
Drive object:
All objects
Message value:
Component: %1, to %2, %3, connection: %4
Reaction:
NONE
Acknowledge:
NONE
Alarms
814
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
The topology comparison has detected an option slot component missing in the actual topology with respect to the target
topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
bb = component class (% 2)
aa = component number of the component that has not been inserted (% 1)
Note:
The component is described in dd, cc and bb, where the component has not been inserted.
Component class and connection number are described in F01375.
Remedy:
Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
Check the hardware:
- check the 24 V supply voltage.
- check DRIVE-CLiQ cables for interruption and contact problems.
- check that the component is working properly.
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
201489
<location>Topology: motor with DRIVE-CLiQ not connected
Drive object:
All objects
Message value:
Component: %1, to %2, %3, connection: %4
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a motor with DRIVE-CLiQ missing in the actual topology with respect to the target
topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
bb = component class (% 2)
aa = component number of the component that has not been inserted (% 1)
Note:
The component is described in dd, cc and bb, where the component has not been inserted.
Component class and connection number are described in F01375.
Remedy:
Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
Check the hardware:
- check the 24 V supply voltage.
- check DRIVE-CLiQ cables for interruption and contact problems.
- check that the component is working properly.
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
201507
<location>BICO: Interconnections to inactive objects present
Drive object:
All objects
Message value:
%1
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
815
SINAMICS alarms
Reaction:
NONE
Acknowledge:
NONE
Cause:
There are BICO interconnections to an inactive/inoperable drive object.
The BI/CI parameters involved are listed in r9498.
The associated BO/CO parameters are listed in r9499.
The list of the BICO interconnections to other drive objects is displayed in r9491 and r9492 of the deactivated drive object.
Note:
r9498 and r9499 are only written to, if p9495 is not set to 0.
Alarm value (r2124, interpret decimal):
Number of BICO interconnections found to inactive drive objects.
Remedy:
- set all open BICO interconnections centrally to the factory setting with p9495 = 2.
- make the non-operational drive object active/operational again (re-insert or activate components).
201508
<location>BICO: Interconnections to inactive objects exceeded
Drive object:
All objects
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The maximum number of BICO interconnections (signal sinks) when deactivating a drive object was exceeded.
When deactivating a drive object, all BICO interconnections (signal sinks) are listed in the following parameters:
- r9498[0...29]: List of the BI/CI parameters involved.
- r9499[0...29]: List of the associated BO/CO parameters.
Remedy:
Not necessary.
This alarm is automatically withdrawn as soon as no BICO interconnection is entered in r9498[29] and r9499[29] (value =
0).
Notice:
When re-activating the drive object, all BICO interconnections should be checked and if required, re-established.
201510
<location>BICO: Signal source is not float type
Drive object:
All objects
Message value:
Parameter: %1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The requested connector output does not have the correct data type. This interconnection is not established.
Fault value (r0949, interpret decimal):
Parameter number to which an interconnection should be made (connector output).
Remedy:
Interconnect this connector input with a connector output having a float data type.
201511
<location>BICO: Interconnection with different scalings
Drive object:
All objects
Message value:
Parameter: %1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Alarms
816
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
The requested BICO interconnection was established. However, a conversion is made between the BICO output and BICO
input using the reference values.
- the BICO output has different normalized units than the BICO input.
- message only for interconnections within a drive object.
Example:
The BICO output has, as normalized unit, voltage and the BICO input has current.
This means that the factor p2002/p2001 is calculated between the BICO output and the BICO input.
p2002: contains the reference value for current
p2001: contains the reference value for voltage
Fault value (r0949, interpret decimal):
Parameter number of the BICO input (signal sink).
Remedy:
Not necessary.
201512
<location>BICO: No scaling available
Drive object:
All objects
Message value:
%1
Reaction:
Infeed: OFF2 (OFF1)
Servo: OFF2
Vector: OFF2
Hla: OFF2
Acknowledge:
POWER ON
Cause:
An attempt was made to determine a conversion factor for a scaling that does not exist.
Fault value (r0949, interpret decimal):
Unit (e.g. corresponding to SPEED) for which an attempt was made to determine a factor.
Remedy:
Apply scaling or check the transfer value.
201513
<location>BICO: Interconnection cross DO with different scalings
Drive object:
All objects
Message value:
Parameter: %1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The requested BICO interconnection was established. However, a conversion is made between the BICO output and BICO
input using the reference values.
An interconnection is made between different drive objects and the BICO output has different normalized units than the
BICO input or the normalized units are the same but the reference values are different.
Example 1:
BICO output with voltage normalized unit, BICO input with current normalized unit, BICO output and BICO input lie in
different drive objects. This means that the factor p2002/p2001 is calculated between the BICO output and the BICO input.
p2002: contains the reference value for current
p2001: contains the reference value for voltage
Example 2:
BICO output with voltage normalized unit in drive object 1 (DO1), BICO input with voltage normalized unit in drive object
2 (DO2). The reference values for voltage (p2001) of the two drive objects have different values. This means that the factor
p2001(DO1)/p2001(DO2) is calculated between the BICO output and the BICO input.
p2001: contains the reference value for voltage, drive objects 1, 2
Fault value (r0949, interpret decimal):
Parameter number of the BICO input (signal sink).
Remedy:
Not necessary.
201514
<location>BICO: Error when writing during a reconnect
Drive object:
All objects
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
817
SINAMICS alarms
Message value:
Parameter: %1
Reaction:
NONE
Acknowledge:
NONE
Cause:
During a reconnect operation (e.g. while booting or downloading - but can also occur in normal operation) a parameter was
not able to be written to.
Example:
When writing to BICO input with double word format (DWORD), in the second index, the memory areas overlap (e.g. p8861).
The parameter is then reset to the factory setting.
Alarm value (r2124, interpret decimal):
Parameter number of the BICO input (signal sink).
Remedy:
Not necessary.
201515
<location>BICO: Writing to parameter not permitted as the master control is active
Drive object:
All objects
Message value:
-
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
When changing the number of CDS or when copying from CDS, the master control is active.
Remedy:
If required, return the master control and repeat the operation.
201590
<location>Drive: Motor maintenance interval expired
Drive object:
All objects
Message value:
Fault cause: %1 bin
Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected service/maintenance interval for this motor was reached.
Alarm value (r2124, interpret decimal):
Motor data set number.
See also: p0650 (Actual motor operating hours), p0651 (Motor operating hours maintenance interval)
Remedy:
carry out service/maintenance and reset the service/maintenance interval (p0651).
201600
<location>SI P1 (CU): STOP A initiated
Drive object:
HLA, HLA_840
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive-integrated "Safety Integrated" function on the Control Unit (CU) has detected a fault and initiated a STOP A (STO
via the safety switch-off signal path of the Control Unit).
- forced checking procedure (test stop) of the safety switch-off signal path of the Control Unit unsuccessful.
- subsequent response to fault F01611 (defect in a monitoring channel).
Fault value (r0949, interpret decimal):
0: Stop request from monitoring channel 2.
1005: STO active although STO not selected and there is no internal STOP A present.
1010: STO inactive although STO is selected or an internal STOP A is present.
9999: Subsequent response to fault F01611.
Alarms
818
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Remedy:
- select Safe Torque Off and deselect again.
- replace Hydraulic Module involved.
For fault value = 9999:
- carry out diagnostics for fault F01611.
Note:
CU: Control Unit
SI: Safety Integrated
STO: Safe Torque Off / SH: Safe standstill
201600
<location>SI P1 (CU): STOP A initiated
Drive object:
SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive-integrated "Safety Integrated" function on the Control Unit (CU) has detected a fault and initiated a STOP A (STO
via the safety switch-off signal path of the Control Unit).
- forced checking procedure (test stop) of the safety switch-off signal path of the Control Unit unsuccessful.
- subsequent response to fault F01611 (defect in a monitoring channel).
Fault value (r0949, interpret decimal):
0: Stop request from monitoring channel 2.
1005:
- STO active, although STO not selected and there is no internal STOP A active.
- For a Power Module with "STO via terminals at the Power Module" (STO_A/STO_B), these terminals are active (DIP switch
to "ON"). However, the "STO via terminals at the Power Module" function has not been enabled (p9601.7 = p9801.7 = 0).
1010: STO inactive although STO is selected or an internal STOP A is present.
1015: Feedback signal of STO for Motor Modules connected in parallel are different.
9999: Subsequent response to fault F01611.
Remedy:
- select Safe Torque Off and deselect again.
- replace the Motor Module involved.
For fault value = 1005:
- deactivate terminals STO_A/STO_B on the Power Module (set both DIP-switches to "OFF") or enable the "STO via terminals
at the Power Module" function.
For fault value = 9999:
- carry out diagnostics for fault F01611.
Note:
CU: Control Unit
MM: Motor Module
SI: Safety Integrated
STO: Safe Torque Off / SH: Safe standstill
201611
<location>SI P1 (CU): Defect in a monitoring channel
Drive object:
HLA, HLA_840
Message value:
%1
Reaction:
NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY (POWER ON)
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
819
SINAMICS alarms
Cause:
The drive-integrated "Safety Integrated" function on processor 1 has detected a fault in the data cross-check between the
two monitoring channels and has initiated a STOP F.
As a result of this fault, after the parameterized transition has expired (p9658), fault F01600 (SI CU: STOP A initiated) is
output.
Fault value (r0949, interpret decimal):
0: Stop request from another monitoring channel.
1 ... 999:
Number of the cross-compared data that resulted in this fault. This number is also displayed in r9795.
1: SI monitoring clock cycle (r9780, r9880).
2: SI enable safety functions (p9601, p9801). Crosswise data comparison is only carried out for the supported bits.
3: SI SGE changeover discrepancy time (p9650, p9850).
4: SI transition period STOP F to STOP A (p9658, p9858).
6: SI Motion enable, safety-relevant functions (p9501, internal value).
7: SI delay time of STO for Safe Stop 1 (p9652, p9852).
8: SI PROFIsafe address (p9610, p9810).
9: SI debounce time for STO/SBC/SS1 (p9651, p9851).
10: SI delay time for initiating STO for ESR (p9697, p9897).
11: SI HLA shutoff valve feedback signal contact configuration (p9626, p9826).
12: SI HLA shutoff valve wait time switch-on (p9625[0], p9825[0]).
13: SI HLA shutoff valve wait time switch-off (p9625[1], p9825[1]).
14: SI PROFIsafe telegram selection (p9611, p9811).
15: SI PROFIsafe bus failure response (p9612, p9812).
1000: Watchdog timer has expired.
Within the time of approx. 5 x p9650, alternatively, the following was defined:
- the signal at terminal STO of the Hydraulic Module continually changed with time intervals less than or equal to the
discrepancy time (p9650/p9850).
- via PROFIsafe/TM54F, STO (also as subsequent response) was continually selected and deselected with time intervals less
than or equal to the discrepancy time (p9650/p9850).
1001, 1002: Initialization error, change timer / check timer.
1900: CRC error in the SAFETY sector.
1901: CRC error in the ITCM sector.
1902: Overloading in the ITCM sector has occurred in operation.
1903: Internal parameterizing error for CRC calculation.
1950: Module temperature outside the permissible temperature range.
1951: Module temperature not plausible.
2000: Status of the STO selection for both monitoring channels different.
2001: Feedback signal of STO shutdown for both monitoring channels different.
2002: Status of the delay timer SS1 for both monitoring channels different (status of the timer in p9650/p9850).
2003: Status of the STO terminal for both monitoring channels different.
6000 ... 6999:
Error in the PROFIsafe control.
For these fault values, the failsafe control signals (Failsafe Values) are transferred to the safety functions. If "STOP B after
failure of the PROFIsafe communication" (p9612) is parameterized, the transfer of the Failsafe Values is delayed.
6000: A fatal PROFIsafe communication error has occurred.
6064 ... 6071: error when evaluating the F parameter. The values of the transferred F parameters do not match the expected
values in the PROFIsafe driver.
6064: Destination address and PROFIsafe address are different (F_Dest_Add).
6065: Destination address not valid (F_Dest_Add).
6066: Source address not valid (F_Source_Add).
6067: Watchdog time not valid (F_WD_Time).
6068: Incorrect SIL level (F_SIL).
6069: Incorrect F-CRC length (F_CRC_Length).
6070: Incorrect F parameter version (F_Par_Version).
Alarms
820
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
6071: CRC error for the F parameters (CRC1). The transferred CRC value of the F parameters does not match the value
calculated in the PROFIsafe driver.
6072: F parameterization is inconsistent.
6165: A communications error was identified when receiving the PROFIsafe telegram. The fault may also occur if an
inconsistent or out-of-date PROFIsafe telegram has been received after switching the Control Unit off and on or after
plugging in the PROFIBUS/PROFINET cable.
6166: A time monitoring error (timeout) was identified when receiving the PROFIsafe telegram.
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
821
SINAMICS alarms
Remedy:
For fault value = 1 ... 5 and 7 ... 999:
- check the cross data comparison that resulted in a STOP F.
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade the Hydraulic Module software.
- upgrade the Control Unit software.
For fault value = 6:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade the Hydraulic Module software.
- upgrade the Control Unit software.
For fault value = 1000:
- check the STO terminal at the Hydraulic Module (contact problems).
- PROFIsafe: Remove contact problems/faults at the PROFIBUS master/PROFINET controller.
- check the wiring of the failsafe inputs at the TM54F (contact problems).
- check the discrepancy time, and if required, increase the value (p9650/p9850).
For fault value = 1001, 1002:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade the Hydraulic Module software.
- upgrade the Control Unit software.
For fault value = 1900, 1901, 1902:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade the Control Unit software.
- replace Control Unit.
For fault value = 2000, 2001, 2002, 2003:
- check the discrepancy time, and if required, increase the value (p9650/p9850, p9652/p9852).
- check the wiring of the safety-relevant inputs (SGE) (contact problems).
- check the causes of the STO selection in r9772. When the SMM functions are active (p9501 = 1), STO can also be selected
using these functions.
- replace Hydraulic Module involved.
Note:
This fault can be acknowledged after removing the cause of the error and after correct selection/deselection of STO.
For fault value = 6000:
- carry out a POWER ON (switch-off/switch-on) for all components.
- check whether there is a DRIVE-CLiQ communication error between the two monitoring channels and, if required, carry out
a diagnostics routine for the faults identified.
- increase the monitoring cycle clock settings (p9500, p9511).
- upgrade firmware to later version.
- contact Technical Support.
- replace the Control Unit.
For fault value = 6064:
- check the setting of the value in the F parameter F_Dest_Add at the PROFIsafe slave.
- check the setting of the PROFIsafe address of the Control Unit (p9610) and that of the hydraulic module (p9810).
For fault value = 6065:
- check the setting of the value in the F parameter F_Dest_Add at the PROFIsafe slave. It is not permissible for the destination
address to be either 0 or FFFF!
For fault value = 6066:
- check the setting of the value in the F parameter F_Source_Add at the PROFIsafe slave. It is not permissible for the source
address to be either 0 or FFFF!
For fault value = 6067:
- check the setting of the value in the F parameter F_WD_Time at the PROFIsafe slave. It is not permissible for the watch time
to be 0!
For fault value = 6068:
- check the setting of the value in the F parameter F_SIL at the PROFIsafe slave. The SIL level must correspond to SIL2!
For fault value = 6069:
Alarms
822
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
- check the setting of the value in the F parameter F_CRC_Length at the PROFIsafe slave. The setting of the CRC2 length is
2-byte CRC in the V1 mode and 3-byte CRC in the V2 mode!
For fault value = 6070:
- check the setting of the value in the F parameter F_Par_Version at the PROFIsafe slave. The value for the F parameter version
is 0 in the V1 mode and 1 in the V2 mode!
For fault value = 6071:
- check the settings of the values of the F parameters and the F parameter CRC (CRC1) calculated from these at the PROFIsafe
slave and, if required, update.
For fault value = 6072:
- check the settings of the values for the F parameters and, if required, correct.
The following combinations are permissible for F parameters F_CRC_Length and F_Par_Version:
F_CRC_Length = 2-byte CRC and F_Par_Version = 0
F_CRC_Length = 3-byte CRC and F_Par_Version = 1
For fault value = 6165:
- if the fault occurs after powering up the Control Unit or after plugging in the PROFIBUS/PROFINET cable, acknowledge the
fault.
- check the configuration and communication at the PROFIsafe slave.
- check the setting of the value for F parameter F_WD_Time on the PROFIsafe slave and increase if necessary.
- check whether there is a DRIVE-CLiQ communication error between the two monitoring channels and, if required, carry out
a diagnostics routine for the faults identified.
- check whether all F parameters of the drive match the F parameters of the F host.
For fault value = 6166:
- check the configuration and communication at the PROFIsafe slave.
- check the setting of the value for F parameter F_WD_Time on the PROFIsafe slave and increase if necessary.
- evaluate diagnostic information in the F host.
- check PROFIsafe connection.
- check whether all F parameters of the drive match the F parameters of the F host.
Note:
CU: Control Unit
EP: Enable Pulses (pulse enable)
ESR: Extended Stop and Retract
MM: Motor Module
SGE: Safety-relevant input
SI: Safety Integrated
SMM: Safe Motion Monitoring
SS1: Safe Stop 1 (corresponds to Stop Category 1 acc. to EN60204)
STO: Safe Torque Off / SH: Safe standstill
201611
<location>SI P1 (CU): Defect in a monitoring channel
Drive object:
SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY (POWER ON)
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
823
SINAMICS alarms
Cause:
The drive-integrated "Safety Integrated" function on processor 1 has detected a fault in the data cross-check between the
two monitoring channels and has initiated a STOP F.
As a result of this fault, after the parameterized transition has expired (p9658), fault F01600 (SI CU: STOP A initiated) is
output.
Fault value (r0949, interpret decimal):
0: Stop request from another monitoring channel.
1 ... 999:
Number of the cross-compared data that resulted in this fault. This number is also displayed in r9795.
1: SI monitoring clock cycle (r9780, r9880).
2: SI enable safety functions (p9601, p9801). Crosswise data comparison is only carried out for the supported bits.
3: SI SGE changeover discrepancy time (p9650, p9850).
4: SI transition period STOP F to STOP A (p9658, p9858).
5: SI enable Safe Brake Control (p9602, p9802).
6: SI Motion enable, safety-relevant functions (p9501, internal value).
7: SI delay time of STO for Safe Stop 1 (p9652, p9852).
8: SI PROFIsafe address (p9610, p9810).
9: SI debounce time for STO/SBC/SS1 (p9651, p9851).
10: SI delay time for initiating STO for ESR (p9697, p9897).
11: SI Safe Brake Adapter mode, BICO interconnection (p9621, p9821).
12: SI Safe Brake Adapter relay ON time (p9622[0], p9822[0]).
13: SI Safe Brake Adapter relay OFF time (p9622[1], p9822[1]).
14: SI PROFIsafe telegram selection (p9611, p9811).
15: SI PROFIsafe bus failure response (p9612, p9812).
1000: Watchdog timer has expired.
Within the time of approx. 5 x p9650, alternatively, the following was defined:
- the signal at terminal EP of the Motor Module continually changed with time intervals less than or equal to the discrepancy
time (p9650/p9850).
- via PROFIsafe/TM54F, STO (also as subsequent response) was continually selected and deselected with time intervals less
than or equal to the discrepancy time (p9650/p9850).
- safe pulse cancellation (r9723.9 - also as subsequent response) was continually selected and deselected with time intervals
less than or equal to the discrepancy time (p9650/p9850).
1001, 1002: Initialization error, change timer / check timer.
1900: CRC error in the SAFETY sector.
1901: CRC error in the ITCM sector.
1902: Overloading in the ITCM sector has occurred in operation.
1903: Internal parameterizing error for CRC calculation.
1950: Module temperature outside the permissible temperature range.
1951: Module temperature not plausible.
2000: Status of the STO selection for both monitoring channels different.
2001: Feedback signal of STO shutdown for both monitoring channels different. This value can also subsequently occur as
a result of other faults.
2002: Status of the delay timer SS1 for both monitoring channels different (status of the timer in p9650/p9850).
2003: Status of the STO terminal for both monitoring channels different.
2004: Status of the STO selection for Motor Modules connected in parallel different.
2005: Feedback signal of the safe pulse suppression on the Control Unit and Motor Modules connected in parallel different.
6000 ... 6999:
Error in the PROFIsafe control.
For these fault values, the failsafe control signals (Failsafe Values) are transferred to the safety functions. If "STOP B after
failure of the PROFIsafe communication" (p9612) is parameterized, the transfer of the Failsafe Values is delayed.
6000: A fatal PROFIsafe communication error has occurred.
6064 ... 6071: error when evaluating the F parameter. The values of the transferred F parameters do not match the expected
values in the PROFIsafe driver.
6064: Destination address and PROFIsafe address are different (F_Dest_Add).
6065: Destination address not valid (F_Dest_Add).
Alarms
824
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
6066: Source address not valid (F_Source_Add).
6067: Watchdog time not valid (F_WD_Time).
6068: Incorrect SIL level (F_SIL).
6069: Incorrect F-CRC length (F_CRC_Length).
6070: Incorrect F parameter version (F_Par_Version).
6071: CRC error for the F parameters (CRC1). The transferred CRC value of the F parameters does not match the value
calculated in the PROFIsafe driver.
6072: F parameterization is inconsistent.
6165: A communications error was identified when receiving the PROFIsafe telegram. The fault may also occur if an
inconsistent or out-of-date PROFIsafe telegram has been received after switching the Control Unit off and on or after
plugging in the PROFIBUS/PROFINET cable.
6166: A time monitoring error (timeout) was identified when receiving the PROFIsafe telegram.
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
825
SINAMICS alarms
Remedy:
For fault value = 1 ... 5 and 7 ... 999:
- check the cross data comparison that resulted in a STOP F.
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade the Motor Module software.
- upgrade the Control Unit software.
For fault value = 6:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade the Motor Module software.
- upgrade the Control Unit software.
For fault value = 1000:
- check the EP terminal at the Motor Module (contact problems).
- PROFIsafe: Remove contact problems/faults at the PROFIBUS master/PROFINET controller.
- check the wiring of the failsafe inputs at the TM54F (contact problems).
- check the discrepancy time, and if required, increase the value (p9650/p9850).
For fault value = 1001, 1002:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade the Motor Module software.
- upgrade the Control Unit software.
For fault value = 1900, 1901, 1902:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade the Control Unit software.
- replace Control Unit.
For fault value = 2000, 2001, 2002, 2003, 2004, 2005:
- check the discrepancy time, and if required, increase the value (p9650/p9850, p9652/p9852).
- check the wiring of the safety-relevant inputs (SGE) (contact problems).
- check the causes of the STO selection in r9772. When the SMM functions are active (p9501 = 1), STO can also be selected
using these functions.
- replace the Motor Module involved.
- diagnose the other active faults and resolve the causes.
Note:
This fault can be acknowledged after removing the cause of the error and after correct selection/deselection of STO.
For fault value = 6000:
- carry out a POWER ON (switch-off/switch-on) for all components.
- check whether there is a DRIVE-CLiQ communication error between the two monitoring channels and, if required, carry out
a diagnostics routine for the faults identified.
- increase the monitoring cycle clock settings (p9500, p9511).
- upgrade firmware to later version.
- contact Technical Support.
- replace the Control Unit.
For fault value = 6064:
- check the setting of the value in the F parameter F_Dest_Add at the PROFIsafe slave.
- check the setting of the PROFIsafe address of the Control Unit (p9610) and that of the Motor Module (p9810).
For fault value = 6065:
- check the setting of the value in the F parameter F_Dest_Add at the PROFIsafe slave. It is not permissible for the destination
address to be either 0 or FFFF!
For fault value = 6066:
- check the setting of the value in the F parameter F_Source_Add at the PROFIsafe slave. It is not permissible for the source
address to be either 0 or FFFF!
For fault value = 6067:
- check the setting of the value in the F parameter F_WD_Time at the PROFIsafe slave. It is not permissible for the watch time
to be 0!
For fault value = 6068:
- check the setting of the value in the F parameter F_SIL at the PROFIsafe slave. The SIL level must correspond to SIL2!
Alarms
826
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
For fault value = 6069:
- check the setting of the value in the F parameter F_CRC_Length at the PROFIsafe slave. The setting of the CRC2 length is
2-byte CRC in the V1 mode and 3-byte CRC in the V2 mode!
For fault value = 6070:
- check the setting of the value in the F parameter F_Par_Version at the PROFIsafe slave. The value for the F parameter version
is 0 in the V1 mode and 1 in the V2 mode!
For fault value = 6071:
- check the settings of the values of the F parameters and the F parameter CRC (CRC1) calculated from these at the PROFIsafe
slave and, if required, update.
For fault value = 6072:
- check the settings of the values for the F parameters and, if required, correct.
The following combinations are permissible for F parameters F_CRC_Length and F_Par_Version:
F_CRC_Length = 2-byte CRC and F_Par_Version = 0
F_CRC_Length = 3-byte CRC and F_Par_Version = 1
For fault value = 6165:
- if the fault occurs after powering up the Control Unit or after plugging in the PROFIBUS/PROFINET cable, acknowledge the
fault.
- check the configuration and communication at the PROFIsafe slave.
- check the setting of the value for F parameter F_WD_Time on the PROFIsafe slave and increase if necessary.
- check whether there is a DRIVE-CLiQ communication error between the two monitoring channels and, if required, carry out
a diagnostics routine for the faults identified.
- check whether all F parameters of the drive match the F parameters of the F host.
For fault value = 6166:
- check the configuration and communication at the PROFIsafe slave.
- check the setting of the value for F parameter F_WD_Time on the PROFIsafe slave and increase if necessary.
- evaluate diagnostic information in the F host.
- check PROFIsafe connection.
- check whether all F parameters of the drive match the F parameters of the F host.
Note:
CU: Control Unit
EP: Enable Pulses (pulse enable)
ESR: Extended Stop and Retract
MM: Motor Module
SGE: Safety-relevant input
SI: Safety Integrated
SMM: Safe Motion Monitoring
SS1: Safe Stop 1
STO: Safe Torque Off / SH: Safe standstill
201612
<location>SI P1 (CU): STO inputs for power units connected in parallel different
Drive object:
SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
Fault cause: %1 bin
Reaction:
NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive-integrated "Safety Integrated" function on the Control Unit (CU) has identified different states of the AND'ed STO
inputs for power units connected in parallel and has initiated a STOP F.
As a result of this fault, after the parameterized transition has expired (p9658), fault F01600 (SI CU: STOP A initiated) is
output.
Fault value (r0949, interpret binary):
Binary image of the digital inputs of the Control Unit that are used as signal source for the function "Safe Torque Off".
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
827
SINAMICS alarms
Remedy:
- check the tolerance time SGE changeover and if required, increase the value (p9650).
- check the wiring of the safety-relevant inputs (SGE) (contact problems).
Note:
CU: Control Unit
SGE: Safety-relevant input
SI: Safety Integrated
STO: Safe Torque Off / SH: Safe standstill
201620
<location>SI P1 (CU): Safe Torque Off active
Drive object:
HLA, HLA_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The "Safe Torque Off" (STO) function of the basic functions has been selected on the Control Unit (CU) using the input
terminal and is active.
Note:
- this message does not result in a safety stop response.
- this message is not output when STO is selected using the Extended Functions.
Remedy:
Not necessary.
Note:
CU: Control Unit
SI: Safety Integrated
STO: Safe Torque Off / SH: Safe standstill
201621
<location>SI P1 (CU): Safe Stop 1 active
Drive object:
HLA, HLA_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The "Safe Stop 1" (SS1) function has been selected on the Control Unit (CU) and is active.
Note:
This message does not result in a safety stop response.
Remedy:
Not necessary.
Note:
CU: Control Unit
SI: Safety Integrated
SS1: Safe Stop 1
201625
<location>SI P1 (CU): Sign-of-life error in safety data
Drive object:
HLA, HLA_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive-integrated "Safety Integrated" function on the Control Unit (CU) has detected an error in the sign-of-life of the
safety data between the two monitoring channels and has initiated a STOP A.
- there is either a DRIVE-CLiQ communication error or communication has failed.
- a time slice overflow of the safety software has occurred.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Alarms
828
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Remedy:
- select STO and then deselect again.
- carry out a POWER ON (switch-off/switch-on) for all components.
- check whether there is a DRIVE-CLiQ communication error between the two monitoring channels and, if required, carry out
a diagnostics routine for the faults identified.
- deselect all drive functions that are not absolutely necessary.
- reduce the number of drives.
- check the electrical cabinet design and cable routing for EMC compliance
Note:
CU: Control Unit
MM: Motor Module
SI: Safety Integrated
STO: Safe Torque Off
201630
<location>SI P1 (CU): Brake control error
Drive object:
SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive-integrated "Safety Integrated" function on the Control Unit (CU) has detected a brake control fault and initiated
a STOP A.
- motor cable is not shielded correctly.
- defect in the brake control circuit of the Motor Module.
Fault value (r0949, interpret decimal):
10, 11:
Fault in "open holding brake" operation.
- parameter p1278 incorrectly set.
- no brake connected or wire breakage (check whether brake releases for p1278 = 1 and p9602/p9802 = 0 (SBC
deactivated)).
- ground fault in brake cable.
20:
Fault in "brake open" state.
- short-circuit in brake winding.
30, 31:
Fault in "close holding brake" operation.
- no brake connected or wire breakage (check whether brake releases for p1278 = 1 and p9602/p9802 = 0 (SBC
deactivated)).
- short-circuit in brake winding.
40:
Fault in "brake closed" state.
50:
Fault in the brake control circuit of the Control Unit or communication fault between the Control Unit and Motor Module
(brake control diagnostics).
80:
Safe Brake Adapter.
Fault in the brake control circuit of the Control Unit or communication fault between the Control Unit and Motor Module
(brake control diagnostics).
90:
Brake released for service purposes (X4).
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
829
SINAMICS alarms
Remedy:
- check parameter p1278 (for SBC, only p1278 = 0 is permissible).
- for a parallel connection, check the setting of the power unit data set to control the holding brake (p7015).
- select Safe Torque Off and deselect again.
- check the motor holding brake connection.
- check the function of the motor holding brake.
- check whether there is a DRIVE-CLiQ communication error between the Control Unit and the Motor Module involved and,
if required, carry out a diagnostics routine for the faults identified.
- check that the electrical cabinet design and cable routing are in compliance with EMC regulations (e.g. shield of the motor
cable and brake conductors are connected with the shield connecting plate and the motor connectors are tightly screwed
to the housing).
- replace the Motor Module involved.
Operation with Safe Brake Module or Safe Brake Adapter:
- check the Safe Brake Module or Safe Brake Adapter connection.
- Replace the Safe Brake Module or Safe Brake Adapter.
Note:
CU: Control Unit
SBC: Safe Brake Control
SI: Safety Integrated
201631
<location>SI P1 (CU): motor holding brake/SBC configuration not practical
Drive object:
SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
A configuration of motor holding brake and SBC was detected that is not practical.
The following configurations can result in this message:
- "No motor holding brake available" (p1215 = 0) and "SBC" enabled (p9602 = 1).
- "Motor holding brake just like the sequence control, connection via BICO" (p1215 = 3) and "SBC" enabled (p9602 = 1).
Remedy:
Check the parameterization of the motor holding brake and SBC and correct.
Note:
SBC: Safe Brake Control
See also: p1215, p9602, p9802
201632
<location>SI P1 (CU): shutoff valve control/feedback signal error
Drive object:
HLA, HLA_840
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Alarms
830
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
The drive-integrated "Safety Integrated" function on the Control Unit (monitoring channel 1) has detected a fault for the
control/feedback signal of the shutoff valve and initiated a STOP A.
Possible causes:
- shutoff valve either not connected or not correctly connected (X272).
- feedback signal of the shutoff valve either not connected or not correctly connected (X281/X282).
- feedback signal of the shutoff valve incorrectly set (p9626/p9826).
- shutoff valve defective.
- Hydraulic Module defective.
Fault value (r0949, interpret decimal):
10, 11:
Fault in the "Open shutoff valve" operation.
20:
Fault in the "Shutoff valve open" state.
30, 31:
Fault in the "Close shutoff valve" operation.
40:
Fault in the "Shutoff valve closed" state.
50, 80:
Fault in the control/feedback signal of the cutoff valve or communication error between the Control Unit and the Hydraulic
Module.
Remedy:
- check the shutoff valve connection (X272).
- check the feedback signals of the shutoff valve (X281, X282).
- check the configuration of the feedback signals of the shutoff valve (p9626/p9826).
- check for EMC-compliant control cabinet design and cable routing (e.g. use shielded cables and connect the shield).
- if necessary, replace the shutoff valve.
- if necessary, replace the Hydraulic Module.
See also: p9626 (SI HLA shutoff valve feedback signal contact configuration (CU)), p9826 (SI HLA shutoff valve feedback
signal contact configuration (MM))
201637
<location>SI: Safety password not assigned
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, ENC, ENC_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO,
SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR,
VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
Safety Integrated is parameterized and enabled. However, a valid safety password has still not been entered.
Remedy:
- assign a valid safety password.
- carry out data save.
201638
<location>SI: Safety password entered
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, ENC, ENC_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO,
SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR,
VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
A valid safety password has been entered. It is possible to change safety parameters in the safety commissioning mode.
Remedy:
Not necessary.
This alarm is automatically withdrawn with "Delete password" (e.g. after exiting the web server - or after a Power on). The
password remains assigned.
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
831
SINAMICS alarms
201640
<location>SI P1 (CU): component replacement identified and acknowledgment/save required
Drive object:
HLA, HLA_840, SERVO, SERVO_AC, VECTOR, VECTOR_AC
Message value:
Fault cause: %1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
"Safety Integrated" has identified that a component has been replaced.
It is no longer possible to operate the particular drive without fault.
When safety functions are active, after a component has been replaced it is necessary to carry out a partial acceptance test.
Fault value (r0949, interpret binary):
Bit 0 = 1:
It has been identified that the Control Unit has been replaced.
Bit 1 = 1:
It has been identified that the Motor Module/Hydraulic Module has been replaced.
Bit 2 = 1:
It has been identified that the Power Module has been replaced.
Bit 3 = 1:
It has been identified that the Sensor Module channel 1 has been replaced.
Bit 4 = 1:
It has been identified that the Sensor Module channel 2 has been replaced.
Bit 5 = 1:
It has been identified that the sensor channel 1 has been replaced.
Bit 6 = 1:
It has been identified that sensor channel 2 has been replaced.
Remedy:
- acknowledge component replacement (p9702 = 29).
- save all parameters (p0977 = 1 or p0971 = 1 or "copy RAM to ROM").
- acknowledge fault (e.g. binector input p2103).
Note:
In addition to the fault, diagnostics bits r9776.2 and r9776.3 are set.
See also: p9702 (SI Acknowledge component replacement), r9776 (SI diagnostics)
201640
<location>SI P1 (CU): component replacement identified and acknowledgment/save required
Drive object:
SERVO_840
Message value:
Fault cause: %1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Alarms
832
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
"Safety Integrated" has identified that a component has been replaced.
Replacing the component means that the "Global checksum" of the "Safety-relevant hardware" is changed. It is no longer
possible to operate the particular drive without fault.
When safety functions are active, after a component has been replaced it is necessary to carry out a partial acceptance test.
Fault value (r0949, interpret binary):
Bit 0 = 1:
It has been identified that the Control Unit has been replaced.
Bit 1 = 1:
It has been identified that the Motor Module/Hydraulic Module has been replaced.
Bit 2 = 1:
It has been identified that the Power Module has been replaced.
Bit 3 = 1:
It has been identified that the Sensor Module channel 1 has been replaced.
Bit 4 = 1:
It has been identified that the Sensor Module channel 2 has been replaced.
Bit 5 = 1:
It has been identified that the sensor channel 1 has been replaced.
Bit 6 = 1:
It has been identified that sensor channel 2 has been replaced.
Remedy:
- acknowledge component replacement (p9702 = 29).
- save all parameters (p0977 = 1 or p0971 = 1 or "copy RAM to ROM").
- acknowledge fault (e.g. binector input p2103).
Note:
In addition to the fault, diagnostics bits r9776.2 and r9776.3 are set.
See also: p9702 (SI Acknowledge component replacement), r9776 (SI diagnostics)
201641
<location>SI P1 (CU): component replacement identified and save required
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_AC, TM41, VECTOR,
VECTOR_AC
Message value:
Fault cause: %1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
"Safety Integrated" has identified that a component has been replaced.
No additional fault response is initiated, therefore operation of the particular drive is not restricted.
When safety functions are active, after a component has been replaced it is necessary to carry out a partial acceptance test.
Fault value (r0949, interpret binary):
Bit 0 = 1:
It has been identified that the Control Unit has been replaced.
Bit 1 = 1:
It has been identified that the Motor Module/Hydraulic Module has been replaced.
Bit 2 = 1:
It has been identified that the Power Module has been replaced.
Bit 3 = 1:
It has been identified that the Sensor Module channel 1 has been replaced.
Bit 4 = 1:
It has been identified that the Sensor Module channel 2 has been replaced.
Bit 5 = 1:
It has been identified that the sensor channel 1 has been replaced.
Bit 6 = 1:
It has been identified that sensor channel 2 has been replaced.
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
833
SINAMICS alarms
Remedy:
- save all parameters (p0977 = 1 or p0971 = 1 or "copy RAM to ROM").
- acknowledge fault (e.g. binector input p2103).
See also: r9776 (SI diagnostics)
201641
<location>SI P1 (CU): component replacement identified and save required
Drive object:
TM54F_MA
Message value:
-
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The "Safety Integrated" function integrated in the drive has identified that a Terminal Module 54F (TM54F) has been
replaced.
Remedy:
- save all parameters (p0977 = 1 or p0971 = 1 or "copy RAM to ROM").
- acknowledge fault (e.g. binector input p2103).
See also: r9776 (SI diagnostics)
201641
<location>SI P1 (CU): component replacement identified and save required
Drive object:
SERVO_840
Message value:
Fault cause: %1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
"Safety Integrated" has identified that a component has been replaced.
Replacing the component does not change the "Global checksum" of the "Safety-relevant hardware". No additional fault
response is initiated, therefore operation of the particular drive is not restricted.
When safety functions are active, after a component has been replaced it is necessary to carry out a partial acceptance test.
Fault value (r0949, interpret binary):
Bit 0 = 1:
It has been identified that the Control Unit has been replaced.
Bit 1 = 1:
It has been identified that the Motor Module/Hydraulic Module has been replaced.
Bit 2 = 1:
It has been identified that the Power Module has been replaced.
Bit 3 = 1:
It has been identified that the Sensor Module channel 1 has been replaced.
Bit 4 = 1:
It has been identified that the Sensor Module channel 2 has been replaced.
Bit 5 = 1:
It has been identified that the sensor channel 1 has been replaced.
Bit 6 = 1:
It has been identified that sensor channel 2 has been replaced.
Remedy:
- save all parameters (p0977 = 1 or p0971 = 1 or "copy RAM to ROM").
- acknowledge fault (e.g. binector input p2103).
See also: r9776 (SI diagnostics)
201649
<location>SI P1 (CU): Internal software error
Drive object:
HLA, HLA_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Alarms
834
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
An internal error in the Safety Integrated software on the Control Unit has occurred.
Note:
This fault results in a STOP A that cannot be acknowledged.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (switch-off/switch-on) for all components.
- re-commission the "Safety Integrated" function and carry out a POWER ON.
- upgrade the firmware of the Control Unit to a later version.
- contact Technical Support.
- replace the Control Unit.
Note:
CU: Control Unit
SI: Safety Integrated
201650
<location>SI P1 (CU): Acceptance test required
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_I_840, CU_LINK, CU_NX_840, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP,
CU_S120_PN, ENC, ENC_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150,
TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive-integrated "Safety Integrated" function on monitoring channel 1 requires an acceptance test.
Note:
This fault results in a STOP A that can be acknowledged.
Fault value (r0949, interpret decimal):
130: Safety parameters for monitoring channel 2 not available.
Note:
This fault value is always output when Safety Integrated is commissioned for the first time.
1000: Reference and actual checksum on monitoring channel 1 are not identical (booting).
- as a result of the changed current controller sampling time (p0115[0]), the clock cycle time for the Safety Integrated Basic
Functions (r9780) was adapted.
- at least one checksum-checked piece of data is defective.
- safety parameters set offline and loaded into the Control Unit.
2000: Reference and actual checksum on monitoring channel 1 are not identical (commissioning mode).
- reference checksum on monitoring channel 1 incorrectly entered (p9799 not equal to r9798).
- when deactivating the safety functions, p9501 or p9503 were not deleted.
2001: Reference and actual checksum on monitoring channel 2 are not identical (commissioning mode).
- reference checksum on monitoring channel 2 incorrectly entered (p9899 not equal to r9898).
- when deactivating the safety functions, p9501 or p9503 are not deleted.
2002: Enable of safety-related functions between the two monitoring channels differ (p9601 not equal to p9801).
2003: Acceptance test is required as a safety parameter has been changed.
2004: An acceptance test is required because a project with enabled safety-functions has been downloaded.
2005: The Safety logbook has identified that a functional safety checksum has changed. An acceptance test is required.
2010: Enable of safety-related brake control between the two monitoring channels differ (p9602 not equal to p9802).
2020: Error when saving the safety parameters for the monitoring channel 2.
3003: Acceptance test is required as a hardware-related safety parameter has been changed.
3005: The Safety logbook has identified that a hardware-related safety checksum has changed. An acceptance test is
required.
9999: Subsequent response of another safety-related fault that occurred when booting that requires an acceptance test.
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
835
SINAMICS alarms
Remedy:
For fault value = 130:
- carry out safety commissioning routine.
For fault value = 1000:
- check the Safety Integrated Basic Functions (r9780) and adapt the reference checksum (p9799).
- again carry out safety commissioning routine.
- replace the memory card or Control Unit.
- Using STARTER, activate the safety parameters for the drive involved (change settings, copy parameters, activate settings).
For fault value = 2000:
- check the safety parameters on monitoring channel 1 and adapt the reference checksum (p9799).
For fault value = 2001:
- check the safety parameters on monitoring channel 2 and adapt the reference checksum (p9899).
For fault value = 2002:
- check the enable the safety-related functions on both monitoring channels (p9601 = p9801).
For fault value = 2003, 2004, 2005:
- carry out an acceptance test and generate an acceptance report.
The procedure when carrying out an acceptance test as well as an example of the acceptance report are provided in the
following literature:
SINAMICS S120 Function Manual Safety Integrated
Note:
The fault with fault value 2005 can only be acknowledged when the "STO" function is deselected.
For fault value = 2010:
- check the enable the safety-related brake control on both monitoring channels (p9602 = p9802).
For fault value = 2020:
- again carry out safety commissioning routine.
- replace the memory card or Control Unit.
For fault value = 3003:
- carry out the function checks for the modified hardware and generate an acceptance report.
The procedure when carrying out an acceptance test as well as an example of the acceptance report are provided in the
following literature:
SINAMICS S120 Function Manual Safety Integrated
For fault value = 3005:
- carry out the function checks for the modified hardware and generate an acceptance report.
The fault with fault value 3005 can only be acknowledged when the "STO" function is deselected.
For fault value = 9999:
- carry out diagnostics for the other safety-related fault that is present.
Note:
CU: Control Unit
MM: Motor Module
SI: Safety Integrated
STO: Safe Torque Off
See also: p9799 (SI reference checksum SI parameters (Control Unit)), p9899 (SI reference checksum SI parameters (Motor
Module))
201650
<location>SI P1 (CU): Acceptance test required
Drive object:
HLA, HLA_840
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Alarms
836