|
|
1A–48 HEATING, VENTILATION AND AIR CONDITIONING (HVAC) O-rings (2) must be fitted in the groove (1) of refrigerant 850RW003 Insert the nut into the union. Leak Check Inspection of refrigerant leak Refrigerant leak may cause an adverse effect not only Inspection flow of refrigerant leak Inspection Steps Check the components of air-conditioner to see if there • To avoid an error in the detection of refrigerant leak, make sure of there being no refrigerant vapor or • Inspection should be conducted chiefly on the pipe connections and sections where a marked oil • It is possible to visually check the leak from inside the cooling unit. Follow the method below when cooling unit, and insert a leak detector to see if there High Pressure Side 1. Discharger section of compressor. 2. Inlet/outlet section of condenser. 3. Inlet/outlet section of receiver driver. 4. Inlet section of cooling unit. Low Pressure Side 1. Outlet section of cooling unit. 2. Intake section of compressor. Step Action Yes No 1 1. Evacuate the refrigerant system. 2. Charge the refrigerant. Is there any refrigerant leak? Repair refrigerant system. Go to Step 2. 2 1. Operate the compressor for more than 5 minutes to raise the pressure on the high pressure side. Is there any refrigerant leak at high pressure components? Repair refrigerant system. Compressor operation to be confirmed. |