Dodge Dakota (R1). Manual - part 789

 

  Index      Dodge     Dodge Dakota (R1) - service repair manual 2000 year

 

Search            

 

 

 

 

 

 

 

 

 

Content   ..  787  788  789  790   ..

 

 

Dodge Dakota (R1). Manual - part 789

 

 

air conditioning system on humid days. A perfor-
mance test is the best way to determine whether the
system is performing up to standard. This test also
provides valuable clues as to the possible cause of
trouble with the air conditioning system.

Before proceeding, (Refer to 24 - HEATING & AIR

CONDITIONING/PLUMBING

-

WARNING)

and

(Refer to 24 - HEATING & AIR CONDITIONING/
PLUMBING - CAUTION). The air temperature in
the test room and in the vehicle must be a minimum
of 21° C (70° F) for this test. Also the fin probe (locat-
ed in the evaporator of the HVAC unit) must be a
minimum of 65° for this test as well.

(1) Connect a tachometer and a manifold gauge

set.

(2) Set the a/c heater control to the recirculation

mode (Max-A/C) position, the temperature control
knob in the full cool position, and the blower motor
switch knob in the highest speed position.

(3) Start the engine and hold the idle at 1,000 rpm

with the compressor clutch engaged. If the compres-
sor does not engage, see the A/C Diagnosis chart in
the Diagnosis and Testing section of this group.

(4) The engine should be at operating temperature.

The doors and windows must be closed.

(5) Insert a thermometer in the driver side center

A/C (panel) outlet. Operate the a/c system until it
stabslizes.

(6) With the compressor clutch engaged, record the

discharge air temperature, the condenser out pres-
sure (high side), and the compressor inlet pressure
(low side). The compressor clutch may cycle, depend-
ing upon the ambient temperature and humidity. If
the clutch cycles, use the readings obtained before
the clutch disengaged.

(7) Compare the discharge air temperature read-

ing to the Performance Temperature and Pressure
chart. If the temperature reading is high, clamp off
both heater hoses (inlet and outlet), wait five min-
utes and record the temperature again. Compare the
second reading to the Performance Temperature and
Pressure chart. If the temperature reading is now
OK, see A/C Diagnosis chart for normal pressures. Or
see A/C Performance Test if air temperatures are too
high,

(8) Compare the discharge (high side) and suction

(low side) pressure readings to the Performance Tem-
perature and Pressure chart. If the pressures are
abnormal, see (Refer to 24 - HEATING & AIR CON-
DITIONING/PLUMBING - DIAGNOSIS AND TEST-
ING - REFRIGERANT SYSTEM LEAKS) and (Refer
to 24 - HEATING & AIR CONDITIONING/PLUMB-
ING - STANDARD PROCEDURE - REFRIGERANT
SYSTEM CHARGE).

Performance Temperature and Pressure

Ambient Air Temperature

21°C

(70°F)

27°C

(80°F)

32°C

(90°F)

38°C

(100°F)

43°C

(110°F)

Maximum Allowable Air

Temperature at Center Panel

Outlet

7°C

(45°F)

7°C

(45°F)

13°C

(55°F)

13°C

(55°F)

18°C

(64°F)

Compressor Inlet Pressure at

Service Port (Low Side)

138 to 207

kPa

(20 to 30 psi)

172 to 241

kPa

(25 to 35 psi)

207 to 276

kPa

(30 to 40 psi)

241 to 310

kPa

(35 to 45 psi)

276 to 345

kPa

(40 to 50 psi)

Condensor Out Pressure at

Service Port (High Side)

1034 to 1724

kPa

(150 to 250

psi)

1379 to 2068

kPa

(200 to 300

psi)

1724 to 2413

kPa

(250 to 350

psi)

1999 to 2689

kPa

(290 to 390

psi)

2413 to 2965

kPa

(350 to 430

psi)

(9) Compare the compressor discharge and suction

(evaporator inlet) pressure readings to the Perfor-
mance Temperature and Pressure chart. If the com-
pressor discharge pressure or suction pressure is not
normal, see the Pressure Diagnosis chart.

24 - 2

HEATING & AIR CONDITIONING

AN

HEATING & AIR CONDITIONING (Continued)

A/C Diagnosis

Condition

Possible Causes

Correction

Rapid compressor clutch
cycling (ten or more cycles
per minute).

1. Low refrigerant system
charge.

1. See Refrigerant System Leaks in the Diagnosis
and Testing section of this group. Test the
refrigerant system for leaks. Repair, evacuate and
charge the refrigerant system, if required.

2. Faulty Evaporator.

2. See Evaporator Temperature Sensor in the
Diagnosis and Testing section of this group. Test
the Evaporator Temperature Sensor.

3. Faulty Powertrain Control
Module (PCM)

3. Refer to the proper Diagnosis Procedurers
manual for testing of the PCM. Test the PCM and
replace, if required.

4. Faulty Pressure
Transducer

4. See Pressure Transducer Diagnosis and
Testing in this section.

5. Faulty Loss of Charge
Pressure Switch

5. See Loss of Charge Pressure Switch
Diagnosis and Testing in this section

Equal pressures, but the
compressor clutch does not
engage.

1. No refrigerant in the
refrigerant system.

1. (Refer to Plumbing/Diagnosis and Testing -
Refrigerant System Leaks) in this group. Test the
refrigerant system for leaks. Repair, evacuate and
charge the refrigerant system, if required.

2. Faulty fuse.

2. Check the fuses in the Power Distribution
Center and the junction block. Repair the shorted
circuit or component and replace the fuses, if
required.

3. Faulty a/c compressor
clutch coil.

3. (Refer to Controls/A/C Compressor Clutch
Coil/Diagnosis and Testing) in this group. Test the
compressor clutch coil and replace, if required.

4. Faulty a/c compressor
clutch relay.

4. (Refer to Controls/A/C Compressor Clutch
Relay/Diagnosis and Testing) in this group. Test
the compressor clutch relay and relay circuits.
Repair the circuits or replace the relay, if
required.

5. Faulty evaporator
temperature sensor.

5. (Refer to Controls/A/C Low Pressure
Switch/Diagnosis and Testing) in this group. Test
the a/c low pressure switch and tighten or
replace, if required.

6. Faulty loss of charge
pressure switch.

6. (Refer to Controls/A/C Pressure Transducer/
Diagnosis and Testing) in this group. Test the a/c
pressure transducer and replace, if required.

7. Faulty Power Train Control
Module.

7. (Refer to Appropriate Diagnostic Information)
for testing of the PCM. Test the PCM and
replace, if required.

8. Faulty pressure
transducer.

8. Refer to Diagnosis and Testing Faulty Pressure
Transducer in the section.

9. Faulty heater-A/C control.

9. Refer to Faulty heater-A/C Control in this
section.

AN

HEATING & AIR CONDITIONING

24 - 3

HEATING & AIR CONDITIONING (Continued)

A/C Diagnosis

Condition

Possible Causes

Correction

Normal pressures, but A/C
Performance Test air
temperatures at center panel
outlet are too high.

1. Excessive refrigerant oil in
system.

1. (Refer to Plumbing/Refrigerant Oil/Standard
Procedure/Refrigerant Oil Level) in this group.
Recover the refrigerant from the refrigerant
system and inspect the refrigerant oil content.
Restore the refrigerant oil to the proper level, if
required.

2. Blend door actuator
inoperative or faulty.

2. Check the Blend Door Actuator operation.
Replace as required.

3. Blend door inoperative or
sealing improperly.

3. (Refer to Distribution/Blend Door/Removal/
Installation) in this group. Inspect the blend door
for proper operation and sealing and correct, if
required.

4. Faulty evaporator.

4. Refer to evaporator section.

The low side pressure is
normal or slightly low, and
the high side pressure is too
low.

1. Low refrigerant system
charge.

1. (Refer to Plumbing/Diagnosis and Testing -
Refrigerant System Leaks) in this group. Test the
refrigerant system for leaks. Repair, evacuate and
charge the refrigerant system, if required.

2. Refrigerant flow through
the accumulator is restricted.

2. (Refer to Plumbing/Accumulator/Removal/
Installation in this group. Replace the restricted
accumulator, if required.

3. Refrigerant flow through
the a/c evaporator is
restricted.

3. (Refer to Plumbing/A/C Evaporator/Removal/
Installation in this group. Replace the restricted
a/c orator, if required.

4. Faulty a/c compressor.

4. (Refer to Plumbing/A/C Compressor/Removal/
Installation in this group. Replace the a/c
compressor, if required.

The low side pressure is
normal or slightly high, and
the high side pressure is too
high.

1. A/C condenser air flow
restricted.

1. Check the a/c condenser for damaged fins,
foreign objects obstructing air flow through the
condenser fins, and missing or improperly
installed air seals. Refer to Cooling for more
information on air seals. Clean, repair, or replace
components as required.

2. Inoperative cooling fan.

2. Refer to Cooling for more information. Test the
cooling fan and replace, if required.

3. Refrigerant system
overcharged.

3. (Refer to Plumbing/Standard Procedure -
igerant System Charge) in this group. Recover
the refrigerant from the refrigerant system.
Charge the refrigerant system to the proper level,
if required.

4. Air in the refrigerant
system.

4. (Refer to Plumbing/Diagnosis and Testing -
Refrigerant System Leaks) in this group. Test the
refrigerant system for leaks. Repair, evacuate and
charge the refrigerant system, if required.

5. Engine overheating.

5. Refer to Cooling for more information. Test the
cooling system and repair, if required.

6. Faulty orifice tube.

6. Refer to orifice tube section.

24 - 4

HEATING & AIR CONDITIONING

AN

HEATING & AIR CONDITIONING (Continued)

A/C Diagnosis

Condition

Possible Causes

Correction

The low side pressure is too
high, and the high side
pressure is too low.

1. Accessory drive belt
slipping.

1. Refer to Cooling for more information. Inspect
the accessory drive belt condition and tension.
Tighten or replace the accessory drive belt, if
required.

2. A/C orifice tube not
installed.

2. (Refer to Plumbing/A/C Orifice Tube) in this
group. Install the missing fixed orifice tube, if
required.

3. Faulty a/c compressor.

3. (Refer to Plumbing/A/C Compressor/Removal/
Installation in this group. Replace the compressor,
if required.

The low side pressure is too
low, and the high side
pressure is too high.

1. Restricted refrigerant flow
through the refrigerant lines.

1. (Refer to Plumbing/Caution - Refrigerant
Hoses/Lines/Tubes Precaution) in this group.
Inspect the refrigerant lines for kinks, tight bends
or improper routing. Correct the routing or replace
the refrigerant line, if required.

2. Restricted refrigerant flow
through the a/c orifice tube.

2. (Refer to Plumbing/A/C Orifice Tube) in this
group. Replace the restricted fixed orifice tube, if
required.

3. Restricted refrigerant flow
through the a/c condenser.

3. (Refer to Plumbing/A/C Condenser) in this
group. Replace the restricted a/c condenser, if
required.

4. Restricted Filter Drier.

4. See Filter-Drier in the Removal and Installation
section of the group. Replace the restricted
Filter-Drier, if required.

DIAGNOSIS AND TESTING - HEATER
PERFORMANCE

Before performing the following tests, refer to

Group 7 – Cooling System for the procedures to
check the engine coolant level and flow, engine cool-
ant

reserve/recovery

system

operation,

accessory

drive belt condition and tension, radiator air flow
and the fan drive operation.

MAXIMUM HEATER OUTPUT

Engine coolant is delivered to the heater core

through two heater hoses. With the engine idling at

normal operating temperature, set the temperature
control knob in the full hot position, the mode control
switch knob in the floor position, and the blower
motor switch knob in the highest speed position.
Using a test thermometer, check the temperature of
the air being discharged at the HVAC housing floor
outlets. Compare the test thermometer reading to the
Temperature Reference Chart.

Temperature Reference

Ambient Air Temperature

15.5° C

(60° F)

21.1° C

(70° F)

26.6° C

(80° F)

32.2° C

(90° F)

Minimum Air Temperature at
Floor Outlet

52.2° C

(126° F)

56.1° C

(133° F)

59.4° C

(139° F)

62.2° C

(144° F)

AN

HEATING & AIR CONDITIONING

24 - 5

HEATING & AIR CONDITIONING (Continued)

 

 

 

 

 

 

 

Content   ..  787  788  789  790   ..