SINAMICS alarms
235211
<location>TM: Temperature alarm threshold channel 0 exceeded
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM15, TM150, TM15DI_DO, TM17, TM31, TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature measured using the temperature sensing of the Terminal Module (TM) (r4105[0]) has exceeded the
threshold value to initiate this alarm (p4102[0]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[0] = 1, 4), the following applies:
- if r4101[0] > 1650 ohms, the temperature r4105[0] = 250 °C
- if r4101[0] <= 1650 ohms, the temperature r4105[0] = -50 °C
Alarm value (r2124, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy:
Allow the temperature sensor to cool down to below p4102[0] - hysteresis (5 K, for TM150, can be set using p4118[0]).
See also: p4102
235212
<location>TM: Temperature alarm threshold channel 1 exceeded
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM150, TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature measured using the temperature sensing of the Terminal Module (TM) (r4105[1]) has exceeded the
threshold value to initiate this alarm (p4102[2]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[1] = 1, 4), the following applies:
- if r4101[1] > 1650 ohms, the temperature r4105[1] = 250 °C
- if r4101[1] <= 1650 ohms, the temperature r4105[1] = -50 °C
Alarm value (r2124, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy:
Allow the temperature sensor to cool down to below p4102[4] - hysteresis (5 K, for TM150, can be set using p4118[1]).
See also: p4102
235213
<location>TM: Temperature alarm threshold channel 2 exceeded
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM150, TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature measured using the temperature sensing of the Terminal Module (TM) (r4105[2]) has exceeded the
threshold value to initiate this alarm (p4102[4]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[2] = 1, 4), the following applies:
- if r4101[2] > 1650 ohms, the temperature r4105[2] = 250 °C
- if r4101[2] <= 1650 ohms, the temperature r4105[2] = -50 °C
Alarm value (r2124, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy:
Allow the temperature sensor to cool down to below p4102[4] - hysteresis (5 K, for TM150, can be set using p4118[2]).
See also: p4102
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1389
SINAMICS alarms
235214
<location>TM: Temperature alarm threshold channel 3 exceeded
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM150, TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature measured using the temperature sensing of the Terminal Module (TM) (r4105[3]) has exceeded the
threshold value to initiate this alarm (p4102[6]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[3] = 1, 4), the following applies:
- if r4101[3] > 1650 ohms, the temperature r4105[3] = 250 °C
- if r4101[3] <= 1650 ohms, the temperature r4105[3] = -50 °C
Alarm value (r2124, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy:
Allow the temperature sensor to cool down to below p4102[6] - hysteresis (5 K, for TM150, can be set using p4118[3]).
See also: p4102
235220
<location>TM: Frequency limit reached for signal output
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM15,
TM15DI_DO, TM17, TM31, TM41, VECTOR, VECTOR_AC
Message value:
-
Reaction:
Infeed: OFF1 (NONE, OFF2)
Servo: OFF1 (NONE, OFF2, OFF3)
Vector: OFF1 (NONE, OFF2, OFF3)
Hla: OFF1 (NONE, OFF2, OFF3)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The signals output from the Terminal Module 41 (TM41) for tracks A/B have reached the limit frequency. The output signals
are no longer in synchronism with the specified setpoint.
SIMOTION (p4400 = 0) operating mode:
- if the TM41 has been configured as the technology project, this fault is also output in response to short-circuited A/B signals
in X520.
SINAMICS (p4400 = 1) operating mode:
- the fine resolution of TM41 in p0418 does not match that of the connector input that was interconnected at p4420
- the encoder position actual value r0479 interconnected at connector input p4420 has an excessively high actual speed
- the output signals correspond to a speed, which is greater than the maximum speed (r1082 of TM41).
Remedy:
SIMOTION (p4400 = 0) operating mode:
- enter a lower speed setpoint (p1155).
- reduce the encoder pulse number (p0408).
- check track A/B for short-circuits.
SINAMICS (p4400 = 1) operating mode:
- enter a lower speed setpoint (p1155).
- reduce the encoder pulse number (p0408).
Notice:
The output signal is no longer monitored after changing the message type to "Alarm" (A).
235221
<location>TM: Setpoint - actual value deviation outside the tolerance range
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM15,
TM15DI_DO, TM17, TM31, TM41, VECTOR, VECTOR_AC
Message value:
-
Alarms
1390
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Reaction:
Infeed: OFF1 (NONE, OFF2)
Servo: OFF1 (NONE, OFF2, OFF3)
Vector: OFF1 (NONE, OFF2, OFF3)
Hla: OFF1 (NONE, OFF2, OFF3)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The deviation between the setpoint and the output signals (track A/B) exceeds the tolerance of +/-3 %. The deviation
between the internal and external measured value is too high (> 1000 pulses).
Remedy:
- reduce the basic clock cycle (p0110, p0111).
- if required, replace the component (e.g. internal short-circuit).
235222
<location>TM: Encoder pulse number not permissible
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM15,
TM15DI_DO, TM17, TM31, TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The encoder pulse number entered does not match the permissible pulse number from a hardware perspective.
Alarm value (r2124, interpret decimal):
1: Encoder pulse number is too high.
2: Encoder pulse number is too low.
4: Encoder pulse number is less than the zero mark offset (p4426).
Remedy:
- enter the encoder pulse number in the permissible range (p0408).
- if necessary, replace TM41 SAC with TM41 DAC.
Note:
TM41 SAC: Article No. = 6SL3055-0AA00-3PA0
TM41 DAC: Article No. = 6SL3055-0AA00-3PA1
The following applies for TM41 SAC:
- minimum/maximum value for p0408: 1000/8192
The following applies for TM41 DAC:
- minimum/maximum value for p0408: 1000/16384
See also: p0408
235223
<location>TM: Zero mark offset not permissible
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM15,
TM15DI_DO, TM17, TM31, TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The entered zero mark offset is not permissible.
Alarm value (r2124, interpret decimal):
1: Zero mark offset is too high.
See also: p4426 (TM41 encoder emulation pulses for zero mark)
Remedy:
Enter the zero mark offset in the permissible range (p4426).
235224
<location>TM: Zero mark synchronization interrupted
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM41,
VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1391
SINAMICS alarms
Cause:
The zero mark synchronization with the encoder to be emulated was interrupted.
Alarm value (r2124, interpret decimal):
0: The encoder is not in the ready state (e.g. encoder parked)
1: An absolute encoder was connected.
2: The encoder r0479[0...2] interconnected via connector input: p4420 is already communicating with another TM41
(precisely one TM41 can be interconnected with a specific r0479[0...2]).
3: The BICO interconnection to Terminal Module 41 (TM41) was removed (CI: p4420 = 0 signal).
4: The encoder interconnected via connector input: p4420 has carried out an EDS changeover or has been re-parameterized
(this operation is not supported, set p4420 to 0 and interconnect again).
5: The maximum number of revolutions of the encoder was exceeded.
6: Encoder in an invalid state.
7: Encoder in an invalid state.
8: Encoder in an invalid state (the encoder is not parameterized or the interconnected signal source is not in the cyclic state).
Remedy:
Not necessary.
- if the encoder changes into the ready state, then a synchronization operation that was previously interrupted is carried out
again.
- if the synchronization was interrupted due to the maximum permissible synchronization duration, then a new
synchronization is not carried out.
- the alarm is only output, if, for an absolute encoder, the zero mark synchronization is set to the zero position (p4401.0 =
1 and p4401.1=0).
235225
<location>TM: Zero mark synchronization held - encoder not in the ready state
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM41,
VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The zero mark synchronization with the encoder to be emulated was held.
The encoder is not in the "ready" state.
Remedy:
Bring the encoder into the "ready" state.
235226
<location>TM: Tracks A/B are deactivated
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM41,
VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
There is no frequency setpoint for the Terminal Module 41 (TM41). The output of tracks A/B has been held (frozen).
Possible causes:
- connector input p4420 is not interconnected.
- the leading encoder is not in the "ready" state (parking encoder or encoder data set not parameterized).
- TM41 has a fault.
- the TM41 is in the commissioning mode (p0010 > 0).
- the TM41 component is not connected to DRIVE-CLiQ.
Remedy:
- appropriately interconnect connector input p4420.
- bring the leading encoder into the "ready" state.
- remove any TM41 faults.
235227
<location>EDS changeover/encoder data set change not supported
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM41,
VECTOR, VECTOR_AC
Message value:
-
Alarms
1392
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Reaction:
NONE
Acknowledge:
NONE
Cause:
Terminal Module 41 (TM41) does not support the following application cases:
- the encoder interconnected via connector input p4420 has carried out an EDS changeover.
- the encoder interconnected with the TM41 was re-parameterized so that the position actual value of the encoder must be
newly interpreted.
For example, this is the case when changing the direction of rotation of the motor (p0410, p1821) or when changing the
fine resolution (p0418). This may result in a sudden change in the position actual value of the encoder (position setpoint
of the TM41), which must not be output at the TM41.
See also: p4420 (TM41 encoder emulation position setpoint)
Remedy:
Set connector input p4420 = 0 and re-wire.
235228
<location>TM: Sampling time p4099[3] invalid
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM41,
VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The sampling time set in p4099[3] for incremental encoder emulation in Terminal Module 41 (TM41) does not correspond
to the valid value. To resolve the problem, correct the setting of p4099[3]. The system automatically performs a warm
restart/sub-boot.
Alarm value (r2124, interpret decimal):
1:
A sampling time p4099[3] < 125 µs was set.
2:
An integer multiple of the DRIVE-CLiQ clock cycle was not entered in p4099[3].
3:
- in the SINAMICS mode (p4400 = 1), the sampling time in p4099[3] is not an integer multiple of the current controller
sampling time (p0115[0]) of the drive object, which supplies the position setpoint (CI: p4420) for the incremental encoder
simulation.
- the encoder interconnected via connector input p4420 (e.g. an SSI encoder) is sampled in a slower clock cycle.
Remedy:
- if necessary, cancel the BICO interconnection via connector input p4420.
- check the rules specified under cause for setting the sampling time in p4099[3].
- if necessary, set the BICO interconnection via connector input p4420 again.
Note:
Every time the BICO interconnection is reset via connector input p4420, the sampling time is checked in p4099[3] and,
where necessary, this message is output.
235229
<location>TM: Time slice deactivated
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM41,
VECTOR, VECTOR_AC
Message value:
%1
Reaction:
Infeed: OFF1 (NONE, OFF2)
Servo: NONE
Vector: NONE
Hla: NONE
Acknowledge:
IMMEDIATELY
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1393
SINAMICS alarms
Cause:
The required value of a cycle time in p4099[0...2] is invalid.
The corresponding time slice was not activated.
Alarm value (r2124, interpret decimal):
0: Digital input/outputs (p4099[0])
1: Analog inputs (p4099[1])
3: Encoder emulation (p4099[3]).
4: Encoder emulation speed setpoint (p4099[3]).
5: Encoder emulation speed setpoint (p4099[3]).
6: Internal sequence control of the TM41 (internal error)
Remedy:
Change the sampling time according to the alarm value.
Note:
The sampling time p4099[0] may not be zero.
235230
<location>TM: Hardware fault
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM150, TM15DI_DO, TM31, TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
Infeed: OFF1 (NONE, OFF2)
Servo: NONE
Vector: NONE
Hla: NONE
Acknowledge:
POWER ON
Cause:
The Terminal Module (TM) used has signaled internal errors.
Signals from this module may not be evaluated because they are very likely to be incorrect.
Remedy:
If required, replace the Terminal Module.
235231
<location>TM: Master control by PLC missing
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM41,
VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The "master control by PLC" signal was missing in operation.
- interconnection of the binector input for "master control by PLC" is incorrect (p0854).
- the higher-level control has withdrawn the "master control by PLC" signal.
- data transfer via the fieldbus (master/drive) was interrupted.
Note:
This alarm is only decisive in the "SIMOTION" operating mode (p4400 = 0).
In the "SINAMICS" operating mode (p4400 = 1), the setpoints at p4420 are evaluated independent of binector input p0854.
Remedy:
- check the interconnection of the binector input for "master control by PLC" (p0854).
- check the "master control by PLC" signal and, if required, switch in.
- check the data transfer via the fieldbus (master/drive).
- check the setting of parameter p2037.
235232
<location>TM41: Zero mark no longer synchronous POWER ON required
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM41,
VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Alarms
1394
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
SINAMICS (p4400 = 1) operating mode:
When parameterizing a Terminal Module 41 (TM41) or when operating a TM41 Module, an operating state was reached
which required a POWER ON.
These include:
- changing the encoder pulse number (p0408).
- changing the fine resolution (p0418).
- withdrawing the DRIVE-CLiQ cable without first deactivating TM41 via p0105.
If this alarm was output, then the zero mark of the TM41 can no longer be output in synchronism to that of the encoder
interconnected at p4420.
SIMOTION (p4400 = 0) operating mode:
A previously set zero mark position (p4426) no longer matches encoder position (r0479) due to the change in the pulse
number (p0408).
Remedy:
The incremental position at output X520 of TM41 can still be evaluated independent of the zero mark.
A POWER ON must be carried out if the TM41 zero mark is evaluated.
235233
<location>DRIVE-CLiQ component function not supported
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM150, TM31, TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A function requested by the Control Unit is not supported by a DRIVE-CLiQ component.
Fault value (r0949, interpret decimal):
1: Terminal Module 31 does not support the function "Timer for temperature evaluation" (X522.7/8, p4103 > 0.000).
4: The improved actual value resolution is not supported (p4401.4).
5: The improved setpoint resolution is not supported (p4401.5).
6: The residual value handling in the setpoint channel cannot be deactivated (p4401.6).
7: Output frequencies greater than 750 kHz cannot be activated (p4401.7).
Remedy:
For fault value = 1:
- Deactivate timer for temperature evaluation (X522.7/8) (p4103 = 0.000).
- use Terminal Module 31 and the relevant firmware version to enable the "Timer for temperature evaluation" function
(Article No. 6SL3055-0AA00-3AA1, firmware version 2.6 and higher).
See also: p4103, p4401 (TM41 encoder emulation mode)
235400
<location>TM: Temperature fault/alarm threshold channel 4 exceeded
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
Infeed: OFF2 (NONE, OFF1)
Servo: OFF2 (NONE, OFF1, OFF3)
Vector: OFF2 (NONE, OFF1, OFF3)
Hla: OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY (POWER ON)
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1395
SINAMICS alarms
Cause:
For the temperature evaluation via the Terminal Module 150 (TM150), at least one of the following conditions to initiate this
fault is fulfilled:
- alarm threshold has been exceeded longer than that set in the timer (p4102[8], p4103[4]).
or
- fault threshold exceeded (p4102[9]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[4] = 1, 4), the following applies:
- if r4101[4] > 1650 ohms, the temperature r4105[4] = 250 °C
- if r4101[4] <= 1650 ohms, the temperature r4105[4] = -50 °C
The temperature actual value is displayed via connector output r4105[4] and can be interconnected.
Notice:
This fault only causes the drive to shut down if there is at least one BICO interconnection between the drive and the Terminal
Module.
Fault value (r0949, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy:
- allow the temperature sensor to cool down to below p4102[9] - hysteresis (p4118[4]).
- if required, set the fault response to NONE (p2100, p2101).
See also: p4102
235401
<location>TM: Temperature fault/alarm threshold channel 5 exceeded
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
Infeed: OFF2 (NONE, OFF1)
Servo: OFF2 (NONE, OFF1, OFF3)
Vector: OFF2 (NONE, OFF1, OFF3)
Hla: OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
For the temperature evaluation via the Terminal Module 150 (TM150), at least one of the following conditions to initiate this
fault is fulfilled:
- alarm threshold has been exceeded longer than that set in the timer (p4102[10], p4103[5]).
or
- fault threshold exceeded (p4102[11]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[5] = 1, 4), the following applies:
- if r4101[5] > 1650 ohms, the temperature r4105[5] = 250 °C
- if r4101[5] <= 1650 ohms, the temperature r4105[5] = -50 °C
The temperature actual value is displayed via connector output r4105[5] and can be interconnected.
Notice:
This fault only causes the drive to shut down if there is at least one BICO interconnection between the drive and the Terminal
Module.
Fault value (r0949, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy:
- allow the temperature sensor to cool down to below p4102[11] - hysteresis (p4118[5]).
- if required, set the fault response to NONE (p2100, p2101).
See also: p4102
235402
<location>TM: Temperature fault/alarm threshold channel 6 exceeded
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Alarms
1396
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Reaction:
Infeed: OFF2 (NONE, OFF1)
Servo: OFF2 (NONE, OFF1, OFF3)
Vector: OFF2 (NONE, OFF1, OFF3)
Hla: OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
For the temperature evaluation via the Terminal Module 150 (TM150), at least one of the following conditions to initiate this
fault is fulfilled:
- alarm threshold has been exceeded longer than that set in the timer (p4102[12], p4103[6]).
or
- fault threshold exceeded (p4102[13]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[6] = 1, 4), the following applies:
- if r4101[6] > 1650 ohms, the temperature r4105[6] = 250 °C
- if r4101[6] <= 1650 ohms, the temperature r4105[6] = -50 °C
The temperature actual value is displayed via connector output r4105[6] and can be interconnected.
Notice:
This fault only causes the drive to shut down if there is at least one BICO interconnection between the drive and the Terminal
Module.
Fault value (r0949, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy:
- allow the temperature sensor to cool down to below p4102[13] - hysteresis (p4118[6]).
- if required, set the fault response to NONE (p2100, p2101).
See also: p4102
235403
<location>TM: Temperature fault/alarm threshold channel 7 exceeded
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
Infeed: OFF2 (NONE, OFF1)
Servo: OFF2 (NONE, OFF1, OFF3)
Vector: OFF2 (NONE, OFF1, OFF3)
Hla: OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
For the temperature evaluation via the Terminal Module 150 (TM150), at least one of the following conditions to initiate this
fault is fulfilled:
- alarm threshold has been exceeded longer than that set in the timer (p4102[14], p4103[7]).
or
- fault threshold exceeded (p4102[15]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[7] = 1, 4), the following applies:
- if r4101[7] > 1650 ohms, the temperature r4105[7] = 250 °C
- if r4101[7] <= 1650 ohms, the temperature r4105[7] = -50 °C
The temperature actual value is displayed via connector output r4105[7] and can be interconnected.
Notice:
This fault only causes the drive to shut down if there is at least one BICO interconnection between the drive and the Terminal
Module.
Fault value (r0949, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy:
- allow the temperature sensor to cool down to below p4102[15] - hysteresis (p4118[7]).
- if required, set the fault response to NONE (p2100, p2101).
See also: p4102
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1397
SINAMICS alarms
235404
<location>TM: Temperature fault/alarm threshold channel 8 exceeded
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
Infeed: OFF2 (NONE, OFF1)
Servo: OFF2 (NONE, OFF1, OFF3)
Vector: OFF2 (NONE, OFF1, OFF3)
Hla: OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
For the temperature evaluation via the Terminal Module 150 (TM150), at least one of the following conditions to initiate this
fault is fulfilled:
- alarm threshold has been exceeded longer than that set in the timer (p4102[16], p4103[8]).
or
- fault threshold exceeded (p4102[17]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[8] = 1, 4), the following applies:
- if r4101[8] > 1650 ohms, the temperature r4105[8] = 250 °C
- if r4101[8] <= 1650 ohms, the temperature r4105[8] = -50 °C
The temperature actual value is displayed via connector output r4105[8] and can be interconnected.
Notice:
This fault only causes the drive to shut down if there is at least one BICO interconnection between the drive and the Terminal
Module.
Fault value (r0949, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy:
- allow the temperature sensor to cool down to below p4102[17] - hysteresis (p4118[8]).
- if required, set the fault response to NONE (p2100, p2101).
See also: p4102
235405
<location>TM: Temperature fault/alarm threshold channel 9 exceeded
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
Infeed: OFF2 (NONE, OFF1)
Servo: OFF2 (NONE, OFF1, OFF3)
Vector: OFF2 (NONE, OFF1, OFF3)
Hla: OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
For the temperature evaluation via the Terminal Module 150 (TM150), at least one of the following conditions to initiate this
fault is fulfilled:
- alarm threshold has been exceeded longer than that set in the timer (p4102[18], p4103[9]).
or
- fault threshold exceeded (p4102[19]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[9] = 1, 4), the following applies:
- if r4101[9] > 1650 ohms, the temperature r4105[9] = 250 °C
- if r4101[9] <= 1650 ohms, the temperature r4105[9] = -50 °C
The temperature actual value is displayed via connector output r4105[9] and can be interconnected.
Notice:
This fault only causes the drive to shut down if there is at least one BICO interconnection between the drive and the Terminal
Module.
Fault value (r0949, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Alarms
1398
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Remedy:
- allow the temperature sensor to cool down to below p4102[19] - hysteresis (p4118[9]).
- if required, set the fault response to NONE (p2100, p2101).
See also: p4102
235406
<location>TM: Temperature fault/alarm threshold channel 10 exceeded
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
Infeed: OFF2 (NONE, OFF1)
Servo: OFF2 (NONE, OFF1, OFF3)
Vector: OFF2 (NONE, OFF1, OFF3)
Hla: OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
For the temperature evaluation via the Terminal Module 150 (TM150), at least one of the following conditions to initiate this
fault is fulfilled:
- alarm threshold has been exceeded longer than that set in the timer (p4102[20], p4103[10]).
or
- fault threshold exceeded (p4102[21]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[10] = 1, 4), the following applies:
- if r4101[10] > 1650 ohms, the temperature r4105[10] = 250 °C
- if r4101[10] <= 1650 ohms, the temperature r4105[10] = -50 °C
The temperature actual value is displayed via connector output r4105[10] and can be interconnected.
Notice:
This fault only causes the drive to shut down if there is at least one BICO interconnection between the drive and the Terminal
Module.
Fault value (r0949, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy:
- allow the temperature sensor to cool down to below p4102[21] - hysteresis (p4118[10]).
- if required, set the fault response to NONE (p2100, p2101).
See also: p4102
235407
<location>TM: Temperature fault/alarm threshold channel 11 exceeded
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
Infeed: OFF2 (NONE, OFF1)
Servo: OFF2 (NONE, OFF1, OFF3)
Vector: OFF2 (NONE, OFF1, OFF3)
Hla: OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY (POWER ON)
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1399
SINAMICS alarms
Cause:
For the temperature evaluation via the Terminal Module 150 (TM150), at least one of the following conditions to initiate this
fault is fulfilled:
- alarm threshold has been exceeded longer than that set in the timer (p4102[22], p4103[11]).
or
- fault threshold exceeded (p4102[23]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[11] = 1, 4), the following applies:
- if r4101[11] > 1650 ohms, the temperature r4105[11] = 250 °C
- if r4101[11] <= 1650 ohms, the temperature r4105[11] = -50 °C
The temperature actual value is displayed via connector output r4105[11] and can be interconnected.
Notice:
This fault only causes the drive to shut down if there is at least one BICO interconnection between the drive and the Terminal
Module.
Fault value (r0949, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy:
- allow the temperature sensor to cool down to below p4102[23] - hysteresis (p4118[11]).
- if required, set the fault response to NONE (p2100, p2101).
See also: p4102
235410
<location>TM: Temperature alarm threshold channel 4 exceeded
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature (r4105[4]) measured using the temperature sensing of the Terminal Module 150 (TM150) has exceeded
the threshold value to initiate this alarm (p4102[8]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[4] = 1, 4), the following applies:
- if r4101[4] > 1650 ohms, the temperature r4105[4] = 250 °C
- if r4101[4] <= 1650 ohms, the temperature r4105[4] = -50 °C
Alarm value (r2124, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy:
Allow the temperature sensor to cool down to below p4102[8] - hysteresis (p4118[4]).
See also: p4102
235411
<location>TM: Temperature alarm threshold channel 5 exceeded
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature (r4105[5]) measured using the temperature sensing of the Terminal Module 150 (TM150) has exceeded
the threshold value to initiate this alarm (p4102[10]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[5] = 1, 4), the following applies:
- if r4101[5] > 1650 ohms, the temperature r4105[5] = 250 °C
- if r4101[5] <= 1650 ohms, the temperature r4105[5] = -50 °C
Alarm value (r2124, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy:
Allow the temperature sensor to cool down to below p4102[10] - hysteresis (p4118[5]).
See also: p4102
Alarms
1400
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
235412
<location>TM: Temperature alarm threshold channel 6 exceeded
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature (r4105[6]) measured using the temperature sensing of the Terminal Module 150 (TM150) has exceeded
the threshold value to initiate this alarm (p4102[12]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[6] = 1, 4), the following applies:
- if r4101[6] > 1650 ohms, the temperature r4105[6] = 250 °C
- if r4101[6] <= 1650 ohms, the temperature r4105[6] = -50 °C
Alarm value (r2124, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy:
Allow the temperature sensor to cool down to below p4102[12] - hysteresis (p4118[6]).
See also: p4102
235413
<location>TM: Temperature alarm threshold channel 7 exceeded
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature (r4105[7]) measured using the temperature sensing of the Terminal Module 150 (TM150) has exceeded
the threshold value to initiate this alarm (p4102[14]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[7] = 1, 4), the following applies:
- if r4101[7] > 1650 ohms, the temperature r4105[7] = 250 °C
- if r4101[7] <= 1650 ohms, the temperature r4105[7] = -50 °C
Alarm value (r2124, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy:
Allow the temperature sensor to cool down to below p4102[14] - hysteresis (p4118[7]).
See also: p4102
235414
<location>TM: Temperature alarm threshold channel 8 exceeded
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature (r4105[8]) measured using the temperature sensing of the Terminal Module 150 (TM150) has exceeded
the threshold value to initiate this alarm (p4102[16]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[8] = 1, 4), the following applies:
- if r4101[8] > 1650 ohms, the temperature r4105[8] = 250 °C
- if r4101[8] <= 1650 ohms, the temperature r4105[8] = -50 °C
Alarm value (r2124, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy:
Allow the temperature sensor to cool down to below p4102[16] - hysteresis (p4118[8]).
See also: p4102
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1401
SINAMICS alarms
235415
<location>TM: Temperature alarm threshold channel 9 exceeded
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature (r4105[9]) measured using the temperature sensing of the Terminal Module 150 (TM150) has exceeded
the threshold value to initiate this alarm (p4102[18]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[9] = 1, 4), the following applies:
- if r4101[9] > 1650 ohms, the temperature r4105[9] = 250 °C
- if r4101[9] <= 1650 ohms, the temperature r4105[9] = -50 °C
Alarm value (r2124, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy:
Allow the temperature sensor to cool down to below p4102[18] - hysteresis (p4118[9]).
See also: p4102
235416
<location>TM: Temperature alarm threshold channel 10 exceeded
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature (r4105[10]) measured using the temperature sensing of the Terminal Module 150 (TM150) has exceeded
the threshold value to initiate this alarm (p4102[20]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[10] = 1, 4), the following applies:
- if r4101[10] > 1650 ohms, the temperature r4105[10] = 250 °C
- if r4101[10] <= 1650 ohms, the temperature r4105[10] = -50 °C
Alarm value (r2124, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy:
Allow the temperature sensor to cool down to below p4102[20] - hysteresis (p4118[10]).
See also: p4102
235417
<location>TM: Temperature alarm threshold channel 11 exceeded
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature (r4105[11]) measured using the temperature sensing of the Terminal Module 150 (TM150) has exceeded
the threshold value to initiate this alarm (p4102[22]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[11] = 1, 4), the following applies:
- if r4101[11] > 1650 ohms, the temperature r4105[11] = 250 °C
- if r4101[11] <= 1650 ohms, the temperature r4105[11] = -50 °C
Alarm value (r2124, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy:
Allow the temperature sensor to cool down to below p4102[22] - hysteresis (p4118[11]).
See also: p4102
Alarms
1402
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
235800
<location>TM: Group signal
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
-
Reaction:
Infeed: OFF2 (NONE, OFF1)
Servo: OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2)
Vector: OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2)
Hla: OFF2 (NONE, OFF1, OFF3, STOP2)
Acknowledge:
NONE
Cause:
The Terminal Module has detected at least one fault.
Remedy:
Evaluates other actual messages.
235801
<location>TM DRIVE-CLiQ: Sign-of-life missing
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communication error has occurred between the Control Unit and the Terminal Module involved.
Fault cause:
10 (= 0A hex):
The sign-of-life bit in the receive telegram is not set.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- check the DRIVE-CLiQ connection.
- replace the component involved.
235802
<location>TM: Time slice overflow
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
A time slice overflow has occurred on the Terminal Module.
Remedy:
Replace the Terminal Module.
235803
<location>TM: Memory test
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM15,
TM15DI_DO, TM17, TM41, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
An error has occurred during the memory test on the Terminal Module.
Remedy:
- check whether the permissible ambient temperature for the Terminal Module is being maintained.
- replace the Terminal Module.
235804
<location>TM: CRC
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1403
SINAMICS alarms
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
A checksum error has occurred when reading-out the program memory on the Terminal Module.
Fault value (r0949, interpret hexadecimal):
Difference between the checksum at POWER ON and the actual checksum.
Remedy:
- check whether the permissible ambient temperature for the component is maintained.
- replace the Terminal Module.
235805
<location>TM: EEPROM checksum error
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
Internal parameter data is corrupted.
Alarm value (r2124, interpret hexadecimal):
01: EEPROM access error.
02: Too many blocks in the EEPROM.
Remedy:
- check whether the permissible ambient temperature for the component is maintained.
- replace the Terminal Module 31 (TM31).
235807
<location>TM: Sequence control time monitoring
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM15,
TM15DI_DO, TM17, TM41, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
Error, timeout, sequence control on the Terminal Module.
Remedy:
Replace the Terminal Module.
235820
<location>TM DRIVE-CLiQ: Telegram error
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Alarms
1404
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
A DRIVE-CLiQ communication error has occurred from the Control Unit to the Terminal Module involved.
Fault cause:
1 (= 01 hex):
Checksum error (CRC error).
2 (= 02 hex):
Telegram is shorter than specified in the length byte or in the receive list.
3 (= 03 hex):
Telegram is longer than specified in the length byte or in the receive list.
4 (= 04 hex):
The length of the receive telegram does not match the receive list.
5 (= 05 hex):
The type of the receive telegram does not match the receive list.
6 (= 06 hex):
The address of the component in the telegram and in the receive list do not match.
7 (= 07 hex):
A SYNC telegram is expected - but the received telegram is not a SYNC telegram.
8 (= 08 hex):
No SYNC telegram is expected - but the received telegram is one.
9 (= 09 hex):
The error bit in the receive telegram is set.
16 (= 10 hex):
The receive telegram is too early.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- check the electrical cabinet design and cable routing for EMC compliance
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
235835
<location>TM DRIVE-CLiQ: Cyclic data transfer error
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communication error has occurred from the Control Unit to the Terminal Module involved. The nodes do not
send and receive in synchronism.
Fault cause:
33 (= 21 hex):
The cyclic telegram has not been received.
34 (= 22 hex):
Timeout in the telegram receive list.
64 (= 40 hex):
Timeout in the telegram send list.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- carry out a POWER ON.
- replace the component involved.
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1405
SINAMICS alarms
235836
<location>TM DRIVE-CLiQ: Send error for DRIVE-CLiQ data
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communication error has occurred between the Control Unit and the Terminal Module involved. Data were not
able to be sent.
Fault cause:
65 (= 41 hex):
Telegram type does not match send list.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
Carry out a POWER ON.
235837
<location>PTM DRIVE-CLiQ: Component fault
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
Fault detected on the DRIVE-CLiQ component concerned. Faulty hardware cannot be excluded.
Fault cause:
32 (= 20 hex):
Error in the telegram header.
35 (= 23 hex):
Receive error: The telegram buffer memory contains an error.
66 (= 42 hex):
Send error: The telegram buffer memory contains an error.
67 (= 43 hex):
Send error: The telegram buffer memory contains an error.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
- check the electrical cabinet design and cable routing for EMC compliance
- if required, use another DRIVE-CLiQ socket (p9904).
- replace the component involved.
235845
<location>TM DRIVE-CLiQ: Cyclic data transfer error
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Alarms
1406
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
A DRIVE-CLiQ communication error has occurred between the Control Unit and the Terminal Module (TM) involved.
Fault cause:
11 (= 0B hex):
Synchronization error during alternating cyclic data transfer.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
Carry out a POWER ON.
235850
<location>TM: Internal software error
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
Infeed: OFF1 (NONE, OFF2)
Servo: OFF1 (NONE, OFF2, OFF3)
Vector: OFF1 (NONE, OFF2, OFF3)
Hla: OFF1 (NONE, OFF2, OFF3)
Acknowledge:
POWER ON
Cause:
An internal software error in the Terminal Module (TM) has occurred.
Fault value (r0949, interpret decimal):
1: Background time slice is blocked.
2: Checksum over the code memory is not OK.
Remedy:
- replace the Terminal Module (TM).
- if required, upgrade the firmware in the Terminal Module.
- contact Technical Support.
235851
<location>TM DRIVE-CLiQ (CU): Sign-of-life missing
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC,
TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communication error has occurred from the Terminal Module involved (TM) to the Control Unit.
The DRIVE-CLiQ component did not set the sign-of-life to the Control Unit.
Fault cause:
10 (= 0A hex):
The sign-of-life bit in the receive telegram is not set.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
Upgrade the firmware of the component involved.
235860
<location>TM DRIVE-CLiQ (CU): Telegram error
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC,
TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1407
SINAMICS alarms
Cause:
A DRIVE-CLiQ communication error has occurred from the Terminal Module involved (TM) to the Control Unit.
Fault cause:
1 (= 01 hex):
Checksum error (CRC error).
2 (= 02 hex):
Telegram is shorter than specified in the length byte or in the receive list.
3 (= 03 hex):
Telegram is longer than specified in the length byte or in the receive list.
4 (= 04 hex):
The length of the receive telegram does not match the receive list.
5 (= 05 hex):
The type of the receive telegram does not match the receive list.
6 (= 06 hex):
The address of the power unit in the telegram and in the receive list do not match.
9 (= 09 hex):
The DRIVE-CLiQ communication from the DRIVE-CLiQ component involved to the Control Unit signals that the supply voltage
has failed.
16 (= 10 hex):
The receive telegram is too early.
17 (= 11 hex):
CRC error and the receive telegram is too early.
18 (= 12 hex):
The telegram is shorter than that specified in the length byte or in the receive list and the receive telegram is too early.
19 (= 13 hex):
The telegram is longer than that specified in the length byte or in the receive list and the receive telegram is too early.
20 (= 14 hex):
The length of the receive telegram does not match the receive list and the receive telegram is too early.
21 (= 15 hex):
The type of the receive telegram does not match the receive list and the receive telegram is too early.
22 (= 16 hex):
The address of the power unit in the telegram and in the receive list does not match and the receive telegram is too early.
25 (= 19 hex):
The error bit in the receive telegram is set and the receive telegram is too early.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- check the electrical cabinet design and cable routing for EMC compliance
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
235875
<location>TM: power supply voltage failed
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC,
TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Alarms
1408
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
The DRIVE-CLiQ communication from the DRIVE-CLiQ component involved to the Control Unit signals that the supply voltage
has failed.
Fault cause:
9 (= 09 hex):
The power supply voltage for the components has failed.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- check the power supply voltage wiring for the DRIVE-CLiQ component (interrupted cable, contacts, ...).
- check the dimensioning of the power supply for the DRIVE-CLiQ component.
235885
<location>TM DRIVE-CLiQ (CU): Cyclic data transfer error
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC,
TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communication error has occurred from the Terminal Module involved (TM) to the Control Unit.
The nodes do not send and receive in synchronism.
Fault cause:
26 (= 1A hex):
Sign-of-life bit in the receive telegram not set and the receive telegram is too early.
33 (= 21 hex):
The cyclic telegram has not been received.
34 (= 22 hex):
Timeout in the telegram receive list.
64 (= 40 hex):
Timeout in the telegram send list.
98 (= 62 hex):
Error at the transition to cyclic operation.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- check the power supply voltage of the component involved.
- carry out a POWER ON.
- replace the component involved.
235886
<location>TM DRIVE-CLiQ (CU): Error when sending DRIVE-CLiQ data
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC,
TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1409
SINAMICS alarms
Cause:
A DRIVE-CLiQ communication error has occurred from the Terminal Module involved (TM) to the Control Unit.
Data were not able to be sent.
Fault cause:
65 (= 41 hex):
Telegram type does not match send list.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
Carry out a POWER ON.
235887
<location>TM DRIVE-CLiQ (CU): Component fault
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC,
TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
Fault detected on the DRIVE-CLiQ component (Terminal Module) involved. Faulty hardware cannot be excluded.
Fault cause:
32 (= 20 hex):
Error in the telegram header.
35 (= 23 hex):
Receive error: The telegram buffer memory contains an error.
66 (= 42 hex):
Send error: The telegram buffer memory contains an error.
67 (= 43 hex):
Send error: The telegram buffer memory contains an error.
96 (= 60 hex):
Response received too late during runtime measurement.
97 (= 61 hex):
Time taken to exchange characteristic data too long.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
- check the electrical cabinet design and cable routing for EMC compliance
- if required, use another DRIVE-CLiQ socket (p9904).
- replace the component involved.
235895
<location>TM DRIVE-CLiQ (CU): Alternating cyclic data transfer error
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC,
TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communication error has occurred from the Terminal Module involved (TM) to the Control Unit.
Fault cause:
11 (= 0B hex):
Synchronization error during alternating cyclic data transfer.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Alarms
1410
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Remedy:
Carry out a POWER ON.
235896
<location>TM DRIVE-CLiQ (CU): Inconsistent component properties
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC,
TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
Component number: %1
Reaction:
Infeed: OFF2 (NONE, OFF1)
Servo: OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2)
Vector: OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2)
Hla: OFF2 (NONE, OFF1, OFF3, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
The properties of the DRIVE-CLiQ component (Terminal Module), specified by the fault value, have changed in an
incompatible fashion with respect to the properties when booted. One cause can be, e.g. that a DRIVE-CLiQ cable or DRIVE-
CLiQ component has been replaced.
Fault value (r0949, interpret decimal):
Component number.
Remedy:
- carry out a POWER ON.
- when a component is replaced, the same component type and if possible the same firmware version should be used.
- when a cable is replaced, only cables whose length is the same as or as close as possible to the length of the original cables
should be used (ensure compliance with the maximum cable length).
235899
<location>TM: Unknown fault
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
New message: %1
Reaction:
Infeed: NONE (OFF1, OFF2)
Servo: NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2)
Vector: NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2)
Hla: NONE (OFF1, OFF2, OFF3, STOP2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
A fault has occurred on the Terminal Module that cannot be interpreted by the Control Unit firmware.
This can occur if the firmware on this component is more recent than the firmware on the Control Unit.
Fault value (r0949, interpret decimal):
Fault number.
Note:
If required, the significance of this new fault can be read about in a more recent description of the Control Unit.
Remedy:
- replace the firmware on the Terminal Module by an older firmware version (r0158).
- upgrade the firmware on the Control Unit (r0018).
235903
<location>TM: I2C bus error occurred
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM15, TM150, TM15DI_DO, TM17, TM31, TM41, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
An error has occurred while accessing the internal I2C bus of the Terminal Module.
Remedy:
Replace the Terminal Module.
235904
<location>TM: EEPROM
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM15, TM150, TM15DI_DO, TM17, TM31, TM41, VECTOR, VECTOR_AC
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1411
SINAMICS alarms
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
An error has occurred accessing the non-volatile memory on the Terminal Module.
Remedy:
Replace the Terminal Module.
235905
<location>TM: Parameter access
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM15, TM150, TM15DI_DO, TM17, TM31, TM41, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The Control Unit attempted to write an illegal parameter value to the Terminal Module.
Remedy:
- check whether the firmware version of the Terminal Module (r0158) matches the firmware version of Control Unit (r0018).
- if required, replace the Terminal Module.
Note:
The firmware versions that match each other are in the readme.txt file on the memory card.
235906
<location>TM: 24 V power supply missing
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM15, TM150, TM15DI_DO, TM17, TM31, TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The 24 V power supply for the digital outputs is missing.
Alarm value (r2124, interpret hexadecimal):
01: TM17 24 V power supply for DI/DO 0 ... 7 missing.
02: TM17 24 V power supply for DI/DO 8 ... 15 missing.
04: TM15 24 V power supply for DI/DO 0 ... 7 (X520) missing.
08: TM15 24 V power supply for DI/DO 8 ... 15 (X521) missing.
10: TM15 24 V power supply for DI/DO 16 ... 23 (X522) missing.
20: TM41 24 V power supply for DI/DO 0 ... 3 missing.
Remedy:
Check the terminals for the power supply voltage (L1+, L2+, L3+, M or +24 V_1 for TM41).
235907
<location>TM: Hardware initialization error
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM15, TM150, TM15DI_DO, TM17, TM31, TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The Terminal Module was not successfully initialized.
Alarm value (r2124, interpret hexadecimal):
01: TM17 or TM41 - incorrect configuration request.
02: TM17 or TM41 - programming not successful.
04: TM17 or TM41 - invalid time stamp
Remedy:
Carry out a POWER ON.
235910
<location>TM: Module overtemperature
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM15, TM150, TM15DI_DO, TM17, TM31, TM41, VECTOR, VECTOR_AC
Alarms
1412
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature in the module has exceeded the highest permissible limit.
Remedy:
- reduce the ambient temperature.
- replace the Terminal Module.
235911
<location>TM: Clock synchronous operation sign-of-life missing
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM15, TM150, TM15DI_DO, TM17, TM31, TM41, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The maximum permissible number of errors in the master sign-of-life (clock synchronous operation) has been exceeded in
cyclic operation.
When the alarm is output, the module outputs are reset up to the next synchronization.
Remedy:
- check the physical bus configuration (terminating resistor, shielding, etc.).
- check the interconnection of the master sign-of-life (r4201 via p0915).
- check whether the master correctly sends the sign-of-life (e.g. set up a trace with r4201.12 ... r4201.15 and trigger signal
r4301.9).
- check the bus and master for utilization level (e.g. bus cycle time Tdp was set too short).
235920
<location>TM: Error temperature sensor channel 0
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM15, TM150, TM15DI_DO, TM17, TM31, TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
When evaluating the temperature sensor, an error occurred.
Alarm value (r2124, interpret decimal):
1: Wire breakage or sensor not connected.
KTY84: R > 1630 Ohm (TM150: R > 2170 Ohm), PT100: R > 194 Ohm, PT1000: R > 1720 Ohm (TM150: R > 1944 Ohm)
2: Measured resistance too low.
PTC thermistor: R < 20 Ohm, KTY84: R < 50 Ohm (TM150: R < 180 Ohm), PT100: R < 60 Ohm, PT1000: R < 603 Ohm
Remedy:
- make sure that the sensor is connected correctly.
- replace the sensor.
235921
<location>TM: Error temperature sensor channel 1
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM150, TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
When evaluating the temperature sensor, an error occurred.
Alarm value (r2124, interpret decimal):
1: Wire breakage or sensor not connected.
KTY84: R > 1630 Ohm (TM150: R > 2170 Ohm), PT100: R > 194 Ohm, PT1000: R > 1720 Ohm (TM150: R > 1944 Ohm)
2: Measured resistance too low.
PTC thermistor: R < 20 Ohm, KTY84: R < 50 Ohm (TM150: R < 180 Ohm), PT100: R < 60 Ohm, PT1000: R < 603 Ohm
Remedy:
- make sure that the sensor is connected correctly.
- replace the sensor.
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1413
SINAMICS alarms
235922
<location>TM: Error temperature sensor channel 2
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM150, TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
When evaluating the temperature sensor, an error occurred.
Alarm value (r2124, interpret decimal):
1: Wire breakage or sensor not connected.
KTY84: R > 1630 Ohm (TM150: R > 2170 Ohm), PT100: R > 194 Ohm, PT1000: R > 1720 Ohm (TM150: R > 1944 Ohm)
2: Measured resistance too low.
PTC thermistor: R < 20 Ohm, KTY84: R < 50 Ohm (TM150: R < 180 Ohm), PT100: R < 60 Ohm, PT1000: R < 603 Ohm
Remedy:
- make sure that the sensor is connected correctly.
- replace the sensor.
235923
<location>TM: Error temperature sensor channel 3
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM150, TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
When evaluating the temperature sensor, an error occurred.
Alarm value (r2124, interpret decimal):
1: Wire breakage or sensor not connected.
KTY84: R > 1630 Ohm (TM150: R > 2170 Ohm), PT100: R > 194 Ohm, PT1000: R > 1720 Ohm (TM150: R > 1944 Ohm)
2: Measured resistance too low.
PTC thermistor: R < 20 Ohm, KTY84: R < 50 Ohm (TM150: R < 180 Ohm), PT100: R < 60 Ohm, PT1000: R < 603 Ohm
Remedy:
- make sure that the sensor is connected correctly.
- replace the sensor.
235924
<location>TM: Error temperature sensor channel 4
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
When evaluating the temperature sensor, an error occurred.
Alarm value (r2124, interpret decimal):
1: Wire breakage or sensor not connected.
KTY84: R > 2170 Ohm, PT100: R > 194 Ohm, PT1000: R > 1944 Ohm
2: Measured resistance too low.
PTC thermistor: R < 20 Ohm, KTY84: R < 180 Ohm, PT100: R < 60 Ohm, PT1000: R < 603 Ohm
Remedy:
- make sure that the sensor is connected correctly.
- replace the sensor.
235925
<location>TM: Error temperature sensor channel 5
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Alarms
1414
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Acknowledge:
NONE
Cause:
When evaluating the temperature sensor, an error occurred.
Alarm value (r2124, interpret decimal):
1: Wire breakage or sensor not connected.
KTY84: R > 2170 Ohm, PT100: R > 194 Ohm, PT1000: R > 1944 Ohm
2: Measured resistance too low.
PTC thermistor: R < 20 Ohm, KTY84: R < 180 Ohm, PT100: R < 60 Ohm, PT1000: R < 603 Ohm
Remedy:
- make sure that the sensor is connected correctly.
- replace the sensor.
235926
<location>TM: Error temperature sensor channel 6
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
When evaluating the temperature sensor, an error occurred.
Alarm value (r2124, interpret decimal):
1: Wire breakage or sensor not connected.
KTY84: R > 2170 Ohm, PT100: R > 194 Ohm, PT1000: R > 1944 Ohm
2: Measured resistance too low.
PTC thermistor: R < 20 Ohm, KTY84: R < 180 Ohm, PT100: R < 60 Ohm, PT1000: R < 603 Ohm
Remedy:
- make sure that the sensor is connected correctly.
- replace the sensor.
235927
<location>TM: Error temperature sensor channel 7
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
When evaluating the temperature sensor, an error occurred.
Alarm value (r2124, interpret decimal):
1: Wire breakage or sensor not connected.
KTY84: R > 2170 Ohm, PT100: R > 194 Ohm, PT1000: R > 1944 Ohm
2: Measured resistance too low.
PTC thermistor: R < 20 Ohm, KTY84: R < 180 Ohm, PT100: R < 60 Ohm, PT1000: R < 603 Ohm
Remedy:
- make sure that the sensor is connected correctly.
- replace the sensor.
235928
<location>TM: Error temperature sensor channel 8
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1415
SINAMICS alarms
Cause:
When evaluating the temperature sensor, an error occurred.
Alarm value (r2124, interpret decimal):
1: Wire breakage or sensor not connected.
KTY84: R > 2170 Ohm, PT100: R > 194 Ohm, PT1000: R > 1944 Ohm
2: Measured resistance too low.
PTC thermistor: R < 20 Ohm, KTY84: R < 180 Ohm, PT100: R < 60 Ohm, PT1000: R < 603 Ohm
Remedy:
- make sure that the sensor is connected correctly.
- replace the sensor.
235929
<location>TM: Error temperature sensor channel 9
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
When evaluating the temperature sensor, an error occurred.
Alarm value (r2124, interpret decimal):
1: Wire breakage or sensor not connected.
KTY84: R > 2170 Ohm, PT100: R > 194 Ohm, PT1000: R > 1944 Ohm
2: Measured resistance too low.
PTC thermistor: R < 20 Ohm, KTY84: R < 180 Ohm, PT100: R < 60 Ohm, PT1000: R < 603 Ohm
Remedy:
- make sure that the sensor is connected correctly.
- replace the sensor.
235930
<location>TM: Error temperature sensor channel 10
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
When evaluating the temperature sensor, an error occurred.
Alarm value (r2124, interpret decimal):
1: Wire breakage or sensor not connected.
KTY84: R > 2170 Ohm, PT100: R > 194 Ohm, PT1000: R > 1944 Ohm
2: Measured resistance too low.
PTC thermistor: R < 20 Ohm, KTY84: R < 180 Ohm, PT100: R < 60 Ohm, PT1000: R < 603 Ohm
Remedy:
- make sure that the sensor is connected correctly.
- replace the sensor.
235931
<location>TM: Error temperature sensor channel 11
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM150,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
When evaluating the temperature sensor, an error occurred.
Alarm value (r2124, interpret decimal):
1: Wire breakage or sensor not connected.
KTY84: R > 2170 Ohm, PT100: R > 194 Ohm, PT1000: R > 1944 Ohm
2: Measured resistance too low.
PTC thermistor: R < 20 Ohm, KTY84: R < 180 Ohm, PT100: R < 60 Ohm, PT1000: R < 603 Ohm
Alarms
1416
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Remedy:
- make sure that the sensor is connected correctly.
- replace the sensor.
235950
<location>TM: Internal software error
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM41,
TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2 (NONE)
Acknowledge:
POWER ON
Cause:
An internal software error has occurred.
Fault value (r0949, interpret decimal):
Information about the fault source.
Only for internal Siemens troubleshooting.
Remedy:
- if necessary, upgrade the firmware in the Terminal Module to a later version.
- contact Technical Support.
235999
<location>TM: Unknown alarm
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120,
TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
New message: %1
Reaction:
NONE
Acknowledge:
NONE
Cause:
An alarm has occurred on the Terminal Module that cannot be interpreted by the Control Unit firmware.
This can occur if the firmware on this component is more recent than the firmware on the Control Unit.
Alarm value (r2124, interpret decimal):
Alarm number.
Note:
If required, the significance of this new alarm can be read about in a more recent description of the Control Unit.
Remedy:
- replace the firmware on the Terminal Module by an older firmware version (r0158).
- upgrade the firmware on the Control Unit (r0018).
236207
<location>Hub: Overtemperature component
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE (OFF1, OFF2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The temperature on the DRIVE-CLiQ Hub Module has exceeded the fault threshold.
Fault value (r0949, interpret decimal):
Actual temperature in 0.1 °C resolution.
Remedy:
- check ambient temperature at component installation location.
- replace the component involved.
236211
<location>Hub: Overtemperature alarm component
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1417
SINAMICS alarms
Cause:
The temperature on the DRIVE-CLiQ Hub Module has exceeded the alarm threshold.
Alarm value (r2124, interpret decimal):
Actual temperature in 0.1 °C resolution.
Remedy:
- check ambient temperature at component installation location.
- replace the component involved.
236214
<location>Hub: overvoltage fault 24 V supply
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE (OFF1, OFF2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The 24 V power supply on the DRIVE-CLiQ Hub Module has exceeded the fault threshold.
Fault value (r0949, interpret decimal):
Actual operating voltage in 0.1 °C resolution
Remedy:
- check the supply voltage of the component involved.
- replace the component involved.
236216
<location>Hub: undervoltage fault 24 V supply
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE (OFF1, OFF2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The 24 V power supply on the DRIVE-CLiQ Hub Module has undershot the fault threshold.
Fault value (r0949, interpret decimal):
Actual operating voltage in 0.1 °C resolution
Remedy:
- check the supply voltage of the component involved.
- replace the component involved.
236217
<location>Hub: undervoltage alarm 24 V supply
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The 24 V power supply on the DRIVE-CLiQ Hub Module has undershot the alarm threshold.
Alarm value (r2124, interpret decimal):
Actual operating voltage in 0.1 °C resolution
Remedy:
- check the supply voltage of the component involved.
- replace the component involved.
236800
<location>Hub: Group signal
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC,
TM41, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The DRIVE-CLiQ Hub Module has detected at least one fault.
Remedy:
Evaluates other actual messages.
Alarms
1418
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
236801
<location>Hub DRIVE-CLiQ: Sign-of-life missing
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC,
TM41, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
NONE
Cause:
A DRIVE-CLiQ communications error has occurred from the Control Unit to the DRIVE-CLiQ Hub Module involved.
Fault cause:
10 (= 0A hex):
The sign-of-life bit in the receive telegram is not set.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- check the DRIVE-CLiQ connection.
- replace the component involved.
236802
<location>Hub: Time slice overflow
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
A time slice overflow has occurred on the DRIVE-CLiQ Hub Module.
Fault value (r0949, interpret decimal):
xx: Time slice number xx
Remedy:
- reduce the current controller frequency.
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade firmware to later version.
- contact Technical Support.
236804
<location>Hub: Checksum error
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
A checksum error has occurred when reading out the program memory on the DRIVE-CLiQ Hub Module.
Fault value (r0949, interpret hexadecimal):
Difference between the checksum at POWER ON and the actual checksum.
Remedy:
- check whether the permissible ambient temperature for the component is maintained.
- replace the DRIVE-CLiQ Hub Module.
236805
<location>Hub: EEPROM checksum incorrect
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC,
TM41, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1419
SINAMICS alarms
Cause:
The internal parameter data on the DRIVE-CLiQ Hub Module is incorrect.
Alarm value (r2124, interpret hexadecimal):
01: EEPROM access error.
02: Too many blocks in the EEPROM.
Remedy:
- check whether the permissible ambient temperature for the component is maintained.
- replace the DRIVE-CLiQ Hub Module.
236820
<location>Hub DRIVE-CLiQ: Telegram error
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC,
TM41, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred from the Control Unit to the DRIVE-CLiQ Hub Module involved.
Fault cause:
1 (= 01 hex):
Checksum error (CRC error).
2 (= 02 hex):
Telegram is shorter than specified in the length byte or in the receive list.
3 (= 03 hex):
Telegram is longer than specified in the length byte or in the receive list.
4 (= 04 hex):
The length of the receive telegram does not match the receive list.
5 (= 05 hex):
The type of the receive telegram does not match the receive list.
6 (= 06 hex):
The address of the component in the telegram and in the receive list do not match.
7 (= 07 hex):
A SYNC telegram is expected - but the received telegram is not a SYNC telegram.
8 (= 08 hex):
No SYNC telegram is expected - but the received telegram is one.
9 (= 09 hex):
The error bit in the receive telegram is set.
16 (= 10 hex):
The receive telegram is too early.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- check the electrical cabinet design and cable routing for EMC compliance
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
236835
<location>Hub DRIVE-CLiQ: Cyclic data transfer error
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC,
TM41, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Alarms
1420
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
A DRIVE-CLiQ communications error has occurred from the Control Unit to the DRIVE-CLiQ Hub Module involved. The nodes
do not send and receive in synchronism.
Fault cause:
33 (= 21 hex):
The cyclic telegram has not been received.
34 (= 22 hex):
Timeout in the telegram receive list.
64 (= 40 hex):
Timeout in the telegram send list.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- carry out a POWER ON.
- replace the component involved.
236836
<location>Hub DRIVE-CLiQ: Send error for DRIVE-CLiQ data
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC,
TM41, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred from the Control Unit to the DRIVE-CLiQ Hub Module involved. Data were
not able to be sent.
Fault cause:
65 (= 41 hex):
Telegram type does not match send list.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
Carry out a POWER ON.
236837
<location>Hub DRIVE-CLiQ: Component fault
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC,
TM41, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
Fault detected on the DRIVE-CLiQ component concerned. Faulty hardware cannot be excluded.
Fault cause:
32 (= 20 hex):
Error in the telegram header.
35 (= 23 hex):
Receive error: The telegram buffer memory contains an error.
66 (= 42 hex):
Send error: The telegram buffer memory contains an error.
67 (= 43 hex):
Send error: The telegram buffer memory contains an error.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1421
SINAMICS alarms
Remedy:
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
- check the electrical cabinet design and cable routing for EMC compliance
- if required, use another DRIVE-CLiQ socket (p9904).
- replace the component involved.
236845
<location>Hub DRIVE-CLiQ: Cyclic data transfer error
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC,
TM41, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred from the Control Unit to the DRIVE-CLiQ Hub Module involved.
Fault cause:
11 (= 0B hex):
Synchronization error during alternating cyclic data transfer.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
Carry out a POWER ON.
236851
<location>Hub DRIVE-CLiQ (CU): Sign-of-life missing
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840,
SERVO_AC, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
DRIVE-CLiQ communication error from DRIVE-CLiQ Hub Module in question to Control Unit.
The DRIVE-CLiQ component did not set the sign-of-life to the Control Unit.
Fault cause:
10 (= 0A hex):
The sign-of-life bit in the receive telegram is not set.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
Upgrade the firmware of the component involved.
236860
<location>Hub DRIVE-CLiQ (CU): Telegram error
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840,
SERVO_AC, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Alarms
1422
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
DRIVE-CLiQ communication error from DRIVE-CLiQ Hub Module in question to Control Unit.
Fault cause:
1 (= 01 hex):
Checksum error (CRC error).
2 (= 02 hex):
Telegram is shorter than specified in the length byte or in the receive list.
3 (= 03 hex):
Telegram is longer than specified in the length byte or in the receive list.
4 (= 04 hex):
The length of the receive telegram does not match the receive list.
5 (= 05 hex):
The type of the receive telegram does not match the receive list.
6 (= 06 hex):
The address of the power unit in the telegram and in the receive list do not match.
9 (= 09 hex):
The DRIVE-CLiQ communication from the DRIVE-CLiQ component involved to the Control Unit signals that the supply voltage
has failed.
16 (= 10 hex):
The receive telegram is too early.
17 (= 11 hex):
CRC error and the receive telegram is too early.
18 (= 12 hex):
The telegram is shorter than that specified in the length byte or in the receive list and the receive telegram is too early.
19 (= 13 hex):
The telegram is longer than that specified in the length byte or in the receive list and the receive telegram is too early.
20 (= 14 hex):
The length of the receive telegram does not match the receive list and the receive telegram is too early.
21 (= 15 hex):
The type of the receive telegram does not match the receive list and the receive telegram is too early.
22 (= 16 hex):
The address of the power unit in the telegram and in the receive list does not match and the receive telegram is too early.
25 (= 19 hex):
The error bit in the receive telegram is set and the receive telegram is too early.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- check the electrical cabinet design and cable routing for EMC compliance
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
236875
<location>HUB: power supply voltage failed
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840,
SERVO_AC, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1423
SINAMICS alarms
Cause:
The DRIVE-CLiQ communication from the DRIVE-CLiQ component involved to the Control Unit signals that the supply voltage
has failed.
Fault cause:
9 (= 09 hex):
The power supply voltage for the components has failed.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- check the power supply voltage wiring for the DRIVE-CLiQ component (interrupted cable, contacts, ...).
- check the dimensioning of the power supply for the DRIVE-CLiQ component.
236885
<location>Hub DRIVE-CLiQ (CU): Cyclic data transfer error
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840,
SERVO_AC, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
DRIVE-CLiQ communication error from DRIVE-CLiQ Hub Module in question to the Control Unit.
The nodes do not send and receive in synchronism.
Fault cause:
26 (= 1A hex):
Sign-of-life bit in the receive telegram not set and the receive telegram is too early.
33 (= 21 hex):
The cyclic telegram has not been received.
34 (= 22 hex):
Timeout in the telegram receive list.
64 (= 40 hex):
Timeout in the telegram send list.
98 (= 62 hex):
Error at the transition to cyclic operation.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- check the supply voltage of the component involved.
- carry out a POWER ON.
- replace the component involved.
236886
<location>Hub DRIVE-CLiQ (CU): Error when sending DRIVE-CLiQ data
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840,
SERVO_AC, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Alarms
1424
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
DRIVE-CLiQ communication error from DRIVE-CLiQ Hub Module in question to Control Unit.
Data were not able to be sent.
Fault cause:
65 (= 41 hex):
Telegram type does not match send list.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
Carry out a POWER ON.
236887
<location>Hub DRIVE-CLiQ (CU): Component fault
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840,
SERVO_AC, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
Fault detected on the DRIVE-CLiQ component (DRIVE-CLiQ Hub Module) involved. Faulty hardware cannot be excluded.
Fault cause:
32 (= 20 hex):
Error in the telegram header.
35 (= 23 hex):
Receive error: The telegram buffer memory contains an error.
66 (= 42 hex):
Send error: The telegram buffer memory contains an error.
67 (= 43 hex):
Send error: The telegram buffer memory contains an error.
96 (= 60 hex):
Response received too late during runtime measurement.
97 (= 61 hex):
Time taken to exchange characteristic data too long.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
- check the electrical cabinet design and cable routing for EMC compliance
- if required, use another DRIVE-CLiQ socket (p9904).
- replace the component involved.
236895
<location>Hub DRIVE-CLiQ (CU): Alternating cyclic data transfer error
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840,
SERVO_AC, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, VECTOR, VECTOR_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
DRIVE-CLiQ communication error from DRIVE-CLiQ Hub Module in question to Control Unit.
Fault cause:
11 (= 0B hex):
Synchronization error during alternating cyclic data transfer.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1425
SINAMICS alarms
Remedy:
Carry out a POWER ON.
236896
<location>Hub DRIVE-CLiQ (CU): Inconsistent component properties
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840,
SERVO_AC, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, VECTOR, VECTOR_AC
Message value:
Component number: %1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The properties of the DRIVE-CLiQ component (DRIVE-CLiQ Hub Module), specified by the fault value, have changed in an
incompatible fashion with respect to the properties when booted. One cause can be, e.g. that a DRIVE-CLiQ cable or DRIVE-
CLiQ component has been replaced.
Fault value (r0949, interpret decimal):
Component number.
Remedy:
- carry out a POWER ON.
- when a component is replaced, the same component type and if possible the same firmware version should be used.
- when a cable is replaced, only cables whose length is the same as or as close as possible to the length of the original cables
should be used (ensure compliance with the maximum cable length).
236899
<location>Hub: Unknown fault
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC,
TM41, VECTOR, VECTOR_AC
Message value:
New message: %1
Reaction:
Infeed: NONE (OFF1, OFF2)
Servo: NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2)
Vector: NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2)
Hla: NONE (OFF1, OFF2, OFF3, STOP2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
A fault occurred on the DRIVE-CLiQ Hub Module that cannot be interpreted by the Control Unit firmware.
This can occur if the firmware on this component is more recent than the firmware on the Control Unit.
Fault value (r0949, interpret decimal):
Fault number.
Note:
If required, the significance of this new fault can be read about in a more recent description of the Control Unit.
Remedy:
- replace the firmware on the DRIVE-CLiQ Hub Module with older firmware (r0158).
- upgrade the firmware on the Control Unit (r0018).
236950
<location>Hub: Internal software error
Drive object:
SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2 (NONE)
Acknowledge:
POWER ON
Cause:
An internal software error has occurred.
Fault value (r0949, interpret decimal):
Information about the fault source.
Only for internal Siemens troubleshooting.
Remedy:
- if required, upgrade the firmware in the DRIVE-CLiQ Hub Module to a more recent version.
- contact Technical Support.
236999
<location>Hub: Unknown alarm
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC,
TM41, VECTOR, VECTOR_AC
Alarms
1426
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Message value:
New message: %1
Reaction:
NONE
Acknowledge:
NONE
Cause:
An alarm occurred on the DRIVE-CLiQ Hub Module that cannot be interpreted by the Control Unit firmware.
This can occur if the firmware on this component is more recent than the firmware on the Control Unit.
Alarm value (r2124, interpret decimal):
Alarm number.
Note:
If required, the significance of this new alarm can be read about in a more recent description of the Control Unit.
Remedy:
- replace the firmware on the DRIVE-CLiQ Hub Module with older firmware (r0158).
- upgrade the firmware on the Control Unit (r0018).
237001
<location>HF Damping Module: overcurrent
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
Fault cause: %1 bin
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The power unit has detected an overcurrent condition.
- HF Choke Module or HF Damping Module defective.
- Resonance frequency of the output filter was excited.
Fault value (r0949, interpret bitwise binary):
Bit 0: Phase U.
Bit 1: Phase V.
Bit 2: Phase W.
Remedy:
- check HF Choke Module and HF Damping Module and if required, replace.
- reduce the motor power in the proximity of the fault-generating frequency.
Note:
HF Choke Module (reactor module)
HF Damping Module
237002
<location>HF Damping Module: Damping voltage too high
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The damping voltage has reached an inadmissibly high value.
- a motor harmonic with a high amplitude has coincided with the resonance frequency of the output filter.
- the current controller excessively excites the resonance of the output filter.
Fault value (r0949, interpret decimal):
Damping voltage in the case of a fault [mV].
See also: r5171 (HF damping voltage actual value)
Remedy:
- reduce the motor power in the proximity of the fault-generating frequency.
- check the current controller and if required, adapt.
- if required, use another motor.
Note:
HF Damping Module
237003
<location>HF Damping Module: Damping voltage not established
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1427
SINAMICS alarms
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A damping voltage was not able to be established.
Fault value (r0949, interpret decimal):
Damping voltage in the case of a fault [mV].
Remedy:
Check the HF Damping Module wiring.
See also: r5171 (HF damping voltage actual value)
237004
<location>HF Damping Module: Heat sink overtemperature
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The temperature of the heat sink in the HF Damping Module has exceeded the permissible limit value.
- insufficient cooling, fan failure.
- overload.
- ambient temperature too high.
Fault value (r0949, interpret decimal):
Temperature [0.01 °C].
Remedy:
- check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
Notice:
This fault can only be acknowledged after the alarm threshold for alarm A05000 has been undershot.
Note:
HF Damping Module
237005
<location>HF Damping Module: I2t overload
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The filter capacitor of the HF Damping Module was overloaded (r5173 = 100 %).
- the filter resonance frequency was excessively excited.
- the HF Choke Module is defective.
Fault value (r0949, interpret decimal):
I2t [100 % = 16384].
Remedy:
- reduce the motor power in the proximity of the fault-generating frequency.
- the system should not stay in a steady-state condition in the vicinity of the fault-generating frequency.
- check the HF Choke Module and if required replace.
Note:
HF Choke Module (reactor module)
HF Damping Module
See also: r5173 (HF Damping Module I2t overload)
237012
<location>HF Damping Module: Heat sink temperature sensor wire breakage
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Alarms
1428
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
The connection to one of the heat sink temperature sensors in the HF Damping Module is interrupted.
Fault value (r0949, interpret binary):
Bit 0: HF Damping Module
Bit 1: HF Choke Module
Remedy:
Contact the manufacturer.
Note:
HF Choke Module (reactor module)
HF Damping Module
237013
<location>HF Damping Module: Heat sink temperature sensor short-circuit
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
The heat sink temperature sensor in the HF Damping Module is short-circuited.
Fault value (r0949, interpret binary):
Bit 0: HF Damping Module
Bit 1: HF Choke Module
Remedy:
Contact the manufacturer.
Note:
HF Choke Module (reactor module)
HF Damping Module
237024
<location>HF Damping Module: Overtemperature thermal model
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
-
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The temperature difference between the heat sink and chip has exceeded the permissible limit value.
- the permissible load duty cycle was not maintained.
- insufficient cooling, fan failure.
- overload.
- ambient temperature too high.
- pulse frequency too high.
See also: r0037
Remedy:
- adapt the load duty cycle.
- check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
- check the motor load.
- reduce the pulse frequency if this is higher than the rated pulse frequency.
237025
<location>HF Damping Module: Chip overtemperature
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1429
SINAMICS alarms
Cause:
The chip temperature has exceeded the permissible limit value.
- the permissible load duty cycle was not maintained.
- insufficient cooling, fan failure.
- overload.
- ambient temperature too high.
- pulse frequency too high.
Fault value (r0949, interpret decimal):
Temperature difference between the heat sink and chip [0.01 °C].
Remedy:
- adapt the load duty cycle.
- check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
- check the motor load.
- reduce the pulse frequency if this is higher than the rated pulse frequency.
Note:
HF Damping Module
See also: r0037
237034
<location>HF Damping Module: Internal overtemperature
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The alarm threshold for internal overtemperature has been reached.
If the temperature inside the unit continues to increase, fault F37036 may be triggered.
- ambient temperature might be too high.
- insufficient cooling, fan failure.
Fault value (r0949, interpret binary):
Bit 0 = 1: Control electronics range.
Bit 1 = 1: Power electronics range.
Remedy:
- check the ambient temperature.
- check the fan for the inside of the unit.
Note:
HF Damping Module
237036
<location>HF Damping Module: Internal overtemperature
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The temperature inside the HF Damping Module has exceeded the permissible temperature limit.
- insufficient cooling, fan failure.
- overload.
- ambient temperature too high.
Fault value (r0949, interpret binary):
Bit 0 = 1: Control electronics range.
Bit 1 = 1: Power electronics range.
Alarms
1430
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Remedy:
- check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
Notice:
This fault can only be acknowledged once the permissible temperature limit minus 5 K has been undershot.
Note:
HF Damping Module
237040
<location>HF Damping Module: 24 V undervoltage
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
Failure of the 24 V power supply for the HF Damping Module.
- the undervoltage threshold was undershot for longer than 3 ms.
Fault value (r0949, interpret decimal):
24 V voltage [0.1 V].
Remedy:
- check the 24 V DC voltage supply of the HF Damping Module.
- carry out a POWER ON (switch-off/switch-on) for the component.
Note:
HF Damping Module
237041
<location>HF Damping Module: 24 V undervoltage alarm
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
Fault in the 24 V power supply for the HF Damping Module.
- the 16 V threshold was undershot..
Alarm value (r2124, interpret decimal):
24 V voltage [0.1 V].
Remedy:
- check the 24 V DC voltage supply of the HF Damping Module.
- carry out a POWER ON (switch-off/switch-on) for the component.
Note:
HF Damping Module
237043
<location>HF Damping Module: 24 V overvoltage
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
-
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
Overvoltage of the 24 V power supply for the HF Damping Module.
- the 31.5 V threshold was exceeded for more than 3 ms.
Remedy:
Check the 24 V DC voltage supply of the HF Damping Module.
Note:
HF Damping Module
237044
<location>HF Damping Module: 24 V overvoltage alarm
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
-
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1431
SINAMICS alarms
Reaction:
NONE
Acknowledge:
NONE
Cause:
Fault in the 24 V power supply for the HF Damping Module.
- the 32.0 V threshold was exceeded.
Remedy:
Check the 24 V DC voltage supply of the HF Damping Module.
Note:
HF Damping Module
237045
<location>HF Damping Module: Supply undervoltage
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
Power supply fault in the HF Damping Module.
- the voltage monitor signals an undervoltage fault on the module.
Fault value (r0949, interpret decimal):
24 V voltage [0.1 V].
Remedy:
- check the 24 V DC voltage supply of the HF Damping Module.
- carry out a POWER ON (switch-off/switch-on) for the component.
- replace the module if necessary.
Note:
HF Damping Module
237049
<location>HF Damping Module: Internal fan defective
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The internal fan of the HF Damping Module has failed.
Remedy:
Check the internal fan of the HF Damping Module and replace if necessary.
237050
<location>HF Damping Module: 24 V overvoltage fault
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
-
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
The voltage monitor signals an overvoltage fault on the module.
Remedy:
- check the 24 V power supply.
- replace the module if necessary.
237052
<location>HF Damping Module: EEPROM data error
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
POWER ON
Alarms
1432
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
EEPROM data error of the HF Damping Module.
Fault value (r0949, interpret hexadecimal):
0: The EEPROM data read in from the HF Damping Module is inconsistent.
1: EEPROM data is not compatible to the firmware of the HF Damping Module.
Additional values:
Only for internal Siemens troubleshooting.
Remedy:
For fault value = 0:
Replace the HF Damping Module or update the EEPROM data.
For fault value = 1:
If necessary, upgrade the firmware to a later version.
Note:
HF Damping Module
237056
<location>HF Damping Module: Heat sink overtemperature
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature of the HF Damping Module heat sink has exceeded the permissible limit value.
- insufficient cooling, fan failure.
- overload.
- ambient temperature too high.
Alarm value (r2124, interpret decimal):
Temperature [0.01 °C].
Remedy:
- check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
Notice:
This fault can only be acknowledged after the alarm threshold for alarm A05000 has been undershot.
Note:
HF Damping Module
237310
<location>HF Choke Module: Overtemperature
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature of the HF Choke Module heat sink has exceeded the permissible limit value.
- insufficient cooling, fan failure.
- overload.
- ambient temperature too high.
Alarm value (r2124, interpret decimal):
Temperature [0.01 °C].
Remedy:
- check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
Notice:
This fault can only be acknowledged after the alarm threshold for alarm A05000 has been undershot.
Note:
HF Choke Module (reactor module)
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1433
SINAMICS alarms
237311
<location>HF Choke Module: Heat sink overtemperature
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The temperature of the HF Choke Module heat sink has exceeded the permissible limit value.
- insufficient cooling, fan failure.
- overload.
- ambient temperature too high.
Fault value (r0949, interpret decimal):
Temperature [0.01 °C].
Remedy:
- check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
- check the motor load.
Notice:
This fault can only be acknowledged after this alarm threshold for alarm A05000 has been undershot.
Note:
HF Choke Module (reactor module)
237312
<location>HF Choke Module: Overtemperature or fan failure
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The HF Choke Module signals an overtemperature or fan failure.
Fault F37313 is output if the alarm is present for longer than 30 s.
Remedy:
- the cable between the HF Choke Module and the HF Damping Module has been withdrawn or is defective (X21).
- check the fan of the HF Choke Module and replace if necessary.
- check whether the ambient temperature is in the permissible range.
Note:
HF Choke Module (reactor module)
HF Damping Module
237313
<location>HF Choke Module: Overtemperature or fan failure
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
-
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
Alarm A37312 to display overtemperature or fan failure in the HF Choke Module was signaled for longer than 30 s.
Remedy:
- the cable between the HF Choke Module and the HF Damping Module has been withdrawn or is defective (X21).
- check the fan of the HF Choke Module and replace if necessary.
- check whether the ambient temperature is in the permissible range.
Note:
HF Choke Module (reactor module)
HF Damping Module
237502
<location>HF Damping Module: Damping voltage too high
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Alarms
1434
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Reaction:
NONE
Acknowledge:
NONE
Cause:
The damping voltage has exceeded the alarm threshold.
- a motor harmonic with a high amplitude has coincided with the resonance frequency of the output filter.
- the current controller excessively excites the resonance of the output filter.
If the damping voltage exceeds an inadmissibly high value, F37002 is output.
Alarm value (r2124, interpret decimal):
Damping voltage in the case of a fault [mV].
See also: r5171 (HF damping voltage actual value)
Remedy:
- reduce the motor power in the proximity of the fault-generating frequency.
- check the current controller and if required, adapt.
- if required, use another motor.
Note:
HF Damping Module
237800
<location>HF Damping Module: Group signal
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The HF Damping Module has detected at least one fault.
Remedy:
Evaluates other actual messages.
237801
<location>HF Damping Module: Sign-of-life missing
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
NONE
Cause:
There is a DRIVE-CLiQ communication error between the Control Unit and the HF Damping Module.
Fault cause:
10 (= 0A hex):
The sign-of-life bit in the receive telegram is not set.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- check the DRIVE-CLiQ connection.
- replace the component involved.
Note:
HF Damping Module
237802
<location>HF Damping Module: time slice overflow
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
-
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A time slice overflow has occurred.
Remedy:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade firmware to later version.
- contact Technical Support.
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1435
SINAMICS alarms
237804
<location>HF Damping Module: CRC
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
OFF2 (OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
A checksum error (CRC error) has occurred for the HF Damping Module.
Remedy:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade firmware to later version.
- contact Technical Support.
Note:
HF Damping Module
237805
<location>HF Damping Module: EEPROM checksum incorrect
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
Internal parameter data is corrupted.
Fault value (r0949, interpret hexadecimal):
01: EEPROM access error.
02: Too many blocks in the EEPROM.
Remedy:
Replace the module.
Note:
HF Damping Module
237820
<location>HF Damping Module: Telegram error
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Alarms
1436
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
A DRIVE-CLiQ communication error has occurred from the Control Unit to the damping module.
Fault cause:
1 (= 01 hex):
Checksum error (CRC error).
2 (= 02 hex):
Telegram is shorter than specified in the length byte or in the receive list.
3 (= 03 hex):
Telegram is longer than specified in the length byte or in the receive list.
4 (= 04 hex):
The length of the receive telegram does not match the receive list.
5 (= 05 hex):
The type of the receive telegram does not match the receive list.
6 (= 06 hex):
The address of the component in the telegram and in the receive list do not match.
7 (= 07 hex):
A SYNC telegram is expected - but the received telegram is not a SYNC telegram.
8 (= 08 hex):
No SYNC telegram is expected - but the received telegram is one.
9 (= 09 hex):
The error bit in the receive telegram is set.
16 (= 10 hex):
The receive telegram is too early.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- check the electrical cabinet design and cable routing for EMC compliance
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
Note:
HF Damping Module
237835
<location>HF Damping Module: Cyclic data transmission error
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
There is a DRIVE-CLiQ communication error between the Control Unit and the HF Damping Module. The nodes do not send
and receive in synchronism.
Fault cause:
33 (= 21 hex):
The cyclic telegram has not been received.
34 (= 22 hex):
Timeout in the telegram receive list.
64 (= 40 hex):
Timeout in the telegram send list.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- carry out a POWER ON.
- replace the component involved.
Note:
HF Damping Module
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1437
SINAMICS alarms
237836
<location>HF Damping Module: Send error for DRIVE-CLiQ data
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
There is a DRIVE-CLiQ communication error between the Control Unit and the HF Damping Module. Data were not able to
be sent.
Fault cause:
65 (= 41 hex):
Telegram type does not match send list.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
Carry out a POWER ON.
Note:
HF Damping Module
237837
<location>HF Damping Module: Component faulted
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
Fault detected on the DRIVE-CLiQ component concerned. Faulty hardware cannot be excluded.
Fault cause:
32 (= 20 hex):
Error in the telegram header.
35 (= 23 hex):
Receive error: The telegram buffer memory contains an error.
66 (= 42 hex):
Send error: The telegram buffer memory contains an error.
67 (= 43 hex):
Send error: The telegram buffer memory contains an error.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
- check the electrical cabinet design and cable routing for EMC compliance
- if required, use another DRIVE-CLiQ socket (p9904).
- replace the component involved.
Note:
HF Damping Module
237845
<location>HF Damping Module: Cyclic data transmission error
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Alarms
1438
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
There is a DRIVE-CLiQ communication error between the Control Unit and the HF Damping Module.
Fault cause:
11 (= 0B hex):
Synchronization error during alternating cyclic data transfer.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
Carry out a POWER ON.
Note:
HF Damping Module
237850
<location>HF Damping Module: Internal software error
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
OFF1 (NONE, OFF2, OFF3)
Acknowledge:
POWER ON
Cause:
An internal software error in the HF Damping Module has occurred.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- Replace the HF Damping Module
- if required, upgrade the firmware in the HF Damping Module.
- contact Technical Support.
Note:
HF Damping Module
237851
<location>HF Damping Module (CU): Sign-of-life missing
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
DRIVE-CLiQ communication error from the HF Damping Module to the Control Unit.
The DRIVE-CLiQ component did not set the sign-of-life to the Control Unit.
Fault cause:
10 (= 0A hex):
The sign-of-life bit in the receive telegram is not set.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
Upgrade the firmware of the component involved.
Note:
HF Damping Module
237860
<location>HF Damping Module (CU): Telegram error
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1439
SINAMICS alarms
Cause:
DRIVE-CLiQ communication error from the HF Damping Module to the Control Unit.
Fault cause:
1 (= 01 hex):
Checksum error (CRC error).
2 (= 02 hex):
Telegram is shorter than specified in the length byte or in the receive list.
3 (= 03 hex):
Telegram is longer than specified in the length byte or in the receive list.
4 (= 04 hex):
The length of the receive telegram does not match the receive list.
5 (= 05 hex):
The type of the receive telegram does not match the receive list.
6 (= 06 hex):
The address of the power unit in the telegram and in the receive list do not match.
9 (= 09 hex):
The DRIVE-CLiQ communication from the DRIVE-CLiQ component involved to the Control Unit signals that the supply voltage
has failed.
16 (= 10 hex):
The receive telegram is too early.
17 (= 11 hex):
CRC error and the receive telegram is too early.
18 (= 12 hex):
The telegram is shorter than that specified in the length byte or in the receive list and the receive telegram is too early.
19 (= 13 hex):
The telegram is longer than that specified in the length byte or in the receive list and the receive telegram is too early.
20 (= 14 hex):
The length of the receive telegram does not match the receive list and the receive telegram is too early.
21 (= 15 hex):
The type of the receive telegram does not match the receive list and the receive telegram is too early.
22 (= 16 hex):
The address of the power unit in the telegram and in the receive list does not match and the receive telegram is too early.
25 (= 19 hex):
The error bit in the receive telegram is set and the receive telegram is too early.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- check the electrical cabinet design and cable routing for EMC compliance
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
Note:
HF Damping Module
237875
<location>HF Damping Module: power supply voltage failed
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Alarms
1440
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
The DRIVE-CLiQ communication from the DRIVE-CLiQ component involved to the Control Unit signals that the supply voltage
has failed.
Fault cause:
9 (= 09 hex):
The power supply voltage for the components has failed.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- check the power supply voltage wiring for the DRIVE-CLiQ component (interrupted cable, contacts, ...).
- check the dimensioning of the power supply for the DRIVE-CLiQ component.
237885
<location>HF Damping Module (CU): Cyclic data transmission error
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
DRIVE-CLiQ communication error from the damping module to the Control Unit.
The nodes do not send and receive in synchronism.
Fault cause:
26 (= 1A hex):
Sign-of-life bit in the receive telegram not set and the receive telegram is too early.
33 (= 21 hex):
The cyclic telegram has not been received.
34 (= 22 hex):
Timeout in the telegram receive list.
64 (= 40 hex):
Timeout in the telegram send list.
98 (= 62 hex):
Error at the transition to cyclic operation.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- check the supply voltage of the component involved.
- carry out a POWER ON.
- replace the component involved.
Note:
HF Damping Module
237886
<location>HF Damping Module (CU): Error when sending DRIVE-CLiQ data
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1441
SINAMICS alarms
Cause:
DRIVE-CLiQ communication error from the HF Damping Module to the Control Unit.
Data were not able to be sent.
Fault cause:
65 (= 41 hex):
Telegram type does not match send list.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
Carry out a POWER ON.
Note:
HF Damping Module
237887
<location>HF Damping Module (CU): Component faulted
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
Fault detected on the DRIVE-CLiQ component (HF Damping Module) involved. Faulty hardware cannot be excluded.
Fault cause:
32 (= 20 hex):
Error in the telegram header.
35 (= 23 hex):
Receive error: The telegram buffer memory contains an error.
66 (= 42 hex):
Send error: The telegram buffer memory contains an error.
67 (= 43 hex):
Send error: The telegram buffer memory contains an error.
96 (= 60 hex):
Response received too late during runtime measurement.
97 (= 61 hex):
Time taken to exchange characteristic data too long.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
- check the electrical cabinet design and cable routing for EMC compliance
- if required, use another DRIVE-CLiQ socket (p9904).
- replace the component involved.
Note:
HF Damping Module
237895
<location>HF Damping Module (CU): Alternating cyclic data transmission error
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
Component number: %1, fault cause: %2
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Alarms
1442
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
DRIVE-CLiQ communication error from the HF Damping Module to the Control Unit.
Fault cause:
11 (= 0B hex):
Synchronization error during alternating cyclic data transfer.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
Carry out a POWER ON.
Note:
HF Damping Module
237896
<location>HF Damping Module (CU): Component properties inconsistent
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
Component number: %1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The properties of the DRIVE-CLiQ component (HF Damping Module), specified by the fault value, have changed in an
incompatible fashion with respect to the properties when booted. One cause can be, e.g. that a DRIVE-CLiQ cable or DRIVE-
CLiQ component has been replaced.
Fault value (r0949, interpret decimal):
Component number.
Remedy:
- carry out a POWER ON.
- when a component is replaced, the same component type and if possible the same firmware version should be used.
- when a cable is replaced, only cables whose length is the same as or as close as possible to the length of the original cables
should be used (ensure compliance with the maximum cable length).
Note:
HF Damping Module
237899
<location>HF Damping Module: Unknown fault
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
New message: %1
Reaction:
NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
A fault has occurred on the HF Damping Module that cannot be interpreted by the Control Unit firmware.
This can occur if the firmware on this component is more recent than the firmware on the Control Unit.
Fault value (r0949, interpret decimal):
Fault number.
Note:
If required, the significance of this new fault can be read about in a more recent description of the Control Unit.
Remedy:
- replace the firmware on the HF Damping Module by an older firmware version (r0168).
- upgrade the firmware on the Control Unit (r0018).
Note:
HF Damping Module
237903
<location>HF Damping Module: I2C bus error occurred
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2)
Acknowledge:
IMMEDIATELY
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1443
SINAMICS alarms
Cause:
Communications error with an EEPROM or an analog/digital converter.
Fault value (r0949, interpret hexadecimal):
80000000 hex:
- internal software error.
00000001 hex ... 0000FFFF hex:
- module fault.
Remedy:
For fault value = 80000000 hex:
- upgrade firmware to later version.
For fault value = 00000001 hex ... 0000FFFF hex:
- replace the module.
Note:
HF Damping Module
237950
<location>HF Damping Module: Internal software error
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
An internal software error has occurred.
Fault value (r0949, interpret decimal):
Information about the fault source.
Only for internal Siemens troubleshooting.
Remedy:
- if necessary, upgrade the firmware in the HF Damping Module to a later version.
- contact Technical Support.
Note:
HF Damping Module
237999
<location>HF Damping Module: Unknown alarm
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
New message: %1
Reaction:
NONE
Acknowledge:
NONE
Cause:
An alarm has occurred on the HF Damping Module that cannot be interpreted by the Control Unit firmware.
This can occur if the firmware on this component is more recent than the firmware on the Control Unit.
Alarm value (r2124, interpret decimal):
Alarm number.
Note:
If required, the significance of this new alarm can be read about in a more recent description of the Control Unit.
Remedy:
- replace the firmware on the HF Damping Module by an older firmware version (r0168).
- upgrade the firmware on the Control Unit (r0018).
Note:
HF Damping Module
240000
<location>Fault at DRIVE-CLiQ socket X100
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Alarms
1444
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
A fault has occurred at the drive object at the DRIVE-CLiQ socket X100.
Fault value (r0949, interpret decimal):
First fault that has occurred for this drive object.
Remedy:
Evaluate the fault buffer of the specified object.
240001
<location>Fault at DRIVE-CLiQ socket X101
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A fault has occurred at the drive object at the DRIVE-CLiQ socket X101.
Fault value (r0949, interpret decimal):
First fault that has occurred for this drive object.
Remedy:
Evaluate the fault buffer of the specified object.
240002
<location>Fault at DRIVE-CLiQ socket X102
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A fault has occurred at the drive object at the DRIVE-CLiQ socket X102.
Fault value (r0949, interpret decimal):
First fault that has occurred for this drive object.
Remedy:
Evaluate the fault buffer of the specified object.
240003
<location>Fault at DRIVE-CLiQ socket X103
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A fault has occurred at the drive object at the DRIVE-CLiQ socket X103.
Fault value (r0949, interpret decimal):
First fault that has occurred for this drive object.
Remedy:
Evaluate the fault buffer of the specified object.
240004
<location>Fault at DRIVE-CLiQ socket X104
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A fault has occurred at the drive object at the DRIVE-CLiQ socket X104.
Fault value (r0949, interpret decimal):
First fault that has occurred for this drive object.
Remedy:
Evaluate the fault buffer of the specified object.
240005
<location>Fault at DRIVE-CLiQ socket X105
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1445
SINAMICS alarms
Acknowledge:
IMMEDIATELY
Cause:
A fault has occurred at the drive object at the DRIVE-CLiQ socket X105.
Fault value (r0949, interpret decimal):
First fault that has occurred for this drive object.
Remedy:
Evaluate the fault buffer of the specified object.
240100
<location>Alarm at DRIVE-CLiQ socket X100
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
An alarm has occurred at the drive object at the DRIVE-CLiQ socket X100.
Alarm value (r2124, interpret decimal):
First alarm that has occurred for this drive object.
Remedy:
Evaluate the alarm buffer of the specified object.
240101
<location>Alarm at DRIVE-CLiQ socket X101
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
An alarm has occurred at the drive object at the DRIVE-CLiQ socket X101.
Alarm value (r2124, interpret decimal):
First alarm that has occurred for this drive object.
Remedy:
Evaluate the alarm buffer of the specified object.
240102
<location>Alarm at DRIVE-CLiQ socket X102
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
An alarm has occurred at the drive object at the DRIVE-CLiQ socket X102.
Alarm value (r2124, interpret decimal):
First alarm that has occurred for this drive object.
Remedy:
Evaluate the alarm buffer of the specified object.
240103
<location>Alarm at DRIVE-CLiQ socket X103
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
An alarm has occurred at the drive object at the DRIVE-CLiQ socket X103.
Alarm value (r2124, interpret decimal):
First alarm that has occurred for this drive object.
Remedy:
Evaluate the alarm buffer of the specified object.
240104
<location>Alarm at DRIVE-CLiQ socket X104
Drive object:
All objects
Message value:
%1
Alarms
1446
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Reaction:
NONE
Acknowledge:
NONE
Cause:
An alarm has occurred at the drive object at the DRIVE-CLiQ socket X104.
Alarm value (r2124, interpret decimal):
First alarm that has occurred for this drive object.
Remedy:
Evaluate the alarm buffer of the specified object.
240105
<location>Alarm at DRIVE-CLiQ socket X105
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
An alarm has occurred at the drive object at the DRIVE-CLiQ socket X105.
Alarm value (r2124, interpret decimal):
First alarm that has occurred for this drive object.
Remedy:
Evaluate the alarm buffer of the specified object.
240799
<location>CX32: Configured transfer end time exceeded
Drive object:
All objects
Message value:
-
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The configured transfer end time when transferring the cyclic actual values was exceeded.
Remedy:
- carry out a POWER ON (switch-off/switch-on) for all components.
- contact Technical Support.
240801
<location>CX32 DRIVE-CLiQ: Sign-of-life missing
Drive object:
All objects
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred from the Control Unit to the controller extension involved.
Fault cause:
10 (= 0A hex):
The sign-of-life bit in the receive telegram is not set.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- replace the component involved.
240820
<location>CX32 DRIVE-CLiQ: Telegram error
Drive object:
All objects
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1447
SINAMICS alarms
Cause:
A DRIVE-CLiQ communications error has occurred from the Control Unit to the controller extension involved.
Fault cause:
1 (= 01 hex):
Checksum error (CRC error).
2 (= 02 hex):
Telegram is shorter than specified in the length byte or in the receive list.
3 (= 03 hex):
Telegram is longer than specified in the length byte or in the receive list.
4 (= 04 hex):
The length of the receive telegram does not match the receive list.
5 (= 05 hex):
The type of the receive telegram does not match the receive list.
6 (= 06 hex):
The address of the component in the telegram and in the receive list do not match.
7 (= 07 hex):
A SYNC telegram is expected - but the received telegram is not a SYNC telegram.
8 (= 08 hex):
No SYNC telegram is expected - but the received telegram is one.
9 (= 09 hex):
The error bit in the receive telegram is set.
16 (= 10 hex):
The receive telegram is too early.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- check the electrical cabinet design and cable routing for EMC compliance
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
240825
<location>CX32 DRIVE-CLiQ: Supply voltage failed
Drive object:
All objects
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
The DRIVE-CLiQ communication from the DRIVE-CLiQ component involved to the Control Unit signals that the supply voltage
has failed.
Fault cause:
9 (= 09 hex):
The power supply voltage for the components has failed.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- check the supply voltage wiring of the DRIVE-CLiQ component (interrupted cable, contacts, ...).
- check the dimensioning of the DRIVE-CLiQ component power supply.
240835
<location>CX32 DRIVE-CLiQ: Cyclic data transfer error
Drive object:
All objects
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Alarms
1448
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
A DRIVE-CLiQ communications error has occurred from the Control Unit to the controller extension involved. The nodes do
not send and receive in synchronism.
Fault cause:
33 (= 21 hex):
The cyclic telegram has not been received.
34 (= 22 hex):
Timeout in the telegram receive list.
64 (= 40 hex):
Timeout in the telegram send list.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- replace the component involved.
240836
<location>CX32 DRIVE-CLiQ: Send error for DRIVE-CLiQ data
Drive object:
All objects
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred from the Control Unit to the controller extension involved. Data were not
able to be sent.
Fault cause:
65 (= 41 hex):
Telegram type does not match send list.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
Carry out a POWER ON (switch-off/switch-on).
240837
<location>CX32 DRIVE-CLiQ: Component fault
Drive object:
All objects
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
Fault detected on the DRIVE-CLiQ component concerned. Faulty hardware cannot be excluded.
Fault cause:
32 (= 20 hex):
Error in the telegram header.
35 (= 23 hex):
Receive error: The telegram buffer memory contains an error.
66 (= 42 hex):
Send error: The telegram buffer memory contains an error.
67 (= 43 hex):
Send error: The telegram buffer memory contains an error.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1449
SINAMICS alarms
Remedy:
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
- check the electrical cabinet design and cable routing for EMC compliance
- if required, use another DRIVE-CLiQ socket (p9904).
- replace the component involved.
240845
<location>CX32 DRIVE-CLiQ: Cyclic data transfer error
Drive object:
All objects
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred from the Control Unit to the controller extension involved.
Fault cause:
11 (= 0B hex):
Synchronization error during alternating cyclic data transfer.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
Carry out a POWER ON (switch-off/switch-on).
240851
<location>CX32 DRIVE-CLiQ (CU): Sign-of-life missing
Drive object:
All objects
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred from the controller extension involved to the Control Unit.
The DRIVE-CLiQ component did not set the sign-of-life to the Control Unit.
Fault cause:
10 (= 0A hex):
The sign-of-life bit in the receive telegram is not set.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
Upgrade the firmware of the component involved.
240860
<location>CX32 DRIVE-CLiQ (CU): Telegram error
Drive object:
All objects
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Alarms
1450
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
A DRIVE-CLiQ communications error has occurred from the controller extension involved to the Control Unit.
Fault cause:
1 (= 01 hex):
Checksum error (CRC error).
2 (= 02 hex):
Telegram is shorter than specified in the length byte or in the receive list.
3 (= 03 hex):
Telegram is longer than specified in the length byte or in the receive list.
4 (= 04 hex):
The length of the receive telegram does not match the receive list.
5 (= 05 hex):
The type of the receive telegram does not match the receive list.
6 (= 06 hex):
The address of the power unit in the telegram and in the receive list do not match.
9 (= 09 hex):
The error bit in the receive telegram is set.
16 (= 10 hex):
The receive telegram is too early.
17 (= 11 hex):
CRC error and the receive telegram is too early.
18 (= 12 hex):
The telegram is shorter than that specified in the length byte or in the receive list and the receive telegram is too early.
19 (= 13 hex):
The telegram is longer than that specified in the length byte or in the receive list and the receive telegram is too early.
20 (= 14 hex):
The length of the receive telegram does not match the receive list and the receive telegram is too early.
21 (= 15 hex):
The type of the receive telegram does not match the receive list and the receive telegram is too early.
22 (= 16 hex):
The address of the power unit in the telegram and in the receive list does not match and the receive telegram is too early.
25 (= 19 hex):
The error bit in the receive telegram is set and the receive telegram is too early.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- check the electrical cabinet design and cable routing for EMC compliance
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
240875
<location>CX32 DRIVE-CLiQ (CU): Supply voltage failed
Drive object:
All objects
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
The DRIVE-CLiQ communication from the DRIVE-CLiQ component involved to the Control Unit signals that the supply voltage
has failed.
Fault cause:
9 (= 09 hex):
The power supply voltage for the components has failed.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1451
SINAMICS alarms
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- check the supply voltage wiring of the DRIVE-CLiQ component (interrupted cable, contacts, ...).
- check the dimensioning of the DRIVE-CLiQ component power supply.
240885
<location>CX32 DRIVE-CLiQ (CU): Cyclic data transfer error
Drive object:
All objects
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred from the controller extension involved to the Control Unit.
The nodes do not send and receive in synchronism.
Fault cause:
26 (= 1A hex):
Sign-of-life bit in the receive telegram not set and the receive telegram is too early.
33 (= 21 hex):
The cyclic telegram has not been received.
34 (= 22 hex):
Timeout in the telegram receive list.
64 (= 40 hex):
Timeout in the telegram send list.
98 (= 62 hex):
Error at the transition to cyclic operation.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- check the power supply voltage of the component involved.
- carry out a POWER ON (switch-off/switch-on).
- replace the component involved.
240886
<location>CX32 DRIVE-CLiQ (CU): Error when sending DRIVE-CLiQ data
Drive object:
All objects
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred from the controller extension involved to the Control Unit.
Data were not able to be sent.
Fault cause:
65 (= 41 hex):
Telegram type does not match send list.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
Carry out a POWER ON (switch-off/switch-on).
240887
<location>CX32 DRIVE-CLiQ (CU): Component fault
Drive object:
All objects
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Alarms
1452
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
Fault detected on the DRIVE-CLiQ component concerned. Faulty hardware cannot be excluded.
Fault cause:
32 (= 20 hex):
Error in the telegram header.
35 (= 23 hex):
Receive error: The telegram buffer memory contains an error.
66 (= 42 hex):
Send error: The telegram buffer memory contains an error.
67 (= 43 hex):
Send error: The telegram buffer memory contains an error.
96 (= 60 hex):
Response received too late during runtime measurement.
97 (= 61 hex):
Time taken to exchange characteristic data too long.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
- check the electrical cabinet design and cable routing for EMC compliance
- if required, use another DRIVE-CLiQ socket (p9904).
- replace the component involved.
240895
<location>CX32 DRIVE-CLiQ (CU): Cyclic data transfer error
Drive object:
All objects
Message value:
Component number: %1, fault cause: %2
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred from the controller extension involved to the Control Unit.
Fault cause:
11 (= 0B hex):
Synchronization error during alternating cyclic data transfer.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
Carry out a POWER ON (switch-off/switch-on).
249150
<location>Cooling unit: Fault occurred
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The cooling unit signals a general fault.
Remedy:
- check the wiring between the cooling unit and the input terminal (Terminal Module).
- check the external control device for the cooling unit.
See also: p0266 (Cooling unit feedback signals signal source)
249151
<location>Cooling unit: Conductivity has exceeded the fault threshold
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
OFF2
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1453
SINAMICS alarms
Acknowledge:
IMMEDIATELY
Cause:
The conductivity of the cooling liquid has exceeded the selected fault threshold (p0269[2]).
See also: p0261 (Cooling unit starting time 2), p0262 (Cooling unit fault conductivity delay time), p0266 (Cooling unit
feedback signals signal source)
Remedy:
Check the device to de-ionize the cooling liquid.
249152
<location>Cooling unit: ON command feedback signal missing
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The feedback signal of the ON command of the cooling unit is missing.
- after the ON command, the feedback signal has not been received within the selected starting time (p0260).
- the feedback signal has failed in operation.
- the cooling unit was stopped by an external signal.
See also: p0260 (Cooling unit starting time 1), r0267 (Cooling unit status word)
Remedy:
- check the wiring between the cooling unit and the input terminal (Terminal Module).
- check the wiring between the output terminal (Terminal Module) and the cooling unit.
- check the external control device for the cooling unit.
249153
<location>Cooling unit: Liquid flow too low
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The drive converter cooling unit signals that the cooling liquid flow is too low.
- after the ON command, the feedback signal has not been received within the selected starting time (p0260).
- in operation, the feedback signal has failed for longer than the permitted failure time (p0263).
See also: p0260 (Cooling unit starting time 1), p0263 (Cooling unit fault liquid flow delay time), r0267 (Cooling unit status
word)
Remedy:
- check the wiring between the cooling unit and the input terminal (Terminal Module).
- check the external control device for the cooling unit.
249154
<location>Cooling unit: Liquid leak is present
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The liquid leakage monitoring function has responded.
Caution:
If this fault is reparameterized as an alarm, then using other monitoring functions it must be ensured that when cooling
water is lost, the drive is switched off!
See also: r0267 (Cooling unit status word)
Remedy:
- check the cooling system for leaks in the cooling circuit.
- check the wiring of the input terminal (Terminal Module) used to monitor leaking fluid.
249155
<location>Cooling unit: Power Stack Adapter, firmware version too old
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
OFF2
Alarms
1454
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Acknowledge:
POWER ON
Cause:
The firmware version in the Power Stack Adapter (PSA) is too old and does not support the liquid cooling.
Remedy:
Upgrade the firmware. Check EEPROM data.
249156
<location>Cooling unit: Cooling liquid temperature has exceeded the fault threshold
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The cooling liquid intake temperature has exceeded the specified fault threshold.
Note:
The value for the fault threshold depends on the power unit (hardware description data, e.g. 52 ... 55 °C).
Remedy:
Check the cooling system and the ambient conditions.
249170
<location>Cooling unit: Alarm has occurred
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The cooling unit signals a general alarm.
Remedy:
- check the wiring between the cooling unit and the input terminal (Terminal Module).
- check the external control device for the cooling unit.
249171
<location>Cooling unit: Conductivity has exceeded the alarm threshold
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The conductivity of the cooling liquid has exceeded the selected alarm threshold (p0269[1]).
Note:
The threshold cannot be set higher than the fault threshold specified in the equipment description.
Remedy:
Check the device to de-ionize the cooling liquid.
249171
<location>Cooling unit: Conductivity has exceeded the alarm threshold
Drive object:
VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
Conductivity monitoring is set for the cooling liquid (r0267.7, from p0266[7]).
See also: p0261, p0262, p0266, r0267
Remedy:
Check the device to de-ionize the cooling liquid.
249172
<location>Cooling unit: Conductivity actual value is not valid
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
When monitoring the conductivity of the cooling liquid, there is a fault in the wiring or in the sensor.
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1455
SINAMICS alarms
Remedy:
- check the wiring between the cooling unit and the Power Stack Adapter (PSA).
- check the function of the sensor to measure the conductivity.
249173
<location>Cooling unit: Cooling liquid temperature has exceeded the alarm threshold
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The cooling liquid intake temperature has exceeded the specified alarm threshold.
Note:
The value for the alarm threshold depends on the power unit (hardware description data, e.g. 42 ... 50 °C).
Remedy:
Check the cooling system and the ambient conditions.
249200
<location>Excitation group signal fault
Drive object:
VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The excitation sequence control signals a fault.
Fault value (r0949, interpret binary):
Bit 0:
When switched off or when switching off the excitation, the signal "excitation ready feedback signal" was not received within
the monitoring time.
Bit 1:
After an ON command, the signal "excitation ready feedback signal" was not received within the monitoring time.
Bit 2:
After the pulses were enabled, the signal "excitation operational feedback signal" was not received within the monitoring
time.
Bit 3:
The "excitation group signal fault" signal is present.
Bit 4:
The switch-on command for the excitation was reset, although pulse enable (r0899.11) is still available, or the excitation
current actual value has still not fallen below a minimum value.
Note:
This signal can be generated via p6500[59].
Remedy:
- check the excitation.
- check commands, feedback signals and BICO interconnections.
- re bit 4: increase the switch-off delay time (p1647).
249201
<location>Excitation group signal alarm
Drive object:
VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The "excitation group signal alarm" signal is present.
Note:
This signal can be generated via p6500[58].
Remedy:
Check the excitation equipment.
Alarms
1456
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
249204
<location>Excitation switch-off alarm
Drive object:
VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
When switching off the excitation, after the delay time (p1647) has expired, the excitation current has still not decayed to
zero.
Remedy:
Extend the switch-off delay time in (p1647).
Note:
The alarm is automatically withdrawn after adapting p1647.
See also: p1647 (Excitation switch-off delay time)
249205
<location>Excitation: incorrect parameterization of the brushless exciter
Drive object:
VECTOR, VECTOR_AC
Message value:
Parameter: %1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The brushless exciter has not been completely parameterized. The speed-dependent ratio cannot be calculated. As a
consequence, it is assumed to be 1.
Alarm value (r2124, interpret decimal):
Parameter number that is assigned an illegal value.
See also: p0699 (Excitation configuration)
Remedy:
Set a value <> 0 for the parameter that is displayed.
See also: p0690, p0691, p0692, p0693, p0694, p0696, p0697, p0698
249920
<location>Protective breaker main circuit tripped
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_I_840, CU_LINK, ENC, ENC_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840,
SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL,
VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The protective breaker in the main circuit of the power supply has tripped.
Note:
This message is output via the signal source of binector input p6577[1] of the Control Unit.
See also: p6577 (Circuit monitoring functions signal source)
Remedy:
Check the main circuit.
249921
<location>Protective breaker redundant main circuit tripped
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_I_840, CU_LINK, ENC, ENC_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840,
SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL,
VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The protective breaker in the main circuit for the redundant feed to the power supply has tripped.
Note:
This message is output via the signal source of binector input p6577[2] of the Control Unit.
See also: p6577 (Circuit monitoring functions signal source)
Remedy:
Check the redundant main circuit.
Alarms