SINAMICS alarms
207998
<location>Drive: Motor data identification active on another drive
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The motor data identification is activated on the drive object specified in the alarm value, and interlocks the other drive
objects so they cannot be switched on.
Alarm value (r2124, interpret decimal):
Drive object with the active motor data identification.
See also: p1910, p1960
Remedy:
- wait for the complete execution of the motor data identification of the drive object designated in the alarm value.
- deselect the motor data identification for the drive object designated in the alarm value (p1910 = 0 or p1960 = 0).
207999
<location>Drive: Motor data identification cannot be activated
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
Closed-loop control is enabled on a SERVO drive object type. To select motor data identification, pulses must be suppressed
for all SERVO drive objects.
Alarm value (r2124, interpret decimal):
Drive object with enabled closed-loop control.
Remedy:
Withdraw the pulse enable on all drives and re-activate the motor data identification.
208000
<location>TB: +/-15 V power supply faulted
Drive object:
All objects
Message value:
%1
Reaction:
Infeed: NONE (OFF1, OFF2)
Servo: NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2)
Vector: NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2)
Hla: NONE (OFF1, OFF2, OFF3, STOP2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
Terminal Board 30 detects an incorrect internal power supply voltage.
Fault value (r0949, interpret decimal):
0: Error when testing the monitoring circuit.
1: Fault in normal operation.
Remedy:
- replace Terminal Board 30.
- replace Control Unit.
208010
<location>TB: Analog-digital converter
Drive object:
All objects
Message value:
-
Reaction:
Infeed: NONE (OFF1, OFF2)
Servo: NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2)
Vector: OFF1 (IASC/DCBRK, NONE, OFF2, OFF3, STOP2)
Hla: NONE (OFF1, OFF2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The analog/digital converter on Terminal Board 30 has not supplied any converted data.
Remedy:
- check the power supply.
- replace Terminal Board 30.
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1113
SINAMICS alarms
208500
<location>COMM BOARD: Monitoring time configuration expired
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S120_DP, CU_S120_PN, ENC, ENC_840, HLA, HLA_840, HUB, R_INF,
S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
Infeed: OFF1 (OFF2)
Servo: OFF1 (OFF2, OFF3)
Vector: OFF1 (OFF2, OFF3)
Hla: OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The monitoring time for the configuration has expired.
Fault value (r0949, interpret decimal):
0: The transfer time of the send configuration data has been exceeded.
1: The transfer time of the receive configuration data has been exceeded.
Remedy:
Check communications link.
208501
<location>PN/COMM BOARD: Setpoint timeout
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, ENC, ENC_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840,
SERVO_AC, TM120, TM150, TM15DI_DO, TM31, TM41, VECTOR, VECTOR_AC
Message value:
-
Reaction:
Infeed: OFF1 (OFF2)
Servo: OFF3 (IASC/DCBRK, NONE, OFF1, OFF2, STOP2)
Vector: OFF3 (IASC/DCBRK, NONE, OFF1, OFF2, STOP2)
Hla: OFF3 (NONE, OFF1, OFF2, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
The reception of setpoints from the COMM BOARD has been interrupted.
- bus connection interrupted.
- controller switched off.
- controller set into the STOP state.
- COMM BOARD defective.
Remedy:
- Restore the bus connection and set the controller to RUN.
- if the error is repeated, check the update time set in the bus configuration (HW Config).
See also: p8840 (COMM BOARD monitoring time)
208502
<location>PN/COMM BOARD: Monitoring time sign-of-life expired
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_PN, ENC, ENC_840,
HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO,
TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
-
Reaction:
Infeed: OFF1 (OFF2)
Servo: OFF1 (OFF2, OFF3)
Vector: OFF1 (OFF2, OFF3)
Hla: OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The monitoring time for the sign-of-life counter has expired.
The connection to the COMM BOARD was interrupted.
Remedy:
- check communications link.
- check COMM BOARD.
Alarms
1114
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
208504
<location>PN/COMM BOARD: Internal cyclic data transfer error
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S120_DP, CU_S120_PN, ENC, ENC_840, HLA, HLA_840, HUB, R_INF,
S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The cyclic actual and/or setpoint values were not transferred within the specified times.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
Check the parameterizing telegram (Ti, To, Tdp, etc.).
208510
<location>PN/COMM BOARD: Send configuration data invalid
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S120_DP, CU_S120_PN, ENC, ENC_840, HLA, HLA_840, HUB, R_INF,
S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
Infeed: OFF1 (OFF2)
Servo: OFF1 (OFF2, OFF3)
Vector: OFF1 (OFF2, OFF3)
Hla: OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
COMM BOARD did not accept the send-configuration data.
Fault value (r0949, interpret decimal):
Return value of the send-configuration data check.
Remedy:
Check the send configuration data.
208511
<location>PN/COMM BOARD: Receive configuration data invalid
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_PN, ENC, ENC_840,
HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO,
TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The drive unit did not accept the receive configuration data.
Alarm value (r2124, interpret decimal):
Return value of the receive configuration data check.
1: Connection established to more drive objects than configured in the device. The drive objects for process data exchange
and their sequence are defined in p0978.
2: Too many PZD data words for output or input to a drive object. The number of possible PZD items in a drive object is
determined by the number of indices in r2050/p2051 for PZD IF1, and in r8850/p8851 for PZD IF2.
3: Uneven number of bytes for input or output.
4: Setting data for synchronization not accepted. For more information, see A01902.
5: Cyclic operation not active.
17: CBE20 Shared Device: Configuration of the F-CPU has been changed.
223: Illegal clock synchronization for the PZD interface set in p8815[0].
257: PN Shared Device: Too many PZD data words for output or input in the overall device.
500: Illegal PROFIsafe configuration for the interface set in p8815[1].
501: PROFIsafe parameter error (e.g. F_dest).
503: PROFIsafe connection is rejected as long as there is no isochronous connection (p8969).
Additional values:
Only for internal Siemens troubleshooting.
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1115
SINAMICS alarms
Remedy:
Check the receive configuration data.
For alarm value = 1, 2:
- check the list of the drive objects with process data exchange (p0978). With p0978[x] = 0, all of the following drive objects
in the list are excluded from the process data exchange.
For alarm value = 2:
- check the number of data words for output and input to a drive object.
For alarm value = 17:
- CBE20 Shared Device: Unplug/plug A-CPU.
For alarm value = 223, 500:
- check the setting in p8839 and p8815.
- ensure that only one PZD interface is operated in clock synchronism or with PROFIsafe.
For alarm value = 257:
- check the number of data words for output and input to the complete device.
For alarm value = 501:
- check the set PROFIsafe address (p9610).
208520
<location>PN/COMM BOARD: Non-cyclic channel error
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S120_DP, CU_S120_PN, ENC, ENC_840, HLA, HLA_840, HUB, R_INF,
S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The memory or the buffer status of the non-cyclic channel has an error.
Alarm value (r2124, interpret decimal):
0: Error in the buffer status.
1: Error in the memory.
Remedy:
Check communications link.
208526
<location>PN/COMM BOARD: No cyclic connection
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_PN, ENC, ENC_840,
HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO,
TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
There is no cyclic connection to the control.
Remedy:
Establish the cyclic connection and activate the control with cyclic operation.
For PROFINET, check the parameters "Name of Station" and "IP of Station" (r61000, r61001).
If a CBE20 is inserted and PROFIBUS is to communicate via PZD Interface 1, then this must be parameterized using the
STARTER commissioning tool or directly using p8839.
208530
<location>PN/COMM BOARD: Message channel error
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S120_DP, CU_S120_PN, ENC, ENC_840, HLA, HLA_840, HUB, R_INF,
S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Alarms
1116
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
The memory or the buffer status of the message channel has an error.
Alarm value (r2124, interpret decimal):
0: Error in the buffer status.
1: Error in the memory.
Remedy:
Check communications link.
208531
<location>CBE20 POWER ON required
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S120_DP, CU_S120_PN, ENC, ENC_840, HLA, HLA_840, HUB, R_INF,
S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
At least one parameter of the CBE20 (e.g. a parameter associated with SINAMICS Link) was changed as a result of a project
download. A POWER ON is required to activate the values.
Note:
CBE20: Communication Board Ethernet 20
See also: p8811, p8812, p8835, p8836
Remedy:
Back up the parameters and carry out a POWER ON (switch-off/switch-on).
208550
<location>PZD Interface Hardware assignment error
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_I_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_PN, ENC,
ENC_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150,
TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The assignment of the hardware to the PZD interface has been incorrectly parameterized.
Alarm value (r2124, interpret decimal):
1: Only one of the two indices is not equal to 99 (automatic).
2: Both PZD interfaces are assigned to the same hardware.
3: Assigned COMM BOARD missing.
4: CBC10 is assigned to interface 1.
See also: p8839 (PZD interface hardware assignment)
Remedy:
Check the parameterization and if required, correct (p8839).
208555
<location>Modbus TCP: commissioning error
Drive object:
CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_PN
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
A setting for the "Modbus TCP" protocol is incorrect.
Alarm value (r2124, interpret decimal):
1: Modbus simultaneously activated on the onboard interface (p2030) and CBE20 (p8835). CBE20 is not activated.
2: A drive object supported by Modbus is not available under p0978[0]. Modbus is not activated.
3: drive object SERVO is under p0978[0] - and FM bit LINMOT is set, Modbus is not activated.
3: drive object SERVO with activated linear motor function is under p0978[0]. Modbus is not activated.
See also: p0978, p2030, p8835
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1117
SINAMICS alarms
Remedy:
For alarm value = 1:
Check the parameterization and if required, correct (p2030, p8835).
For alarm value = 2, 3:
Appropriately resort the list of drive objects in p0978.
Modbus supports the following drive object: SERVO (without linear motor), VECTOR
208560
<location>IE: Syntax error in configuration file
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_PN, ENC, ENC_840,
HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO,
TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
A syntax error has been detected in the ASCII configuration file for the Industrial Ethernet interface (X127). The saved
configuration file has not been loaded.
Note:
IE: Industrial Ethernet
Remedy:
- Check the interface configuration (p8900 and following), correct if necessary, and activate (p8905 = 1).
- Save the parameters for interface configuration (e.g. p8905 = 2)
or
- reinitialize the station using the "Edit Ethernet node" screen form (e.g. with STARTER commissioning tool).
See also: p8905 (Activate IE interface configuration)
208561
<location>IE: Consistency error affecting adjustable parameters
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_PN, ENC, ENC_840,
HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO,
TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
A consistency error was detected when activating the configuration (p8905) for the Industrial Ethernet interface (X127).
Alarm value (r2124, interpret decimal):
0: general consistency error
1: error in the IP configuration (IP address, subnet mask or standard gateway).
2: Error in the station names.
5: standard gateway is also set at the PROFINET onboard interface.
6: the station name is also set at the PROFINET onboard interface.
7: IP address is located in the same subnet as the IP address of the PROFINET onboard interface.
Note:
For alarm value = 0, 1, 2, 5, 7 the following applies: the configuration was not changed.
For alarm value = 6 the following applies: The new configuration was however activated.
IE: Industrial Ethernet
See also: p8900 (IE Name of Station), p8901 (IE IP address), p8902 (IE default gateway), p8903 (IE Subnet Mask)
Remedy:
- check the required interface configuration (p8900 and following), correct if necessary, and activate (p8905).
or
- reinitialize the station using the "Edit Ethernet node" screen form (e.g. with STARTER commissioning tool).
See also: p8905 (Activate IE interface configuration)
208562
<location>PROFINET: Syntax error in configuration file
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_PN, ENC, ENC_840,
HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO,
TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Alarms
1118
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
A syntax error has been detected in the ASCII configuration file for the onboard PROFINET interface. The saved configuration
file has not been loaded.
Remedy:
- Check the interface configuration (p8920 and following), correct if necessary, and activate (p8925 = 1).
- Save the parameters for interface configuration (e.g. p8925 = 2).
or
- reinitialize the station using the "Edit Ethernet node" screen form (e.g. with STARTER commissioning tool).
See also: p8925 (Activate PN interface configuration)
208563
<location>PROFINET: Consistency error affecting adjustable parameters
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_PN, ENC, ENC_840,
HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO,
TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
A consistency error was detected when activating the configuration (p8925) for the PROFINET interface.
Alarm value (r2124, interpret decimal):
0: general consistency error
1: error in the IP configuration (IP address, subnet mask or standard gateway).
2: Name of station error.
3: DHCP was not able to be activated, as a cyclic PROFINET connection already exists.
4: a cyclic PROFINET connection is not possible as DHCP is activated.
5: standard gateway is also set at the Industrial Ethernet interface (X127).
6: standard station name is also set at the Industrial Ethernet interface (X127).
7: IP address is located in the same subnet as the IP address of the Industrial Ethernet interface (X127).
Note:
For alarm value = 0, 1, 2, 3, 4, 5, 7, the following applies: the configuration was not changed.
For alarm value = 6 the following applies: The new configuration was however activated.
DHCP: Dynamic Host Configuration Protocol
See also: p8920, p8921, p8922, p8923
Remedy:
- check the required interface configuration (p8940 and following), correct if necessary, and activate (p8945).
or
- reinitialize the station using the "Edit Ethernet node" screen form (e.g. with STARTER commissioning tool).
See also: p8925 (Activate PN interface configuration)
208564
<location>PN/COMM BOARD: syntax error in the configuration file
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_PN, ENC, ENC_840,
HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO,
TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
A syntax error has been detected in the ASCII configuration file for the Communication Board Ethernet 20/25/41 (CBE20/
CBE25/CBE41). The saved configuration file has not been loaded.
Remedy:
- Correct and activate the CBExx configuration (p8940 and following) (p8945 = 2).
- Reinitialize the CBExx (e.g. using the STARTER commissioning tool)
Note:
The configuration is not applied until the next POWER ON!
See also: p8945 (CBExx activate configuration of interfaces)
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1119
SINAMICS alarms
208565
<location>PNCOMM BOARD: Consistency error affecting adjustable parameters
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_PN, ENC, ENC_840,
HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO,
TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
A consistency error was detected when activating the configuration (p8945) for the Communication Board Ethernet
20/25/41 (CBE20/CBE25/CBE41).
Alarm value (r2124, interpret decimal):
0: general consistency error
1: error in the IP configuration (IP address, subnet mask or standard gateway).
2: Error in the station names.
3: DHCP was not able to be activated, as a cyclic PROFINET connection already exists.
4: a cyclic PROFINET connection is not possible as DHCP is activated.
Note:
For all alarm values, the following applies: currently set configuration has not been activated.
DHCP: Dynamic Host Configuration Protocol
See also: p8940 (CBExx name of station), p8941 (CBExx IP address), p8942 (CBExx default gateway), p8943 (CBExx subnet
mask), p8944 (CBExx DHCP mode)
Remedy:
- check the required interface configuration (p8940 and following), correct if necessary, and activate (p8945).
or
- reinitialize the station using the "Edit Ethernet node" screen form (e.g. with STARTER commissioning tool).
See also: p8945 (CBExx activate configuration of interfaces)
208700
<location>CAN: Communications error
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S120_DP, CU_S120_PN, ENC, ENC_840, HLA, HLA_840, HUB, R_INF,
S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
Infeed: NONE (OFF1, OFF2)
Servo: OFF3 (NONE, OFF1, OFF2)
Vector: OFF3 (NONE, OFF1, OFF2)
Hla: OFF3 (NONE, OFF1, OFF2)
Acknowledge:
IMMEDIATELY
Cause:
A CAN communications error has occurred.
Fault value (r0949, interpret decimal):
1: The error counter for the send telegrams has exceeded the BUS OFF value 255. The bus disables the CAN controller.
- bus cable short circuit.
- incorrect baud rate.
- incorrect bit timing.
2: The master no longer interrogated the CAN node status longer than for its "life time". The "life time" is obtained from the
"guard time" (p8604[0]) multiplied by the "life time factor" (p8604[1]).
- bus cable interrupted.
- bus cable not connected.
- incorrect baud rate.
- incorrect bit timing.
- master fault.
See also r8843.2 IF2 PZD status - fieldbus running.
Note:
The fault response can be set as required using p8641.
See also: p8604 (CAN life guarding), p8641 (CAN Abort Connection Option Code), r8843 (IF2 PZD state)
Alarms
1120
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Remedy:
- check the bus cable
- check the baud rate (p8622).
- check the bit timing (p8623).
- check the master.
The CAN controller must be manually restarted with p8608 = 1 after the cause of the fault has been resolved!
See also: p8608 (CAN Clear Bus Off Error), p8622 (CAN bit rate), p8623 (CAN Bit Timing selection)
208701
<location>CAN: NMT state change
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S120_DP, CU_S120_PN, ENC, ENC_840, HLA, HLA_840, HUB, R_INF,
S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
Infeed: OFF2
Servo: OFF3
Vector: OFF3
Hla: OFF3
Acknowledge:
IMMEDIATELY
Cause:
A CANopen NMT state transition from "operational" to "pre-operational" or after "stopped".
Fault value (r0949, interpret decimal):
1: CANopen NMT state transition from "operational" to "pre-operational".
2: CANopen NMT state transition from "operational" to "stopped".
Note:
In the NMT state "pre-operational", process data cannot be transferred and in the NMT state "stopped", no process data and
no service data can be transferred.
Remedy:
Not necessary.
Acknowledge the fault and continue operation.
208702
<location>CAN: RPDO Timeout
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S120_DP, CU_S120_PN, ENC, ENC_840, HLA, HLA_840, HUB, R_INF,
S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
-
Reaction:
Infeed: OFF2 (NONE, OFF1)
Servo: OFF3 (NONE, OFF1, OFF2)
Vector: OFF3 (NONE, OFF1, OFF2)
Hla: OFF3 (NONE, OFF1, OFF2)
Acknowledge:
IMMEDIATELY
Cause:
The monitoring time of the CANopen RPDO telegram has expired because the bus connection was either interrupted or the
CANopen Master was switched-off.
See also r8843.0 IF2 PZD status - setpoint failure or r8843.2 IF2 PZD status - fieldbus running.
See also: p8699 (CAN: RPDO monitoring time), r8843 (IF2 PZD state)
Remedy:
- check the bus cable
- check the master.
- If required, increase the monitoring time (p8699).
208703
<location>CAN: Maximum number of drive objects exceeded
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S120_DP, CU_S120_PN, ENC, ENC_840, HLA, HLA_840, HUB, R_INF,
S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
-
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1121
SINAMICS alarms
Reaction:
Infeed: OFF2 (NONE, OFF1)
Servo: OFF3 (NONE, OFF1, OFF2)
Vector: OFF3 (NONE, OFF1, OFF2)
Hla: OFF3 (NONE, OFF1, OFF2)
Acknowledge:
IMMEDIATELY
Cause:
The maximum number of 8 drive objects with the "CAN" function module was exceeded.
Note:
In the CANopen standard, a maximum of 8 CANopen device modules (drive objects with function module "CAN") are
defined for each CANopen slave.
Remedy:
- New commissioning of maximum 8 drive objects with the "CAN" function module in the topology.
- For the drive objects, if required, deselect the "CAN" function module (r0108.29).
208751
<location>CAN: Telegram loss
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S120_DP, CU_S120_PN, ENC, ENC_840, HLA, HLA_840, HUB, R_INF,
S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The CAN controller has lost a receive message.
Alarm value (r2124, interpret decimal):
Hardware channel in the CAN controller.
0: Firmware version < 5.2 (no reference to the original hardware channel).
1: NMT command message
2: SYNC message
3: NMT error control message
7 ... 31: RPDO message
32: SDO message
Remedy:
- increase the cycle times of the received messages.
- CANopen reduce sampling time (p8848).
See also: p8848 (IF2 PZD sampling time)
208752
<location>CAN: Error counter for error passive exceeded
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S120_DP, CU_S120_PN, ENC, ENC_840, HLA, HLA_840, HUB, R_INF,
S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The error counter for the send or receive telegrams has exceeded the value 127.
Remedy:
- check the bus cable
- set a higher baud rate (p8622).
- check the bit timing and if required optimize (p8623).
See also: p8622 (CAN bit rate), p8623 (CAN Bit Timing selection)
208753
<location>CAN: Message buffer overflow
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S120_DP, CU_S120_PN, ENC, ENC_840, HLA, HLA_840, HUB, R_INF,
S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Alarms
1122
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Acknowledge:
NONE
Cause:
A message buffer overflow.
Alarm value (r2124, interpret decimal):
1: Non-cyclic send buffer (SDO response buffer) overflow.
2: Non-cyclic receive buffer (SDO receive buffer) overflow.
3: Cyclic send buffer (PDO send buffer) overflow.
Remedy:
- check the bus cable.
- set a higher baud rate (p8622).
- check the bit timing and if required optimize (p8623).
For alarm value = 2:
- reduce the cycle times of the SDO receive messages.
- SDO request from master only after SDO feedback for previous SDO request.
See also: p8622 (CAN bit rate), p8623 (CAN Bit Timing selection)
208754
<location>CAN: Incorrect communications mode
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S120_DP, CU_S120_PN, ENC, ENC_840, HLA, HLA_840, HUB, R_INF,
S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
In the "operational" mode, an attempt was made to change parameters p8700 ... p8737.
Remedy:
Change to the "pre-operational" or "stopped" mode.
208755
<location>CAN: Object cannot be mapped
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S120_DP, CU_S120_PN, ENC, ENC_840, HLA, HLA_840, HUB, R_INF,
S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The CANopen object is not provided for the Process Data Object (PDO) Mapping.
Remedy:
Use a CANopen object intended for the PDO mapping or enter 0.
The following objects can be mapped in the Receive Process Data Object (RPDO) or Transmit Process Data Object (TPDO):
- RPDO: 6040 hex, 6060 hex, 60FF hex, 6071 hex; 5800 hex - 580F hex; 5820 hex - 5827 hex
- TPDO: 6041 hex, 6061 hex, 6063 hex, 6069 hex, 606B hex, 606C hex, 6074 hex; 5810 hex - 581F hex; 5830 hex - 5837
hex
Only sub-index 0 of the specified objects can be mapped.
Note:
As long as A08755 is present, the COB-ID cannot be set to valid.
208756
<location>CAN: Number of mapped bytes exceeded
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S120_DP, CU_S120_PN, ENC, ENC_840, HLA, HLA_840, HUB, R_INF,
S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The number of bytes of the mapped objects exceeds the telegram size for net data. A max. of 8 bytes is permissible.
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1123
SINAMICS alarms
Remedy:
Map fewer objects or objects with a smaller data type.
See also: p8710, p8711, p8712, p8713, p8714, p8715, p8716, p8717, p8730, p8731, p8732, p8733, p8734, p8735,
p8736, p8737
208757
<location>CAN: Set COB-ID invalid
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S120_DP, CU_S120_PN, ENC, ENC_840, HLA, HLA_840, HUB, R_INF,
S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
For online operation, the appropriate COB-ID must be set invalid before mapping.
Example:
Mapping for RPDO 1 should be changed (p8710[0]).
--> set p8700[0] = C00006E0 hex (invalid COB-ID)
--> set p8710[0] as required.
--> p8700[0] enter a valid COB-ID
Remedy:
Set the COB-ID to invalid.
208758
<location>CAN: Maximum number of valid PDO exceeded
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S120_DP, CU_S120_PN, ENC, ENC_840, HLA, HLA_840, HUB, R_INF,
S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
An attempt was made to exceed the maximum number of valid PDO.
Alarm value (r2124, interpret decimal):
1:
An attempt was made to exceed the total number of valid RPDO of all CANopen supported drive objects.
As a result of the hardware, the limit is 25 valid RPDO.
2:
An attempt was made to exceed the total number of valid TPDO of all CANopen supported drive objects.
The limit is defined by the following ratio:
CAN sampling time (p8848) / CAN minimum processing time (r8739)
Note:
RPDO: Receive Process Data Object
TPDO: Transmit Process Data Object
See also: r8739 (Minimum CAN processing time), r8742 (CAN PDO available number)
Remedy:
Comply with the limit for the maximum number of valid RPDO or TPDO.
Apply one of the following options to delete the alarm:
- successfully write to the COB ID index of a PDO communication parameter (p870x[0], p872x[0]).
- change CANopen NMT state.
- execute CANopen NMT command reset node.
- execute CANopen NMT command reset communication.
- carry out a warm restart (p0009 = 30, p0976 = 2).
- carry out a POWER ON (switch-off/switch-on).
Note:
The remaining available RPDO or TPDO are indicated in r8742.
Alarms
1124
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
208759
<location>CAN: PDO COB-ID already available
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S120_DP, CU_S120_PN, ENC, ENC_840, HLA, HLA_840, HUB, R_INF,
S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
Parameter: %1
Reaction:
NONE
Acknowledge:
NONE
Cause:
An existing PDO COB-ID was allocated.
Alarm value (r2124, interpret decimal):
Parameter number.
Note:
The COB-ID is included in index zero (p870x[0], p872x[0]).
Remedy:
Select another PDO COB-ID.
208760
<location>CAN: maximum size of the IF PZD exceeded
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S120_DP, CU_S120_PN, ENC, ENC_840, HLA, HLA_840, HUB, R_INF,
S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The maximum size of the IF PZD was exceeded.
Alarm value (r2124, interpret decimal):
1: error for IF PZD receive.
2: error for IF PZD send.
Note:
IF: interface
Remedy:
Map fewer process data in PDO.
Apply one of the following options to delete the alarm:
- POWER ON (switch-off/switch-on).
- carry out a warm restart (p0009 = 30, p0976 = 2).
- execute CANopen NMT command reset node.
- change CANopen NMT state.
- delete alarm buffer [0...7] (p2111 = 0).
208800
<location>PROFIenergy energy-saving mode active
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_PN, ENC, ENC_840,
HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO,
TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The PROFIenergy energy-saving mode is active
Alarm value (r2124, interpret decimal):
Mode ID of the active PROFIenergy energy-saving mode.
See also: r5600 (Pe energy-saving mode ID)
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1125
SINAMICS alarms
Remedy:
The alarm is automatically withdrawn when the energy-saving mode is exited.
Note:
The energy-saving mode is exited after the following events:
- the PROFIenergy command end_pause is received from the higher-level control.
- the higher-level control has changed into the STOP operating state.
- the PROFINET connection to the higher-level control has been disconnected.
209000
<location>Web server user incorrectly configured
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_PN, ENC, ENC_840,
HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO,
TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
An error occurred when configuring the web server user.
Fault value (r0949, interpret decimal):
0: No admin password
1: Invalid admin password
2: Invalid SINAMICS password
Remedy:
Correct the user configuration, enter a correct password.
213000
<location>License not adequate
Drive object:
All objects
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
- For the converter, the options that require a license are being used but the licenses are not sufficient.
- an error occurred when checking the existing licenses.
Fault value (r0949, interpret decimal):
0:
The existing license is not sufficient.
1:
An adequate license was not able to be determined as the memory card with the required licensing data was withdrawn in
operation.
2:
An adequate license was not able to be determined as there is no licensing data available on the memory card.
3:
An adequate license was not able to be determined as there is a checksum error in the license key.
4:
An internal error occurred when checking the license.
Alarms
1126
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Remedy:
For fault value = 0:
Additional licenses are required and these must be activated (p9920, p9921).
For fault value = 1:
With the system powered down, re-insert the memory card that matches the system.
For fault value = 2:
Enter and activate the license key (p9920, p9921).
For fault value = 3:
Compare the license key (p9920) entered with the license key on the Certificate of License.
Re-enter the license key and activate (p9920, p9921).
For fault value = 4:
- carry out a POWER ON.
- upgrade firmware to later version.
- contact Technical Support.
Note:
An overview of the converter functions requiring a license can be displayed using a commissioning tool in the online mode.
Depending on the commissioning tool, you can obtain the necessary licenses (serial number, license Key, Trial License
Mode).
213001
<location>Error in license checksum
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_PN, ENC, ENC_840,
HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO,
TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
When checking the checksum of the license key, an error was detected.
Remedy:
Compare the license key (p9920) entered with the license key on the Certificate of License.
Re-enter the license key and activate (p9920, p9921).
213009
<location>Licensing Technology Extension not licensed
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_PN, ENC, ENC_840,
HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO,
TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF1
Acknowledge:
IMMEDIATELY
Cause:
At least one Technology Extension that requires a license does not have a license.
Note:
Refer to r4955 and p4955 for information about the installed Technology Extensions.
Remedy:
- enter and activate the license key for Technology Extensions that require a license (p9920, p9921).
- if necessary, deactivate Technology Extensions that are not licensed (p4956).
See also: p9920 (Licensing enter license key), p9921 (Licensing activate license key)
213010
<location>Licensing function module not licensed
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_PN, ENC, ENC_840,
HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO,
TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF1
Acknowledge:
IMMEDIATELY
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1127
SINAMICS alarms
Cause:
At least one function module requiring a license is not licensed.
Fault value (r0949, interpret hexadecimal):
Bit x = 1: The corresponding function module does not have a license.
Note:
Assigning bit number to function module, see p0108 or r0108.
Remedy:
- enter and activate the license key for function modules that require a license license (p9920, p9921).
- if necessary, deactivate unlicensed function modules (p0108, r0108).
See also: p9920 (Licensing enter license key), p9921 (Licensing activate license key)
213020
<location>Licensing not sufficient in the control
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_I_840, CU_LINK, ENC, ENC_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840,
SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL,
VECTOR, VECTOR_AC
Message value:
-
Reaction:
OFF1
Acknowledge:
IMMEDIATELY
Cause:
For the drive unit, the options that require a license are being used but the licenses are not sufficient.
Remedy:
- enter and activate the license key for options that require a license.
- if necessary, deactivate unlicensed options.
213021
<location>Licensing for output frequencies > 550 Hz missing
Drive object:
All objects
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
Configuring the converter results in an output frequency greater than 550 Hz. This function requires a license. The "High
Output Frequency" license is required.
Note:
- in this specific case, the output frequency is limited to 550 Hz.
- the "Trial License" function is not effective for license "High Output Frequency".
Remedy:
- enter and activate the license key for "High Output Frequency" and activate (p9920, p9921).
- if necessary operate the motor below the output frequency of 550 Hz.
213030
<location>Trial License activated
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_PN, ENC, ENC_840,
HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO,
TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The "Trial License" function was activated. One of the available periods is expiring.
See also: p9918 (Licensing active Trial License), r9919 (Licensing Trial License status)
Remedy:
Not necessary.
The alarm is automatically withdrawn after the periods have expired.
213031
<location>Trial License period expired
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_PN, ENC, ENC_840,
HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO,
TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Alarms
1128
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Acknowledge:
NONE
Cause:
One of the available periods of the "Trial License" function has expired.
See also: p9918 (Licensing active Trial License), r9919 (Licensing Trial License status)
Remedy:
- if required, start an additional period (p9918 = 1).
- deactivate functions requiring a license.
- appropriately license the drive unit.
Note:
A license that is not adequate will only become evident after the next time the system runs up.
213032
<location>Trial License last period activated
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_PN, ENC, ENC_840,
HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO,
TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The "Trial License" function was activated. The last of the available periods is expiring.
See also: p9918 (Licensing active Trial License), r9919 (Licensing Trial License status)
Remedy:
Not necessary.
The alarm is automatically withdrawn after the last period has expired.
213033
<location>Trial License last period expired
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_PN, ENC, ENC_840,
HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO,
TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The last period of the "Trial License" function has expired. No additional periods available.
See also: p9918 (Licensing active Trial License), r9919 (Licensing Trial License status)
Remedy:
- deactivate functions requiring a license.
- appropriately license the drive unit.
Note:
A license that is not adequate will only become evident after the next time the system runs up.
213100
<location>Know-how protection: Copy protection error
Drive object:
All objects
Message value:
%1
Reaction:
OFF1
Acknowledge:
IMMEDIATELY
Cause:
The know-how protection with copy protection for the memory card is active.
An error has occurred when checking the memory card.
Fault value (r0949, interpret decimal):
0: A memory card is not inserted.
2: An invalid memory card is inserted.
3: The memory card is being used in another Control Unit.
12: An invalid memory card is inserted (OEM input incorrect, p7769).
13: The memory card is being used in another Control Unit (OEM input incorrect, p7759).
See also: p7765 (KHP configuration)
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1129
SINAMICS alarms
Remedy:
For fault value = 0:
- insert the correct memory card and carry out POWER ON.
For fault value = 2, 3, 12, 13:
- contact the responsible OEM.
- Deactivate copy protection (p7765) and acknowledge the fault (p3981).
- Deactivate know-how protection (p7766 ... p7768) and acknowledge the fault (p3981).
Note:
In general, the copy protection can only be changed when know-how protection is deactivated.
KHP: Know-How Protection
See also: p3981, p7765
213101
<location>Know-how protection: Copy protection cannot be activated
Drive object:
All objects
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
An error occurred when attempting to activate the copy protection for the memory card.
Fault value (r0949, interpret decimal):
0: A memory card is not inserted.
Note:
KHP: Know-How Protection
Remedy:
- insert the memory card and carry out POWER ON.
- Try to activate copy protection again (p7765).
See also: p7765 (KHP configuration)
213102
<location>Know-how protection: Consistency error of the protected data
Drive object:
All objects
Message value:
%1
Reaction:
OFF1
Acknowledge:
IMMEDIATELY
Cause:
An error was identified when checking the consistency of the protected files. As a consequence, the project on the memory
card cannot be run.
Fault value (r0949, interpret hexadecimal):
yyyyxxxx hex: yyyy = object number, xxxx = fault cause
xxxx = 1:
A file has a checksum error.
xxxx = 2:
The files are not consistent with one another.
xxxx = 3:
The project files, which were loaded into the file system via load (download from the memory card), are inconsistent.
Note:
KHP: Know-How Protection
Remedy:
- Replace the project on the memory card or replace project files for download from the memory card.
- Restore the factory setting and download again.
230001
<location>Power unit: Overcurrent
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
Fault cause: %1 bin
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Alarms
1130
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
The power unit has detected an overcurrent condition.
- closed-loop control is incorrectly parameterized.
- motor has a short-circuit or fault to ground (frame).
- U/f operation: Up ramp set too low.
- U/f operation: Rated motor current is significantly greater than that of the Motor Module.
- infeed: High discharge and post-charging currents for line voltage dip.
- infeed: High post-charging currents for overload when motoring and DC link voltage dip.
- infeed: Short-circuit currents at switch-on as there is no commutating reactor.
- power cables are not correctly connected.
- the power cables exceed the maximum permissible length.
- power unit defective.
- line phase interrupted.
Additional causes for a parallel switching device (r0108.15 = 1):
- a power unit has tripped (switched off) due to a ground fault.
- the closed-loop circulating current control is either too slow or has been set too fast.
Fault value (r0949, interpret bitwise binary):
Bit 0: Phase U.
Bit 1: Phase V.
Bit 2: Phase W.
Bit 3: Overcurrent in the DC link.
Note:
Fault value = 0 means that the phase with overcurrent is not recognized (e.g. for blocksize device).
Remedy:
- check the motor data - if required, carry out commissioning.
- check the motor circuit configuration (star/delta).
- U/f operation: Increase up ramp.
- U/f operation: Check the assignment of the rated currents of the motor and Motor Module.
- infeed: Check the line supply quality.
- infeed: Reduce the motor load.
- infeed: Check the correct connection of the line filter and the line commutating reactor.
- check the power cable connections.
- check the power cables for short-circuit or ground fault.
- check the length of the power cables.
- replace power unit.
- check the line supply phases.
For a parallel switching device (r0108.15 = 1) the following additionally applies:
- check the ground fault monitoring thresholds (p0287).
- check the setting of the closed-loop circulating current control (p7036, p7037).
230002
<location>Power unit: DC link voltage overvoltage
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The power unit has detected overvoltage in the DC link.
- motor regenerates too much energy.
- device supply voltage too high.
- when operating with a Voltage Sensing Module (VSM), the phase assignment L1, L2, L3 at the VSM differs from the phase
assignment at the power unit.
- line phase interrupted.
Fault value (r0949, interpret decimal):
DC link voltage at the time of trip [0.1 V].
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1131
SINAMICS alarms
Remedy:
- increase the ramp-down time
- activate the DC link voltage controller (p1240)
- use a brake resistor or Active Line Module
- increase the current limit of the infeed or use a larger component (for the Active Line Module)
- check the device supply voltage
- check and correct the phase assignment at the VSM and at the power unit
- check the line supply phases.
See also: p0210, p1240
230002
<location>Power unit: DC link voltage overvoltage
Drive object:
VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The power unit has detected overvoltage in the DC link.
- motor regenerates too much energy.
- device supply voltage too high.
- when operating with a Voltage Sensing Module (VSM), the phase assignment L1, L2, L3 at the VSM differs from the phase
assignment at the power unit.
- line phase interrupted.
Fault value (r0949, interpret decimal):
DC link voltage at the time of trip [0.1 V].
Remedy:
- increase the ramp-down time
- activate the DC link voltage controller
- use a brake resistor or Active Line Module
- increase the current limit of the infeed or use a larger component (for the Active Line Module)
- check the device supply voltage
- check and correct the phase assignment at the VSM and at the power unit
- check the line supply phases.
- set the rounding times (p1130, p1136). This is particularly recommended in U/f operation to relieve the DC link voltage
controller with rapid ramp-down times of the ramp-function generator.
See also: p0210, p1240
230003
<location>Power unit: DC link voltage undervoltage
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The power unit has detected an undervoltage condition in the DC link.
- line supply failure
- line supply voltage below the permissible value.
- line supply infeed failed or interrupted.
- line phase interrupted.
Note:
The monitoring threshold for undervoltage in the DC link is indicated in r0296.
Alarms
1132
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Remedy:
- check the line supply voltage
- check the line supply infeed and observe the fault messages relating to it (if there are any)
- check the line supply phases.
- check the line supply voltage setting (p0210).
- booksize units: check the setting of p0278.
Note:
The ready signal for the infeed (r0863) must be interconnected to the associated drive inputs (p0864).
See also: p0210
230004
<location>Power unit: Overtemperature heat sink AC inverter
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The temperature of the power unit heat sink has exceeded the permissible limit value.
- insufficient cooling, fan failure.
- overload.
- ambient temperature too high.
- pulse frequency too high.
Fault value (r0949, interpret decimal):
Temperature [0.01 °C].
Remedy:
- check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
- check the motor load.
- reduce the pulse frequency if this is higher than the rated pulse frequency.
Notice:
This fault can only be acknowledged after the alarm threshold for alarm A05000 has been undershot.
See also: p1800
230005
<location>Power unit: Overload I2t
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The power unit was overloaded (r0036 = 100 %).
- the permissible rated power unit current was exceeded for an inadmissibly long time.
- the permissible load duty cycle was not maintained.
Fault value (r0949, interpret decimal):
I2t [100 % = 16384].
Remedy:
- reduce the continuous load.
- adapt the load duty cycle.
- check the motor and power unit rated currents.
See also: r0036, r0206, p0307
230005
<location>Power unit: Overload I2t
Drive object:
VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1133
SINAMICS alarms
Cause:
The power unit was overloaded (r0036 = 100 %).
- the permissible rated power unit current was exceeded for an inadmissibly long time.
- the permissible load duty cycle was not maintained.
Fault value (r0949, interpret decimal):
I2t [100 % = 16384].
Remedy:
- reduce the continuous load.
- adapt the load duty cycle.
- check the motor and power unit rated currents.
- increase p0294
See also: r0036, r0206, p0307
230006
<location>Power unit: Thyristor Control Board
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The Thyristor Control Board (TCB) of the Basic Line Module signals a fault.
- there is no line supply voltage.
- the line contactor is not closed.
- the line supply voltage is too low.
- line supply frequency outside the permissible range (45 ... 66 Hz).
- there is a DC link short-circuit.
- there is a DC link short-circuit (during the precharging phase).
- the motor either has a short-circuit or insulation fault (from an inverter connected to the DC link).
- voltage supply for the Thyristor Control Board outside the nominal range (5 ... 18 V) and line voltage >30 V.
- there is an internal fault in the Thyristor Control Board.
Remedy:
The faults must be saved in the Thyristor Control Board and must be acknowledged. To do this, the supply voltage of the
Thyristor Control Board must be switched out for at least 10 s!
- check the line supply voltage
- check or energize the line contactor.
- check the monitoring time and, if required, increase (p0857).
- if required, observe additional power unit messages/signals.
- check the DC link regarding short-circuit or ground fault.
- check the motor regarding short-circuit or ground fault.
- evaluate diagnostic LEDs for the Thyristor Control Board.
230008
<location>Power unit: Sign-of-life error cyclic data
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
Infeed: NONE (OFF1, OFF2)
Servo: NONE (OFF1, OFF2, OFF3)
Vector: NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The Control Unit has not punctually updated the cyclic setpoint telegram to the power unit. The number of consecutive
tolerated sign of life errors has exceeded the fault threshold (p7789) set in the power unit.
Remedy:
- for projects with the VECTOR drive object, check whether p0117 = 6 has been set on the Control Unit.
- increase the fault threshold (p7789).
- check the Motor Module, and if required replace.
See also: p0117 (Current controller computing dead time mode)
Alarms
1134
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
230010
<location>Power unit: Sign-of-life error cyclic data
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
A DRIVE-CLiQ communication error has occurred between the Control Unit and the power unit involved.
The cyclic setpoint telegrams of the Control Unit were not received on time by the power unit for at least one clock cycle.
Remedy:
Check the Motor Module and if required, replace.
230011
<location>Power unit: Line phase failure in main circuit
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2 (OFF1)
Acknowledge:
IMMEDIATELY
Cause:
At the power unit, the DC link voltage ripple has exceeded the permissible limit value.
Possible causes:
- a line phase has failed.
- the 3 line phases are inadmissibly asymmetrical.
- the capacitance of the DC link capacitor forms a resonance frequency with the line inductance and the reactor integrated
in the power unit.
- the fuse of a phase of a main circuit has ruptured.
- a motor phase has failed.
- for power units operated on a single phase, the permissible active power was exceeded.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- check the main circuit fuses.
- check whether a single-phase load is distorting the line voltages.
- Detune the resonant frequency with the line inductance by using an upstream line reactor.
- Dampen the resonant frequency with the line inductance by switching over the DC link voltage compensation in the
software (see p1810) - or increase the smoothing (see p1806). However, this can have a negative impact on the torque
ripple at the motor output.
- check the motor feeder cables.
230012
<location>Power unit: Temperature sensor wire breakage
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1135
SINAMICS alarms
Cause:
The connection to a temperature sensor in the power unit is interrupted.
Fault value (r0949, interpret binary):
Bit 0: Module slot (electronics slot)
Bit 1: Air intake
Bit 2: Inverter 1
Bit 3: Inverter 2
Bit 4: Inverter 3
Bit 5: Inverter 4
Bit 6: Inverter 5
Bit 7: Inverter 6
Bit 8: Rectifier 1
Bit 9: Rectifier 2
Bit 14: Capacitor air discharge
Bit 15: Liquid intake
Remedy:
Contact Technical Support.
230013
<location>Power unit: Temperature sensor short circuit
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
A temperature sensor in the power unit is short-circuited.
Fault value (r0949, interpret binary):
Bit 0: Module slot (electronics slot)
Bit 1: Air intake
Bit 2: Inverter 1
Bit 3: Inverter 2
Bit 4: Inverter 3
Bit 5: Inverter 4
Bit 6: Inverter 5
Bit 7: Inverter 6
Bit 8: Rectifier 1
Bit 9: Rectifier 2
Bit 14: Capacitor air discharge
Bit 15: Liquid intake
Remedy:
Contact Technical Support.
230015
<location>Power unit: Phase failure motor cable
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
-
Reaction:
OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
A phase failure in the motor feeder cable was detected.
The signal can also be output in the following case:
- the motor is correctly connected, however the closed-speed control is instable and therefore an oscillating torque is
generated.
Note:
Chassis power units do not feature phase failure monitoring.
Remedy:
- check the motor feeder cables.
- check the speed controller settings.
Alarms
1136
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
230015
<location>Power unit: Phase failure motor cable
Drive object:
VECTOR, VECTOR_AC
Message value:
-
Reaction:
OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
A phase failure in the motor feeder cable was detected.
The signal can also be output in the following cases:
- the motor is correctly connected, but the drive has stalled in U/f control. In this case, a current of 0 A is possibly measured
in one phase due to asymmetry of the currents.
- the motor is correctly connected, however the closed-speed control is instable and therefore an oscillating torque is
generated.
Note:
Chassis power units do not feature phase failure monitoring.
Remedy:
- check the motor feeder cables.
- increase the ramp-up or ramp-down time (p1120) if the drive has stalled in U/f control.
- check the speed controller settings.
230016
<location>Power unit: Load supply switched off
Drive object:
SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The DC link voltage is too low.
Alarm value (r2124, interpret decimal):
DC link voltage at the time of the trip [V].
Remedy:
- switch on load supply.
- check the line supply if necessary.
230017
<location>Power unit: 26.5 V supply voltage fault
Drive object:
HLA, HLA_840
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
For a drive that has been enabled, it has been identified that the 26.5 V supply voltage for the Hydraulic Module has a fault
(X271).
Permissible range: 26.0 ... 27.0 V
Fault value (r0949, interpret decimal):
Voltage value [0.1 V].
Remedy:
- check the 26.5 V supply voltage (X271).
230017
<location>Power unit: Hardware current limit has responded too often
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
Fault cause: %1 bin
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1137
SINAMICS alarms
Cause:
The hardware current limitation in the relevant phase (see A30031, A30032, A30033) has responded too often. The
number of times the limit has been exceeded depends on the design and type of power unit.
For infeed units, the following applies:
- closed-loop control is incorrectly parameterized.
- load on the infeed is too high.
- Voltage Sensing Module incorrectly connected.
- line reactor missing or the incorrect type.
- power unit defective.
The following applies to Motor Modules:
- closed-loop control is incorrectly parameterized.
- fault in the motor or in the power cables.
- the power cables exceed the maximum permissible length.
- motor load too high
- power unit defective.
Fault value (r0949, interpret binary):
Bit 3: phase U
Bit 4: phase V
Bit 5: phase W
Additional bits:
Only for internal Siemens troubleshooting.
Note:
Fault value = 0 means that the phase with current limiting is not recognized (e.g. for blocksize device).
Remedy:
For infeed units, the following applies:
- check the controller settings and reset and identify the controller if necessary (p0340 = 2, p3410 = 5)
- reduce the load and increase the DC link capacitance or use a higher-rating infeed if necessary
- check the connection of the optional Voltage Sensing Module
- check the connection and technical data of the commutating reactor.
- check the power cables for short-circuit or ground fault.
- replace power unit.
The following applies to Motor Modules:
- check the motor data and if required, recalculate the controller parameters (p0340 = 3). As an alternative, run a motor data
identification (p1910 = 1, p1960 = 1).
- check the motor circuit configuration (star-delta).
- check the motor load.
- check the power cable connections.
- check the power cables for short-circuit or ground fault.
- check the length of the power cables.
- replace power unit.
230020
<location>Power unit: Configuration not supported
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
fault cause: %1, additional information: %2
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Alarms
1138
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
A configuration is requested that is not supported by the power unit.
Fault value (r0949, interpret hexadecimal):
yyyyxxxx hex: xxxx = fault cause, yyyy = additional information (internal Siemens)
xxxx = 0: Autonomous operation is requested but is not supported.
xxxx = 1: The requested DRIVE-CLiQ timing is not permissible.
xxxx = 2: A PM260 has been detected with PS-ASIC version 2. This combination is not supported.
xxxx = 3: Initialization was not able to be successfully completed. It is possible that the Control Unit was withdrawn from the
Power Module before or during power up.
xxxx = 4: The combination of power unit and Control Unit or Control Unit Adapter is not supported.
xxxx = 5: The higher current controller dynamic performance is not supported.
xxxx = 6: it is not permitted to operate the Motor Module with this Control Unit and firmware version.
Remedy:
For fault cause = 0:
If required, deactivate an active internal voltage protection (p1231).
For fault cause = 1:
Update the Control Unit firmware or change the DRIVE-CLiQ topology.
For fault cause = 2:
Replace the power unit with a PM260 with PS-ASIC version 3 (or higher).
For fault cause = 3, 4:
Insert a Control Unit or Control Unit Adapter (CUAxx) on an appropriate Power Module and perform a POWER ON for the
Control Unit or the Control Unit Adapter.
For fault cause = 5:
- use a booksize format power unit.
- for a Double Motor Module operate the two drive controls with the same current controller sampling time (p0115[0]).
Otherwise, the higher current controller dynamics can only be activated on the drive with the longer sampling time.
- if required, deselect the higher current controller dynamic performance (p1810.11 = 0). After deselecting the computing
dead time, recalculate the controller gains (p0340 = 4). If required, optimize the speed controller.
For fault cause = 6:
- use a suitable Motor Module.
- use a Control Unit with approved firmware version.
See also: p0115, p1231, p1810
230021
<location>Power unit: Ground fault
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1139
SINAMICS alarms
Cause:
The power has detected a ground fault.
Possible causes:
- ground fault in the power cables.
- ground fault at the motor.
- CT defective.
- when the brake closes, this causes the hardware DC current monitoring to respond.
- short-circuit at the braking resistor.
- the closed-loop circulating current control for devices connected in parallel (r0108.15 = 1) is either too slow or has been
set too fast.
Note:
For power units, a ground fault is also emulated in r3113.5.
Fault value (r0949, interpret decimal):
0:
- the hardware DC current monitoring has responded.
- short-circuit at the braking resistor.
> 0:
Absolute value, total current amplitude [20479 = r0209 * 1.4142].
Remedy:
- check the power cable connections.
- check the motor.
- check the CT.
- check the cables and contacts of the brake connection (a wire is possibly broken).
- check the braking resistor.
For parallel switching devices (r0108.15 = 1) the following additionally applies:
- check the ground fault monitoring thresholds (p0287).
- check the setting of the closed-loop circulating current control (p7036, p7037).
See also: p0287 (Ground fault monitoring shutdown threshold)
230022
<location>Power unit: Monitoring U_ce
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
Fault cause: %1 bin
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
In the power unit, the monitoring of the collector-emitter voltage (U_ce) of the semiconductor has responded.
Possible causes:
- fiber-optic cable interrupted.
- power supply of the IGBT gating module missing.
- short-circuit at the power unit output.
- defective semiconductor in the power unit.
Fault value (r0949, interpret binary):
Bit 0: Short-circuit in phase U
Bit 1: Short circuit in phase V
Bit 2: Short-circuit in phase W
Bit 3: Light transmitter enable defective
Bit 4: U_ce group fault signal interrupted
See also: r0949 (Fault value)
Remedy:
- check the fiber-optic cable and if required, replace.
- check the power supply of the IGBT gating module (24 V).
- check the power cable connections.
- select the defective semiconductor and replace.
Alarms
1140
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
230024
<location>Power unit: Overtemperature thermal model
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC
Message value:
-
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The temperature difference between the heat sink and chip has exceeded the permissible limit value.
- the permissible load duty cycle was not maintained.
- insufficient cooling, fan failure.
- overload.
- ambient temperature too high.
- pulse frequency too high.
See also: r0037
Remedy:
- adapt the load duty cycle.
- check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
- check the motor load.
- reduce the pulse frequency if this is higher than the rated pulse frequency.
230024
<location>Power unit: Overtemperature thermal model
Drive object:
VECTOR, VECTOR_AC
Message value:
-
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The temperature difference between the heat sink and chip has exceeded the permissible limit value.
- the permissible load duty cycle was not maintained.
- insufficient cooling, fan failure.
- overload.
- ambient temperature too high.
- pulse frequency too high.
See also: r0037
Remedy:
- adapt the load duty cycle.
- check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
- check the motor load.
- reduce the pulse frequency if this is higher than the rated pulse frequency.
- if DC braking is active: reduce braking current (p1232).
230025
<location>Power unit: Chip overtemperature
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1141
SINAMICS alarms
Cause:
The chip temperature of the semiconductor has exceeded the permissible limit value.
- the permissible load duty cycle was not maintained.
- insufficient cooling, fan failure.
- overload.
- ambient temperature too high.
- pulse frequency too high.
Fault value (r0949, interpret decimal):
Temperature difference between the heat sink and chip [0.01 °C].
Remedy:
- adapt the load duty cycle.
- check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
- check the motor load.
- reduce the pulse frequency if this is higher than the rated pulse frequency.
Notice:
This fault can only be acknowledged after the alarm threshold for alarm A05001 has been undershot.
See also: r0037
230027
<location>Power unit: Precharging DC link time monitoring
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
Enable signals: %1, Status: %2
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Alarms
1142
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
The power unit DC link was not able to be precharged within the expected time.
1) There is no line supply voltage connected.
2) The line contactor/line side switch has not been closed.
3) The line supply voltage is too low.
4) Line supply voltage incorrectly set (p0210).
5) The precharging resistors are overheated as there were too many precharging operations per time unit.
6) The precharging resistors are overheated as the DC link capacitance is too high.
7) The precharging resistors are overheated because when there is no "ready for operation" (r0863.0) of the infeed unit,
power is taken from the DC link.
8) The precharging resistors are overheated as the line contactor was closed during the DC link fast discharge through the
Braking Module.
9) The DC link has either a ground fault or a short-circuit.
10) The precharging circuit is possibly defective (only for chassis units).
11) Infeed is defective and/or fuse has ruptured in the Motor Module (only Booksize units).
Fault value (r0949, interpret binary):
yyyyxxxx hex:
yyyy = power unit state
0: Fault status (wait for OFF and fault acknowledgment).
1: Restart inhibit (wait for OFF).
2: Overvoltage condition detected -> change into the fault state.
3: Undervoltage condition detected -> change into the fault state.
4: Wait for bridging contactor to open -> change into the fault state.
5: Wait for bridging contactor to open -> change into restart inhibit.
6: Wait for bypass contactor to open
7: Commissioning.
8: Ready for precharging.
9: Precharging started, DC link voltage lower than the minimum switch-on voltage
10: Precharging, DC link voltage end of precharging still not detected
11: Wait for the end of the de-bounce time of the main contactor after precharging has been completed.
12: Precharging completed, ready for pulse enable.
13: It was detected that the STO terminal was energized at the power unit
xxxx = Missing internal enable signals, power unit (inverted bit-coded, FFFF hex -> all internal enable signals available)
Bit 0: Power supply of the IGBT gating shut down.
Bit 1: Ground fault detected.
Bit 2: Peak current intervention.
Bit 3: I2t exceeded.
Bit 4. Thermal model overtemperature calculated.
Bit 5: (heat sink, gating module, power unit) overtemperature measured.
Bit 6: Reserved.
Bit 7: Overvoltage detected.
Bit 8: Power unit has completed precharging, ready for pulse enable.
Bit 9: STO terminal missing.
Bit 10: Overcurrent detected.
Bit 11: Armature short-circuit active.
Bit 12: DRIVE-CLiQ fault active.
Bit 13: Vce fault detected, transistor de-saturated due to overcurrent/short-circuit.
Bit 14: Undervoltage detected.
See also: p0210
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1143
SINAMICS alarms
Remedy:
In general:
- check the line supply voltage at the input terminals.
- check the line supply voltage setting (p0210).
For booksize drive units, the following applies:
- wait (approx. 8 minutes) until the precharging resistors have cooled down. For this purpose, preferably disconnect the
infeed unit from the line supply.
For 5):
- carefully observe the permissible precharging frequency (refer to the appropriate Manual).
For 6):
- check the total capacitance of the DC link and reduce in accordance with the maximum permissible DC link capacitance if
necessary (refer to the appropriate Manual).
For 7):
- interconnect the ready-for-operation signal from the infeed unit (r0863.0) in the enable logic of the drives connected to
this DC link
For 8):
- check the connections of the external line contactor. The line contactor must be open during DC link fast discharge.
For 9):
- check the DC link for ground faults or short circuits.
For 11):
- check the DC link voltage of the infeed (r0070) and Motor Modules (r0070).
If the DC link voltage generated by the infeed (or external) is not displayed for the Motor Modules (r0070), then a fuse has
ruptured in the Motor Module.
See also: p0210
230030
<location>Power unit: Internal overtemperature alarm
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature inside the drive converter has exceeded the permissible temperature limit.
- insufficient cooling, fan failure.
- overload.
- ambient temperature too high.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- possibly use an additional fan.
- check whether the ambient temperature is in the permissible range.
Notice:
This alarm is automatically withdrawn once the permissible temperature limit value has been fallen below minus 5 K.
230031
<location>Power unit: Hardware current limiting in phase U
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Alarms
1144
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
Hardware current limit for phase U responded. The pulsing in this phase is inhibited for one pulse period.
- closed-loop control is incorrectly parameterized.
- fault in the motor or in the power cables.
- the power cables exceed the maximum permissible length.
- motor load too high
- power unit defective.
Note:
Alarm A30031 is always output if, for a Power Module, the hardware current limiting of phase U, V or W responds.
Remedy:
- check the motor data and if required, recalculate the control parameters (p0340 = 3). As an alternative, run a motor data
identification (p1910 = 1, p1960 = 1).
- check the motor circuit configuration (star/delta).
- check the motor load.
- check the power cable connections.
- check the power cables for short-circuit or ground fault.
- check the length of the power cables.
230032
<location>Power unit: Hardware current limiting in phase V
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
Hardware current limit for phase V responded. The pulsing in this phase is inhibited for one pulse period.
- closed-loop control is incorrectly parameterized.
- fault in the motor or in the power cables.
- the power cables exceed the maximum permissible length.
- motor load too high
- power unit defective.
Note:
Alarm A30031 is always output if, for a Power Module, the hardware current limiting of phase U, V or W responds.
Remedy:
Check the motor data and if required, recalculate the control parameters (p0340 = 3). As an alternative, run a motor data
identification (p1910 = 1, p1960 = 1).
- check the motor circuit configuration (star/delta).
- check the motor load.
- check the power cable connections.
- check the power cables for short-circuit or ground fault.
- check the length of the power cables.
230033
<location>Power unit: Hardware current limiting in phase W
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
Hardware current limit for phase W responded. The pulsing in this phase is inhibited for one pulse period.
- closed-loop control is incorrectly parameterized.
- fault in the motor or in the power cables.
- the power cables exceed the maximum permissible length.
- motor load too high
- power unit defective.
Note:
Alarm A30031 is always output if, for a Power Module, the hardware current limiting of phase U, V or W responds.
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1145
SINAMICS alarms
Remedy:
- check the motor data and if required, recalculate the control parameters (p0340 = 3). As an alternative, run a motor data
identification (p1910 = 1, p1960 = 1).
- check the motor circuit configuration (star/delta).
- check the motor load.
- check the power cable connections.
- check the power cables for short-circuit or ground fault.
- check the length of the power cables.
230034
<location>Power unit: Internal overtemperature
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR,
VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The alarm threshold for internal overtemperature has been reached.
If the temperature inside the power unit increases up to the fault threshold, then fault F30036 is triggered.
- ambient temperature might be too high.
- insufficient cooling, fan failure.
Alarm value (r2124, interpret binary):
Bit 0 = 1: Overtemperature in the control electronics area.
Bit 1 = 1: Overtemperature in the power electronics area.
Bit 2 = 1: Overtemperature in the processor area.
Bit 3 = 1: Overtemperature in the processor area.
Bit 4 = 1: Overtemperature when the internal fan is defective.
Bit 5 = 1: Intake air overtemperature.
Remedy:
- check the ambient temperature.
- check the fan for the inside of the unit.
230035
<location>Power unit: Air intake overtemperature
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
The air intake in the power unit has exceeded the permissible temperature limit.
For air-cooled power units, the temperature limit is at 55 °C.
- ambient temperature too high.
- insufficient cooling, fan failure.
Fault value (r0949, interpret decimal):
Temperature [0.01 °C].
Remedy:
- check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
Notice:
This fault can only be acknowledged after the alarm threshold for alarm A05002 has been undershot.
230036
<location>Power unit: Internal overtemperature
Drive object:
All objects
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Alarms
1146
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
The temperature inside the converter has exceeded the permissible limit value.
- insufficient cooling, fan failure.
- overload.
- ambient temperature too high.
Fault value (r0949, interpret binary):
Bit 0 = 1: Overtemperature in the control electronics area.
Bit 1 = 1: Overtemperature in the power electronics area.
Bit 2 = 1: Overtemperature in the processor area.
Bit 3 = 1: Overtemperature in the processor area.
Bit 4 = 1: Overtemperature when the internal fan is defective.
Bit 5 = 1: Intake air overtemperature.
Remedy:
- check the internal fan.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
Notice:
This fault can only be acknowledged once the permissible temperature limit minus 5 K has been fallen below.
230037
<location>Power unit: Rectifier overtemperature
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The temperature in the rectifier of the power unit has exceeded the permissible temperature limit.
- insufficient cooling, fan failure.
- overload.
- ambient temperature too high.
- line supply phase failure.
Fault value (r0949, interpret decimal):
Temperature [0.01 °C].
Remedy:
- check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
- check the motor load.
- check the line supply phases.
Notice:
This fault can only be acknowledged after the alarm threshold for alarm A05004 has been undershot.
230038
<location>Power unit: Capacitor fan monitoring
Drive object:
B_INF, B_INF_840
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The capacitor fan signals a fault.
Remedy:
Replace the capacitor fan in the power unit.
230039
<location>Power unit: Failure capacitor fan
Drive object:
B_INF, B_INF_840
Message value:
%1
Reaction:
OFF1
Acknowledge:
IMMEDIATELY
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1147
SINAMICS alarms
Cause:
The capacitor fan has failed.
Remedy:
Replace the capacitor fan in the power unit.
230040
<location>Power unit: Undervolt 24 V
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The undervoltage threshold of the 24 V power supply for the power unit was fallen below for longer than 3 ms.
Note:
- for booksize power units, the undervoltage threshold is 15 V.
- for all other power units, the undervoltage threshold depends on the power unit, and is not displayed.
Fault value (r0949, interpret decimal):
24 V voltage [0.1 V].
Remedy:
- check the power supply of the power unit.
- carry out a POWER ON (switch-off/switch-on) for the component.
230040
<location>Power unit: Undervolt 24/48 V
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
Channel: %1, voltage: %2 [0.1 V]
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The undervoltage threshold of the 24 V power supply for the power unit was fallen below for longer than 3 ms.
Note:
- for booksize power units, the undervoltage threshold is 15 V.
- for CU310-2, CUA31 and CUA32 the undervoltage threshold is 16 V.
- for all other power units (e.g. S120M), the undervoltage threshold depends on the power unit, and is not displayed.
Fault value (r0949, interpret hexadecimal):
yyxxxx hex: yy = channel, xxxx = voltage [0.1 V]
yy = 0: 24 V power supply
yy = 1: 48 V power supply
Remedy:
- check the power supply of the power unit.
- carry out a POWER ON (switch-off/switch-on) for the component.
230040
<location>Power unit: Undervolt 24 V
Drive object:
VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The undervoltage threshold of the 24 V power supply for the power unit was fallen below for longer than 3 ms.
Note:
- for booksize power units, the undervoltage threshold is 15 V.
- for CU310-2, CUA31 and CUA32 the undervoltage threshold is 16 V.
- for all other power units, the undervoltage threshold depends on the power unit, and is not displayed.
Fault value (r0949, interpret decimal):
24 V voltage [0.1 V].
Remedy:
- check the power supply of the power unit.
- carry out a POWER ON (switch-off/switch-on) for the component.
Alarms
1148
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
230041
<location>Power unit: Undervoltage 24 V alarm
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
For the power unit power supply, the lower threshold has been violated.
Alarm value (r2124, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- check the power supply of the power unit.
- carry out a POWER ON (switch-off/switch-on) for the component.
230041
<location>Power unit: Undervolt 24/48 V alarm
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
Channel: %1, voltage: %2 [0.1 V]
Reaction:
NONE
Acknowledge:
NONE
Cause:
For the power unit power supply, the lower threshold has been violated.
Alarm value (r2124, interpret hexadecimal):
yyxxxx hex: yy = channel, xxxx = voltage [0.1 V]
yy = 0: 24 V power supply
yy = 1: 48 V power supply
Remedy:
- check the power supply of the power unit.
- carry out a POWER ON (switch-off/switch-on) for the component.
230041
<location>Power unit: Undervoltage 24 V alarm
Drive object:
VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
For the power unit power supply, the lower threshold has been violated.
Alarm value (r2124, interpret decimal):
24 V voltage [0.1 V].
Remedy:
- check the power supply of the power unit.
- carry out a POWER ON (switch-off/switch-on) for the component.
230042
<location>Power unit: Fan has reached the maximum operating hours
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1149
SINAMICS alarms
Cause:
The maximum operating time of at least one fan will soon be reached, or has already been exceeded.
Alarm value (r2124, interpret binary):
Bit 0 = 1:
The operating hours counter of the heat sink fan will reach the maximum operating time in 500 hours. After 500 hours has
elapsed, bit 0 is cleared and bit 2 is set in the alarm value.
Bit 1 = 1:
The wear counter of the heat sink fan has reached 99 %. The remaining service life is 1%. After this 1% has elapsed, bit 1
is cleared and bit 2 is set in the alarm value.
Bit 2 = 1:
The operating hours counter of the heat sink fan has exceeded the maximum operating time - and/or the wear counter has
exceeded 100%.
Bit 8 = 1:
The operating hours counter of the fan inside the device will reach the maximum operating time in 500 hours. After 500
hours has elapsed, bit 8 is cleared and bit 10 is set in the alarm value.
Bit 10 = 1:
The operating hours counter of the fan inside the device has exceeded the maximum operating time.
Remedy:
For the fan involved, carry out the following:
- replace the fan.
- reset the operating hours counter (p0251, p0254).
See also: p0251, p0252, p0254, r0277
230043
<location>Power unit: Overvolt 24 V
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
For the power unit power supply, the upper threshold has been violated.
Fault value (r0949, interpret decimal):
24 V voltage [0.1 V].
Remedy:
Check the power supply of the power unit.
230043
<location>Power unit: Overvolt 24/48 V
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
Channel: %1, voltage: %2 [0.1 V]
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
For the power unit power supply, the upper threshold has been violated.
Fault value (r0949, interpret hexadecimal):
yyxxxx hex: yy = channel, xxxx = voltage [0.1 V]
yy = 0: 24 V power supply
yy = 1: 48 V power supply
Remedy:
Check the power supply of the power unit.
230044
<location>Power unit: Overvoltage 24 V alarm
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
For the power unit power supply, the upper threshold has been violated.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
Alarms
1150
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Remedy:
Check the power supply of the power unit.
230044
<location>Power unit: Overvolt 24/48 V alarm
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
Channel: %1, voltage: %2 [0.1 V]
Reaction:
NONE
Acknowledge:
NONE
Cause:
For the power unit power supply, the upper threshold has been violated.
Alarm value (r2124, interpret hexadecimal):
yyxxxx hex: yy = channel, xxxx = voltage [0.1 V]
yy = 0: 24 V power supply
yy = 1: 48 V power supply
Remedy:
Check the power supply of the power unit.
230044
<location>Power unit: Overvoltage 24 V alarm
Drive object:
VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
For the power unit power supply, the upper threshold has been violated.
Alarm value (r2124, interpret decimal):
24 V voltage [0.1 V].
Remedy:
Check the power supply of the power unit.
230045
<location>Power unit: Supply undervoltage
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
Power supply fault in the power unit.
- the voltage monitor signals an undervoltage fault on the module.
The following applies for CU31x:
- the voltage monitoring on the DAC board signals an undervoltage fault on the module.
Remedy:
- check the power supply of the power unit.
- carry out a POWER ON (switch-off/switch-on) for the component.
- replace the module if necessary.
230045
<location>Power unit: Supply undervoltage
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
Power supply fault in the power unit.
- the voltage monitor signals an undervoltage fault on the module.
The following applies for CU31x:
- the voltage monitoring on the DAC board signals an undervoltage fault on the module.
For S120M, the following applies:
- this message is displayed for undervoltage or overvoltage.
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1151
SINAMICS alarms
Remedy:
- check the power supply of the power unit.
- carry out a POWER ON (switch-off/switch-on) for the component.
- replace the module if necessary.
230046
<location>Power unit: Undervoltage alarm
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
Before the last restart, a problem occurred at the power unit power supply.
The voltage monitor in the internal FPGA of the PSA signals an undervoltage fault on the module.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- check the 24 V DC voltage supply to power unit.
- carry out a POWER ON (switch-off/switch-on) for the component.
- replace the module if necessary.
230046
<location>Power unit: Undervoltage alarm
Drive object:
SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
Before the last restart, a problem occurred at the power unit power supply.
The voltage monitor in the internal FPGA of the PSA signals an undervoltage fault on the module.
Alarm value (r2124, interpret decimal):
Register value of the voltage fault register.
Remedy:
- check the 24 V DC voltage supply to power unit.
- carry out a POWER ON (switch-off/switch-on) for the component.
- replace the module if necessary.
230047
<location>Cooling unit: Cooling medium flow rate too low
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The flow rate of the cooling unit has fallen below the fault threshold.
Remedy:
- check the feedback signals and parameter assignment (p0260 ... p0267).
- check the coolant feed.
- check the thermal conductivity of the coolant.
- check the coolant concentration.
230048
<location>Power unit: fan defective
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
Fault cause: %1 bin
Reaction:
NONE
Acknowledge:
NONE
Alarms
1152
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
The feedback signal from a fan indicates a fault.
- fan defective.
- fan blocked.
- feedback signal inaccurate.
- fan power supply interrupted (only for r0193.13 = 1 and heat sink fan)
Alarm value (r2124, interpret binary):
Bit 0 = 1: heat sink fan
Bit 1 = 1: fan inside the device
Note:
- for firmware version < 5.1 of the power unit, the alarm value is always 0. The alarm then refers to the heat sink fan.
- for r0193.13 = 1, fault F30058 is output instead of this alarm for heat sink fans, if the pulses are inhibited or the fault occurs
within 10 s after the fan runs up when the pulses are enabled.
- for r0193.13 = 1, fault F30059 is output instead of this alarm for fans inside the unit, if the air intake temperature
(r0037[3]) has exceeded a specific threshold.
Remedy:
- check the fan involved.
- if required, replace the fan.
- check the fan power supply and if required switch on (only for r0193.13 = 1 and heat sink fan).
Note:
If the alarm has been withdrawn, this does not necessarily mean that the cause of the fault has been resolved. It is also
possible that the software switched off the fan, and therefore can no longer evaluate the feedback signal.
230049
<location>Power unit: Internal fan faulty
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The internal fan has failed.
Remedy:
Check the internal fan and replace if necessary.
230050
<location>Power unit: 24 V supply overvoltage
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR,
VECTOR_AC
Message value:
-
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
The voltage monitor signals an overvoltage fault on the module.
Remedy:
- check the 24 V power supply.
- replace the module if necessary.
230051
<location>Power unit: Motor holding brake short circuit detected
Drive object:
SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A short-circuit at the motor holding brake terminals has been detected.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- check the motor holding brake for a short-circuit.
- check the connection and cable for the motor holding brake.
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1153
SINAMICS alarms
230052
<location>EEPROM data error
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
EEPROM data error of the power unit module.
Fault value (r0949, interpret decimal):
0, 2, 3, 4:
The EEPROM data read in from the power unit module are incorrect.
1:
EEPROM data is not compatible to the firmware of the power unit application.
Additional values:
Only for internal Siemens troubleshooting.
Remedy:
For fault value = 0, 2, 3, 4:
Replace the power unit module or update the EEPROM data.
For fault value = 1:
The following applies for CU31x and CUA31:
Update the firmware \SIEMENS\SINAMICS\CODE\SAC\cu31xi.ufw (cua31.ufw)
230053
<location>FPGA data faulty
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
POWER ON
Cause:
The FPGA data of the power unit are faulty. This can be caused, for example, if a firmware update is interrupted.
Remedy:
Replace the power unit or update of the FPGA data by updating the firmware.
Note:
If this fault occurs after a firmware update, then update the firmware again.
230054
<location>Power unit: Undervoltage when opening the brake
Drive object:
HLA, HLA_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
When the brake is being opened, it is detected that the power supply voltage is less than 21.4 V
Alarm value (r2124, interpret decimal):
Supply voltage fault [0.1 V].
Example:
Alarm value = 195 --> voltage = 19.5 V
Remedy:
Check the 24 V voltage for stability and value.
230055
<location>Power unit: Braking chopper overcurrent
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
An overcurrent condition has occurred in the braking chopper.
Alarms
1154
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Remedy:
- check whether the braking resistor has a short circuit.
- for an external braking resistor, check whether the resistor may have been dimensioned too small.
Note:
The braking chopper is only enabled again at pulse enable after the fault has been acknowledged.
230057
<location>Power unit: Line asymmetry
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
Frequencies have been detected on the DC link voltage that would suggest line asymmetry or failure of a line phase.
It is also possible that a motor phase has failed.
Fault F30011 is output if the alarm is present and at the latest after 5 minutes.
The precise duration depends on the power unit type and the particular frequencies. For booksize and chassis power units,
the duration also depends on how long the alarm has been active.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- check the line phase connection.
- check the motor feeder cable connections.
If there is no phase failure of the line or motor, then line asymmetry is involved.
- reduce the power in order to avoid fault F30011.
230058
<location>Power unit: heat sink fan defective
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY
Cause:
The feedback signal from the heat sink fan signals a fault.
- fan defective.
- fan blocked.
- feedback signal inaccurate.
- fan power supply interrupted (only for r0193.13 = 1)
Remedy:
- check the heat sink fan and replace if necessary.
- check the fan power supply and if required switch on (only for r0193.13 = 1)
- if, for an S120 Combi, a separately driven fan with feedback signal is used, then check its wiring (X12.2 or X13.2).
Note:
- if a separately driven fan without feedback signal is used for an S120 Combi, instead of the feedback signal of the fan, a
connection to ground must be established (X12.1/2 or X13.1/2).
- if the fault can be acknowledged, this does not necessarily mean that the cause of the fault has been resolved. It is also
possible that the software switched off the fan, and therefore can no longer evaluate the feedback signal.
230059
<location>Power unit: Internal fan faulty
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The internal power unit fan has failed and is possibly defective.
Remedy:
Check the internal fan and replace if necessary.
Note:
If the fault can be acknowledged, this does not necessarily mean that the cause of the fault has been resolved. It is also
possible that the software switched off the fan, and therefore can no longer evaluate the feedback signal.
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1155
SINAMICS alarms
230060
<location>Precharge contactor state monitoring
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
Fault cause: %1 bin
Reaction:
OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
A feedback signal for the precharging contactor (ALM, SLM, BLM diode) or the line contactor (BLM thyristor) interconnected
and the monitoring activated.
After switching-in/switching-out the contactor, a correct feedback signal was not received within the monitoring time set
in p0255[0, 2].
Fault value (r0949, interpret binary):
Bit 0: The time set in p0255[0, 2] was exceeded when switching-in/switching-out the contactor.
Bit 1: The precharging contactor was opened while precharging or in the infeed mode (BLM thyristor).
Bit 2: The precharging contactor was switched-in in the OFF state or during infeed operation.
Remedy:
- check the monitoring time setting (p0255[0, 2]).
- check the contactor wiring and activation.
- replace the contactor.
See also: p0255 (Power unit contactor monitoring time)
230061
<location>Bridging contactor monitoring
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
Fault cause: %1 bin
Reaction:
OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
A feedback signal for the bypass contactor is interconnected and the monitoring activated.
After switching-in/switching-out the contactor, a correct feedback signal was not received within the monitoring time set
in p0255[1, 3].
Fault value (r0949, interpret binary):
Bit 0: The time set in p0255[1, 3] was exceeded when switching-in/switching-out the contactor.
Bit 1: The bypass contactor was opened in operation.
Bit 2: The bypass contactor was switched-in in the OFF state or during precharging.
Remedy:
- check the monitoring time setting (p0255[1, 3]).
- check the contactor wiring and activation.
- replace the contactor.
See also: p0255 (Power unit contactor monitoring time)
230065
<location>Voltage measured values not plausible
Drive object:
VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The voltage measurement is not supplying any plausible values
Alarm value (r2124, interpret bitwise binary):
Bit 1: Phase U.
Bit 2: Phase V.
Bit 3: Phase W.
Remedy:
- Deactivate voltage measurement (p0247.0 = 0).
- Deactivate flying restart with voltage measurement (p0247.5 = 0) and deactivate fast flying restart (p1780.11 = 0).
230066
<location>Power unit: overtemperature, alarm capacitor air discharge
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Alarms
1156
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The air discharged from the DC link capacitor has exceeded the alarm threshold.
- ambient temperature too high.
- insufficient cooling, fan failure.
Alarm value (r2124, interpret decimal):
Temperature when reaching the alarm threshold [0.01 °C].
Note:
If operation is unchanged, then the permissible limit value can be exceeded. In this case, fault F30067 is output and the
pulses inhibited.
Remedy:
- check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
Note:
This alarm is only withdrawn after the alarm threshold has been fallen below - and the corresponding hysteresis.
230067
<location>Power unit: overtemperature, fault capacitor air discharge
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The air discharged from the DC link capacitor has exceeded the permissible limit.
- ambient temperature too high.
- insufficient cooling, fan failure.
Fault value (r0949, interpret decimal):
Temperature when reaching the limit value [0.01 °C].
Remedy:
- check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
Note:
This fault can only be acknowledged after the limit value has been fallen below, and the corresponding hysteresis (5 K).
230068
<location>Power unit: undertemperature inverter heat sink
Drive object:
SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The actual inverter heat sink temperature is below the permissible minimum value.
Possible causes:
- the power unit is being operated at an ambient temperature that lies below the permissible range.
- the temperature sensor evaluation is defective.
Fault value (r0949, interpret decimal):
Inverter heat sink temperature [0.1 °C].
Remedy:
- ensure that higher ambient temperatures prevail.
- replace the power unit.
230070
<location>Cycle requested by the power unit module not supported
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1157
SINAMICS alarms
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A cycle is requested that is not supported by the power unit.
Fault value (r0949, interpret hexadecimal):
0: The current control cycle is not supported.
1: The DRIVE-CLiQ cycle is not supported.
2: Internal timing problem (clearance between RX and TX instants too low).
3: Internal timing problem (TX instant too early).
Remedy:
The power unit only supports the following cycles:
62.5 µs, 125 µs, 250 µs and 500 µs
For fault value = 0:
Set a permitted current control cycle.
For fault value = 1:
Set a permitted DRIVE-CLiQ cycle.
For fault value = 2, 3:
Contact the manufacturer (you may have an incompatible firmware version).
230071
<location>No new actual values received from the power unit
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The number of actual value telegrams from the power unit module that have failed has exceeded the permissible number.
Remedy:
Check the interface (adjustment and locking) to the power unit module.
230072
<location>Setpoints can no longer be transferred to the power unit
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The following applies for CU31x and CUA31:
More than one setpoint telegram was not able to be transferred to the power unit module.
Remedy:
The following applies for CU31x and CUA31:
Check the interface (adjustment and locking) to the power unit module.
230073
<location>Actual value/setpoint preprocessing no longer synchronous
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
Communication with the power unit module is no longer in synchronism with the current control cycle.
Remedy:
Wait until synchronization is re-established.
230074
<location>Communication error between the Control Unit and Power Module
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, HLA, HLA_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR,
VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Alarms
1158
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
Communications between the Control Unit (CU) and Power Module (PM) via the interface no longer possible. The CU may
have been withdrawn or is incorrectly inserted.
Fault value (r0949, interpret hexadecimal):
0 hex:
- a Control Unit with external 24 V supply was withdrawn from the Power Module during operation.
- with the Power Module switched off, the external 24 V supply for the Control Unit was interrupted for some time.
1 hex:
The Control Unit was withdrawn from the Power Module during operation, although the encoderless safe motion
monitoring functions are enabled. This is not supported. After re-inserting the Control Unit in operation, communications
to the Power Module no longer possible.
20A hex:
The Control Unit was inserted on a Power Module, which has another code number.
20B hex:
The Control Unit was inserted on a Power Module, which although it has the same code number, has a different serial
number.
601 hex:
The Control Unit was inserted on a Power Module, whose power/performance class (chassis unit) is not supported.
Remedy:
Reinsert the Control Unit (CU) or the Control Unit Adapter (CUAxx) onto the original Power Module and continue operation.
If required, carry out a POWER ON for the CU and/or the CUA.
230075
<location>Configuration of the power unit unsuccessful
Drive object:
SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A communication error has occurred while configuring the power unit using the Control Unit. The cause is not clear.
Fault value (r0949, interpret decimal):
0:
The output filter initialization was unsuccessful.
1:
Activation/deactivation of the regenerative feedback functionality was unsuccessful.
2:
Activation/deactivation of the chopper function was unsuccessful.
Remedy:
- acknowledge the fault and continue operation.
- if the fault reoccurs, carry out a POWER ON (switch-off/switch-on).
- if required, replace the power unit.
230076
<location>Power unit: thermal overload internal braking resistor alarm
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The energy absorbed by the internal braking resistor has exceeded the alarm threshold of 80 %. If the power unit is still
operated in the generator mode, then this can reach the shutdown threshold. To avoid overheating of the braking resistor,
use of the braking resistor is inhibited and alarm A30077 is output.
Alarm value (r2124, interpret decimal):
Energy absorbed by the braking resistor [Ws].
Remedy:
Reduce the power when generating.
Note:
For a DC link coupling, the generating power of all of the coupled power units must be taken into consideration.
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1159
SINAMICS alarms
230077
<location>Power unit: thermal overload internal braking resistor
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The internal braking resistor is thermally overloaded. This is the reason that its use was inhibited.
Alarm value (r2124, interpret decimal):
Energy absorbed by the braking resistor [Ws].
Remedy:
Reduce the power when generating.
Note:
- once the internal braking resistor has thermally recovered, it is enabled for further use.
- for a DC link coupling, the generating power of all the coupled power units must be taken into consideration.
230078
<location>Power unit: defective fan or line reactor has overheated
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
-
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The temperature monitoring of the internal braking resistor or the line reactor has responded. In addition to the OFF2
response, the use of the internal braking resistor was inhibited.
Note:
- an overtemperature condition of the internal braking resistor can only be initiated as a result of a defective fan.
- an overtemperature condition of the line reactor can occur when a DC link coupling is used - and if the power when
motoring, which is fed into the DC link - is not evenly distributed across the rectifiers of the power units.
Remedy:
- check the converter fan and replace if necessary.
- reduce the motoring power.
230079
<location>Power unit: referred to the supply voltage, the DC link voltage is too high
Drive object:
SERVO, SERVO_840, SERVO_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The alarm is output if the following conditions are simultaneously satisfied:
1. The device supply voltage (p0210) was reduced.
2. A DC link voltage is present, which is too high when referred to the new supply voltage.
DC link precharging cannot be completed as this could place some converter components at risk.
Alarm value (r2124, interpret decimal):
Voltage value to which the DC link voltage must, in the meantime, be reduced in order to complete precharging [V].
See also: p0210
Remedy:
As a minimum, reduce the DC link voltage to the voltage specified in the alarm value.
Note:
The alarm is automatically withdrawn if the DC link voltage drops below the voltage specified in the alarm value.
Fault F07802 is output if an attempt is made to enable the pulses even though an alarm is active.
230080
<location>Power unit: Current increasing too quickly
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
Fault cause: %1 bin
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Alarms
1160
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
The power unit has detected an excessive rate of rise in the overvoltage range.
- closed-loop control is incorrectly parameterized.
- motor has a short-circuit or fault to ground (frame).
- U/f operation: Up ramp set too low.
- U/f operation: rated current of motor much greater than that of power unit.
- infeed: High discharge and post-charging currents for line voltage dip.
- infeed: High post-charging currents for overload when motoring and DC link voltage dip.
- infeed: Short-circuit currents at switch-on as there is no commutating reactor.
- power cables are not correctly connected.
- power cables exceed the maximum permissible length.
- power unit defective.
Additional causes for a parallel switching device (r0108.15 = 1):
- a power unit has tripped (switched off) due to a ground fault.
- the closed-loop circulating current control is either too slow or has been set too fast.
Fault value (r0949, interpret bitwise binary):
Bit 0: Phase U.
Bit 1: Phase V.
Bit 2: Phase W.
Remedy:
- check the motor data - if required, carry out commissioning.
- check the motor circuit configuration (star-delta)
- U/f operation: Increase up ramp.
- U/f operation: Check assignment of rated currents of motor and power unit.
- infeed: Check the line supply quality.
- infeed: Reduce the motor load.
- infeed: Correct connection of the line reactor.
- check the power cable connections.
- check the power cables for short-circuit or ground fault.
- check the length of the power cables.
- replace power unit.
For a parallel switching device (r0108.15 = 1) the following additionally applies:
- check the ground fault monitoring thresholds (p0287).
- check the setting of the closed-loop circulating current control (p7036, p7037).
230081
<location>Power unit: Switching operations too frequent
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
Fault cause: %1 bin
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1161
SINAMICS alarms
Cause:
The power unit has executed too many switching operations for current limitation.
- closed-loop control is incorrectly parameterized.
- motor has a short-circuit or fault to ground (frame).
- U/f operation: Up ramp set too low.
- U/f operation: rated current of motor much greater than that of power unit.
- infeed: High discharge and post-charging currents for line voltage dip.
- infeed: High post-charging currents for overload when motoring and DC link voltage dip.
- infeed: Short-circuit currents at switch-on as there is no commutating reactor.
- power cables are not correctly connected.
- power cables exceed the maximum permissible length.
- power unit defective.
Additional causes for a parallel switching device (r0108.15 = 1):
- a power unit has tripped (switched off) due to a ground fault.
- the closed-loop circulating current control is either too slow or has been set too fast.
Fault value (r0949, interpret bitwise binary):
Bit 0: Phase U.
Bit 1: Phase V.
Bit 2: Phase W.
Remedy:
- check the motor data - if required, carry out commissioning.
- check the motor circuit configuration (star-delta)
- U/f operation: Increase up ramp.
- U/f operation: Check assignment of rated currents of motor and power unit.
- infeed: Check the line supply quality.
- infeed: Reduce the motor load.
- infeed: Correct connection of the line reactor.
- check the power cable connections.
- check the power cables for short-circuit or ground fault.
- check the length of the power cables.
- replace power unit.
For a parallel switching device (r0108.15 = 1) the following additionally applies:
- check the ground fault monitoring thresholds (p0287).
- check the setting of the closed-loop circulating current control (p7036, p7037).
230082
<location>Power unit: cooling medium flow rate too low alarm threshold
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The flow rate is too low, and has fallen below the specified alarm threshold. If the flow rate is still too low after the specified
time has expired, then fault F30083 is output.
Remedy:
- check the coolant flow rate.
- check the thermal conductivity of the coolant.
- check the coolant concentration.
230083
<location>Power unit: cooling medium flow rate too low fault threshold
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The flow rate is too low, and has fallen below the specified fault threshold.
Alarms
1162
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Remedy:
- check the coolant flow rate.
- check the thermal conductivity of the coolant.
- check the coolant concentration.
230086
<location>Power unit: coolant temperature has exceeded the alarm threshold
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The coolant temperature has exceeded the specified alarm threshold.
If the coolant temperature increases up to the specified fault threshold, then fault F30087 is output.
Alarm value (r2124, interpret decimal):
Coolant temperature.
Remedy:
Check the cooling system and the ambient conditions.
230087
<location>Power unit: coolant temperature has exceeded the fault threshold
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The coolant temperature has exceeded the specified fault threshold.
Fault value (r0949, interpret decimal):
Coolant temperature.
Remedy:
Check the cooling system and the ambient conditions.
230105
<location>PU: Actual value sensing fault
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, R_INF, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
At least one incorrect actual value channel was detected on the Power Stack Adapter (PSA).
The incorrect actual value channels are displayed in the following diagnostic parameters.
Remedy:
Evaluate the diagnostic parameters.
If the actual value channel is incorrect, check the components and if required, replace.
230314
<location>Power unit: 24 V power supply overloaded by PM
Drive object:
SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The 24 V power supply through the Power Module (PM) is overloaded.
An external 24 V power supply via X124 on the Control Unit is not connected.
Remedy:
Connect an external 24 V power supply via X124 at the Control Unit.
230315
<location>Power unit: 24 V power supply overloaded by PM
Drive object:
SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1163
SINAMICS alarms
Cause:
The 24 V power supply through the Power Module (PM) is overloaded.
An external 24 V power supply via X124 on the Control Unit is not connected.
Remedy:
Connect an external 24 V power supply via X124 at the Control Unit.
230502
<location>Power unit: DC link overvoltage
Drive object:
SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The power unit has detected overvoltage in the DC link on a pulse inhibit.
- device supply voltage too high.
- line reactor incorrectly dimensioned.
Alarm value (r0949, interpret decimal):
DC link voltage [1 bit = 100 mV].
See also: r0070
Remedy:
- check the device supply voltage (p0210).
- check the dimensioning of the line reactor.
See also: p0210
230600
<location>SI P2: STOP A initiated
Drive object:
HLA, HLA_840
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive-integrated "Safety Integrated" function in monitoring channel 2 has detected a fault and initiated a STOP A (STO
via the safety switch-off signal path of monitoring channel 2).
- forced checking procedure (test stop) of the safety switch-off signal path of monitoring channel 2 unsuccessful.
- subsequent response to fault F30611 (defect in a monitoring channel).
Fault value (r0949, interpret decimal):
0: stop request from the Control Unit.
1005: STO active although STO not selected and there is no internal STOP A present.
1010: STO inactive although STO is selected or an internal STOP A is present.
9999: Subsequent response to fault F30611.
Remedy:
- select Safe Torque Off and deselect again.
- carry out a POWER ON (switch-off/switch-on) for all components.
- replace Hydraulic Module involved.
For fault value = 9999:
- carry out diagnostics for fault F30611.
Note:
CU: Control Unit
SI: Safety Integrated
STO: Safe Torque Off / SH: Safe standstill
230600
<location>SI P2: STOP A initiated
Drive object:
SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Alarms
1164
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
The drive-integrated "Safety Integrated" function in monitoring channel 2 has detected a fault and initiated a STOP A (STO
via the safety switch-off signal path of monitoring channel 2).
- forced checking procedure (test stop) of the safety switch-off signal path of monitoring channel 2 unsuccessful.
- subsequent response to fault F30611 (defect in a monitoring channel).
Fault value (r0949, interpret decimal):
0: Stop request from the Control Unit.
1005:
- STO active, although STO not selected and there is no internal STOP A active.
- For a Power Module with "STO via terminals at the Power Module" (STO_A/STO_B), these terminals are active (DIP switch
to "ON"). However, the "STO via terminals at the Power Module" function has not been enabled (p9601.7 = p9801.7 = 0).
1010: STO inactive although STO is selected or an internal STOP A is present.
1011: internal error for STO deselected in monitoring channel 2.
1020: Internal software error in the "Internal voltage protection" function. The "internal voltage protection" function is
withdrawn. A STOP A that cannot be acknowledged is initiated.
9999: Subsequent response to fault F30611.
Remedy:
- select Safe Torque Off and deselect again.
- carry out a POWER ON (switch-off/switch-on) for all components.
- replace the Motor Module involved.
For fault value = 1005:
- deactivate terminals STO_A/STO_B on the Power Module (set both DIP-switches to "OFF") or enable the "STO via terminals
at the Power Module" function.
For fault value = 9999:
- carry out diagnostics for fault F30611.
Note:
CU: Control Unit
MM: Motor Module
SI: Safety Integrated
STO: Safe Torque Off / SH: Safe standstill
230611
<location>SI P2: Defect in a monitoring channel
Drive object:
HLA, HLA_840
Message value:
%1
Reaction:
NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY (POWER ON)
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1165
SINAMICS alarms
Cause:
The drive-integrated "Safety Integrated" function on processor 2 has detected a fault in the data cross-check between the
two monitoring channels and has initiated a STOP F.
As a result of this fault, after the parameterized transition has expired (p9858), fault F30600 is output (SI MM: STOP A
initiated).
Fault value (r0949, interpret decimal):
0: Stop request from the other monitoring channel.
1 ... 999:
Number of the cross-compared data that resulted in this fault. This number is also displayed in r9895.
1: SI monitoring clock cycle (r9780, r9880).
2: SI enable safety functions (p9601, p9801). Crosswise data comparison is only carried out for the supported bits.
3: SI SGE changeover discrepancy time (p9650, p9850).
4: SI transition period STOP F to STOP A (p9658, p9858).
6: SI Motion enable, safety-relevant functions (p9501, internal value).
7: SI delay time of STO for Safe Stop 1 (p9652, p9852).
8: SI PROFIsafe address (p9610, p9810).
9: SI debounce time for STO/SBC/SS1 (p9651, p9851).
10: SI delay time for initiating STO for ESR (p9697, p9897).
11: SI HLA shutoff valve feedback signal contact configuration (p9626, p9826).
12: SI HLA shutoff valve wait time switch-on (p9625[0], p9825[0]).
13: SI HLA shutoff valve wait time switch-off (p9625[1], p9825[1]).
14: SI PROFIsafe telegram selection (p9611, p9811).
15: SI PROFIsafe bus failure response (p9612, p9812).
1000: Watchdog timer has expired.
Within the time of approx. 5 x p9650, alternatively, the following was defined:
- the signal at terminal STO of the Hydraulic Module continually changed with time intervals less than or equal to the
discrepancy time (p9650/p9850).
- via PROFIsafe/TM54F, STO (also as subsequent response) was continually selected and deselected with time intervals less
than or equal to the discrepancy time (p9650/p9850).
1001, 1002: Initialization error, change timer / check timer.
1950: Module temperature outside the permissible temperature range.
1951: Module temperature not plausible.
2000: Status of the STO selection for both monitoring channels different.
2001: Feedback signal of STO shutdown for both monitoring channels different.
2002: Status of the delay timer SS1 for both monitoring channels different (status of the timer in p9650/p9850).
2003: Status of the STO terminal for both monitoring channels different.
6000 ... 6999:
Error in the PROFIsafe control.
For these fault values, the failsafe control signals (Failsafe Values) are transferred to the safety functions. If "STOP B after
failure of the PROFIsafe communication" (p9812) is parameterized, the transfer of the Failsafe Values is delayed.
The significance of the individual message values is described in safety message C01611.
Alarms
1166
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Remedy:
For fault value = 1 ... 5 and 7 ... 999:
- check the cross data comparison that resulted in a STOP F.
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade the Hydraulic Module software.
- upgrade the Control Unit software.
For fault value = 6:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade the Hydraulic Module software.
- upgrade the Control Unit software.
For fault value = 1000:
- check the wiring of the safety-relevant inputs (SGE) on the Control Unit (contact problems).
- PROFIsafe: Remove contact problems/faults at the PROFIBUS master/PROFINET controller.
- check the wiring of the failsafe inputs at the TM54F (contact problems).
- check the discrepancy time, and if required, increase the value (p9650/p9850).
For fault value = 1001, 1002:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade the Hydraulic Module software.
- upgrade the Control Unit software.
For fault value = 1950:
- operate the module in the permissible range.
- check the module fan, replace the Hydraulic Module involved.
For fault value = 1951:
- operate the module in the permissible range.
- replace Hydraulic Module involved.
For fault value = 2000, 2001, 2002, 2003:
- check the discrepancy time, and if required, increase the value (p9650/p9850, p9652/p9852).
- check the wiring of the safety-relevant inputs (SGE) (contact problems).
- check why STO was selected in r9872. When the SMM functions are active (p9501 = 1), STO can also be selected using these
functions.
- replace Hydraulic Module involved.
Note:
This fault can be acknowledged after removing the cause of the error and after correct selection/deselection of STO.
For fault value = 6000 ... 6999:
Refer to the description of the message values in safety message C01611.
Note:
CU: Control Unit
ESR: Extended Stop and Retract
HM: Hydraulic Module.
SGE: Safety-relevant input
SI: Safety Integrated
SMM: Safe Motion Monitoring
SS1: Safe Stop 1 (corresponds to Stop Category 1 acc. to EN60204)
STO: Safe Torque Off / SH: Safe standstill
230611
<location>SI P2: Defect in a monitoring channel
Drive object:
SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY (POWER ON)
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1167
SINAMICS alarms
Cause:
The drive-integrated "Safety Integrated" function on processor 2 has detected a fault in the data cross-check between the
two monitoring channels and has initiated a STOP F.
As a result of this fault, after the parameterized transition has expired (p9858), fault F30600 is output (SI MM: STOP A
initiated).
Fault value (r0949, interpret decimal):
0: Stop request from another monitoring channel.
1 ... 999:
Number of the cross-compared data that resulted in this fault. This number is also displayed in r9895.
1: SI monitoring clock cycle (r9780, r9880).
2: SI enable safety functions (p9601, p9801). Crosswise data comparison is only carried out for the supported bits.
3: SI SGE changeover discrepancy time (p9650, p9850).
4: SI transition period STOP F to STOP A (p9658, p9858).
5: SI enable Safe Brake Control (p9602, p9802).
6: SI Motion enable, safety-relevant functions (p9501, internal value).
7: SI delay time of STO for Safe Stop 1 (p9652, p9852).
8: SI PROFIsafe address (p9610, p9810).
9: SI debounce time for STO/SBC/SS1 (p9651, p9851).
10: SI delay time for initiating STO for ESR (p9697, p9897).
11: SI Safe Brake Adapter mode, BICO interconnection (p9621, p9821).
12: SI Safe Brake Adapter relay ON time (p9622[0], p9822[0]).
13: SI Safe Brake Adapter relay OFF time (p9622[1], p9822[1]).
14: SI PROFIsafe telegram selection (p9611, p9811).
15: SI PROFIsafe bus failure response (p9612, p9812).
1000: Watchdog timer has expired.
Within the time of approx. 5 x p9650, alternatively, the following was defined:
- the signal at terminal EP of the Motor Module continually changed with time intervals less than or equal to the discrepancy
time (p9650/p9850).
- via PROFIsafe/TM54F, STO (also as subsequent response) was continually selected and deselected with time intervals less
than or equal to the discrepancy time (p9650/p9850).
- safe pulse cancellation (r9723.9 - also as subsequent response) was continually selected and deselected with time intervals
less than or equal to the discrepancy time (p9650/p9850).
1001, 1002: Initialization error, change timer / check timer.
1950: Module temperature outside the permissible temperature range.
1951: Module temperature not plausible.
1952: S120M: hardware access fault.
1953: Module temperature outside the permissible temperature range.
1954: Module temperature not plausible.
2000: Status of the STO selection for both monitoring channels different.
2001: Feedback signal of STO shutdown for both monitoring channels different. This value can also subsequently occur as
a result of other faults.
2002: Status of the delay timer SS1 for both monitoring channels different (status of the timer in p9650/p9850).
2003: Status of the STO terminal for both monitoring channels different.
2004: Forced checking procedure of the switch-off signal path of the second channel unsuccessful.
2005: Forced checking procedure of the switch-off signal path of the second channel unsuccessful.
6000 ... 6999:
Error in the PROFIsafe control.
For these fault values, the failsafe control signals (Failsafe Values) are transferred to the safety functions. If "STOP B after
failure of the PROFIsafe communication" (p9812) is parameterized, the transfer of the Failsafe Values is delayed.
The significance of the individual message values is described in safety message C01611.
Alarms
1168
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Remedy:
For fault value = 1 ... 5 and 7 ... 999:
- check the cross data comparison that resulted in a STOP F.
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade the Motor Module software.
- upgrade the Control Unit software.
For fault value = 6:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade the Motor Module software.
- upgrade the Control Unit software.
For fault value = 1000:
- check the wiring of the safety-relevant inputs (SGE) on the Control Unit (contact problems).
- PROFIsafe: Remove contact problems/faults at the PROFIBUS master/PROFINET controller.
- check the wiring of the failsafe inputs at the TM54F (contact problems).
- check the discrepancy time, and if required, increase the value (p9650/p9850).
For fault value = 1001, 1002:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade the Motor Module software.
- upgrade the Control Unit software.
For fault value = 1950:
- operate the module in the permissible range.
- check the module fan, replace the Motor Module involved.
For fault value = 1951:
- operate the module in the permissible range.
- replace the Motor Module involved.
For fault value = 1952:
- replace the Motor Module involved.
For fault value = 2000, 2001, 2002, 2003:
- check the discrepancy time, and if required, increase the value (p9650/p9850, p9652/p9852).
- check the wiring of the safety-relevant inputs (SGE) (contact problems).
- check why STO was selected in r9872. When the SMM functions are active (p9501 = 1), STO can also be selected using these
functions.
For fault value 2004, 2005:
- replace the Motor Module involved.
- replace the Motor Module involved.
- diagnose the other active faults and resolve the causes.
Note:
This fault can be acknowledged after removing the cause of the error and after correct selection/deselection of STO.
For fault value = 6000 ... 6999:
Refer to the description of the message values in safety message C01611.
Note:
CU: Control Unit
EP: Enable Pulses (pulse enable)
ESR: Extended Stop and Retract
MM: Motor Module
SGE: Safety-relevant input
SI: Safety Integrated
SMM: Safe Motion Monitoring
SS1: Safe Stop 1
STO: Safe Torque Off / SH: Safe standstill
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1169
SINAMICS alarms
230620
<location>SI P2: Safe Torque Off active
Drive object:
HLA, HLA_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The "Safe Torque Off" (STO) function of the basic functions has been selected in monitoring channel 2 using the input
terminal and is active.
Note:
- this message does not result in a safety stop response.
- this message is not output when STO is selected using the Extended Functions.
Remedy:
Not necessary.
Note:
MM: Motor Module
SI: Safety Integrated
STO: Safe Torque Off / SH: Safe standstill
230621
<location>SI P2: Safe Stop 1 active
Drive object:
HLA, HLA_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
The "Safe Stop 1" function (SS1) was selected in monitoring channel 2 and is active.
Note:
This message does not result in a safety stop response.
Remedy:
Not necessary.
Note:
MM: Motor Module
SI: Safety Integrated
SS1: Safe Stop 1
230625
<location>SI P2: Sign-of-life error in safety data
Drive object:
HLA, HLA_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive-integrated "Safety Integrated" function in monitoring channel 2 has detected an error in the sign-of-life of the
safety data between the two monitoring channels and initiated a STOP A.
- there is either a DRIVE-CLiQ communication error or communication has failed.
- a time slice overflow of the safety software has occurred.
- the enable of the safety functions in both monitoring channels is inconsistent (p9601 = 0, p9801 <> 0).
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Alarms
1170
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Remedy:
- select Safe Torque Off and deselect again.
- carry out a POWER ON (switch-off/switch-on) for all components.
- check whether there is a DRIVE-CLiQ communication error between the two monitoring channels and, if required, carry out
a diagnostics routine for the faults identified.
- deselect all drive functions that are not absolutely necessary.
- reduce the number of drives.
- check the electrical cabinet design and cable routing for EMC compliance
- check the enable of the safety functions for both of the monitoring channels and if required, correct (p9601, p9801).
Note:
P2: processor 2
SI: Safety Integrated
230630
<location>SI P2: Brake control error
Drive object:
SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The "Safety Integrated" function integrated in the drive on the Motor Module (MM) has detected a brake control error and
initiated a STOP A.
- motor cable is not shielded correctly.
- defect in the brake control circuit of the Motor Module.
Fault value (r0949, interpret decimal):
10:
Fault in "open holding brake" operation.
- parameter p1278 incorrectly set.
- no brake connected or wire breakage (check whether brake releases for p1278 = 1 and p9602/p9802 = 0 (SBC
deactivated)).
- ground fault in brake cable.
30:
Fault in "close holding brake" operation.
- no brake connected or wire breakage (check whether brake releases for p1278 = 1 and p9602/p9802 = 0 (SBC
deactivated)).
- short-circuit in brake winding.
40:
Fault in "brake closed" state.
60, 70:
Fault in the brake control circuit of the Control Unit or communication fault between the Control Unit and Motor Module
(brake control).
81: Safe Brake Adapter: Fault in "brake closed" state.
82: Safe Brake Adapter: Fault for the operation "open brake".
83: Safe Brake Adapter: Fault for the operation "close brake".
84, 85:
Safe Brake Adapter:
Fault in the brake control circuit of the Control Unit or communication fault between the Control Unit and Motor Module
(brake control).
90:
Brake released for service purposes (X4).
91:
Fault in "open holding brake" operation.
- no brake connected or wire breakage (check whether brake releases for p1278 = 1 and p9602/p9802 = 0 (SBC
deactivated)).
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1171
SINAMICS alarms
Remedy:
- check parameter p1278 (for SBC, only p1278 = 0 is permissible).
- select Safe Torque Off and deselect again.
- check the motor holding brake connection.
- check the function of the motor holding brake.
- check whether there is a DRIVE-CLiQ communication error between the Control Unit and the Motor Module involved and,
if required, carry out a diagnostics routine for the faults identified.
- check that the electrical cabinet design and cable routing are in compliance with EMC regulations (e.g. shield of the motor
cable and brake conductors are connected with the shield connecting plate and the motor connectors are tightly screwed
to the housing).
- replace the Motor Module involved.
Operation with Safe Brake Module or Safe Brake Adapter:
- check the Safe Brake Module or Safe Brake Adapter connection.
- Replace the Safe Brake Module or Safe Brake Adapter.
Note:
MM: Motor Module
SBC: Safe Brake Control
SI: Safety Integrated
230631
<location>Brake control: External release active
Drive object:
SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
For mounting purposes, the brake is supplied with voltage via terminal X4.1 and released.
Remedy:
If required, again remove the power supply at X4.1.
230632
<location>SI P2: shutoff valve control/feedback signal error
Drive object:
HLA, HLA_840
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Alarms
1172
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
The drive-integrated "Safety Integrated" function on the Hydraulic Module (monitoring channel 2) has detected a fault for
the control/feedback signal of the shutoff valve and initiated a STOP A.
Possible causes:
- shutoff valve either not connected or not correctly connected (X272).
- feedback signal of the shutoff valve either not connected or not correctly connected (X281/X282).
- feedback signal of the shutoff valve incorrectly set (p9626/p9826).
- shutoff valve defective.
- Hydraulic Module defective.
Fault value (r0949, interpret decimal):
10:
Fault in the "Open shutoff valve" operation.
30:
Fault in the "Close shutoff valve" operation.
40:
Fault in the "Shutoff valve closed" state.
60, 70:
Fault in the control of the cutoff valve or communication error between the Control Unit and the Hydraulic Module.
81:
Feedback signal of the shutoff valve: Fault in the "Shutoff valve closed" state.
82:
Feedback signal of the shutoff valve: Fault when "Opening shutoff valve".
83:
Feedback signal of the shutoff valve: Fault when "Closing shutoff valve".
84:
Feedback signal of the shutoff valve: Fault in the control of the shutoff valve or communication error between the Control
Unit and the Hydraulic Module.
Remedy:
- check the shutoff valve connection (X272).
- check the feedback signals of the shutoff valve (X281, X282).
- check the configuration of the feedback signals of the shutoff valve (p9626/p9826).
- check for EMC-compliant control cabinet design and cable routing (e.g. use shielded cables and connect the shield).
- if necessary, replace the shutoff valve.
- if necessary, replace the Hydraulic Module.
See also: p9626 (SI HLA shutoff valve feedback signal contact configuration (CU)), p9826 (SI HLA shutoff valve feedback
signal contact configuration (MM))
230640
<location>SI P2: Fault in the switch-off signal path of the second channel
Drive object:
HLA, HLA_840
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The Hydraulic Module has detected a communications error with the higher-level control or the TM54F to transfer the safety-
relevant information.
Note:
This fault results in a STOP A that can be acknowledged.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1173
SINAMICS alarms
Remedy:
For the higher-level control, the following applies:
- check the PROFIsafe address in the higher-level control and Hydraulic Module and if required, align.
- save all parameters (p0977 = 1).
- carry out a POWER ON (switch-off/switch-on) for all components.
For TM54F, carry out the following steps:
- start the copy function for the node identifier (p9700 = 1D hex).
- acknowledge hardware CRC (p9701 = EC hex).
- save all parameters (p0977 = 1).
- carry out a POWER ON (switch-off/switch-on) for all components.
For a parallel connection, the following applies:
- check the PROFIsafe address in both monitoring channels and if required, align.
- save all parameters (p0977 = 1).
- carry out a POWER ON (switch-off/switch-on) for all components.
The following generally applies:
- upgrade the Hydraulic Module software.
Note:
MM: Motor Module
SI: Safety Integrated
See also: p9810 (SI PROFIsafe address (Motor Module))
230640
<location>SI P2: Fault in the switch-off signal path of the second channel
Drive object:
SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The Motor Module has detected a communication error with the higher-level control or the TM54F to transfer the safety-
relevant information or there is a communication error between Motor Modules connected in parallel.
Note:
This fault results in a STOP A that can be acknowledged.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
For the higher-level control, the following applies:
- check the PROFIsafe address in the higher-level control and Motor Modules and if required, align.
- save all parameters (p0977 = 1).
- carry out a POWER ON (switch-off/switch-on) for all components.
For TM54F, carry out the following steps:
- start the copy function for the node identifier (p9700 = 1D hex).
- acknowledge hardware CRC (p9701 = EC hex).
- save all parameters (p0977 = 1).
- carry out a POWER ON (switch-off/switch-on) for all components.
For a parallel connection, the following applies:
- check the PROFIsafe address in both monitoring channels and if required, align.
- save all parameters (p0977 = 1).
- carry out a POWER ON (switch-off/switch-on) for all components.
The following generally applies:
- upgrade the Motor Module software.
Note:
MM: Motor Module
SI: Safety Integrated
See also: p9810 (SI PROFIsafe address (Motor Module))
Alarms
1174
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
230649
<location>SI P2: Internal software error
Drive object:
HLA, HLA_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
An internal error in the Safety Integrated software in monitoring channel 2 has occurred.
Note:
This fault results in a STOP A that cannot be acknowledged.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (switch-off/switch-on) for all components.
- re-commission the Safety Integrated Function and carry out a POWER ON.
- upgrade the Motor Module/Hydraulic Module software.
- contact Technical Support.
- replace the Motor Module/Hydraulic Module.
Note:
MM: Motor Module
SI: Safety Integrated
230650
<location>SI P2: Acceptance test required
Drive object:
HLA, HLA_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The "Safety Integrated" function on monitoring channel 2 requires an acceptance test.
Note:
This fault results in a STOP A that can be acknowledged.
Fault value (r0949, interpret decimal):
130: Safety parameters for monitoring channel 2 not available.
Note:
This fault value is always output when Safety Integrated is commissioned for the first time.
1000: Reference and actual checksum in monitoring channel 2 are not identical (booting).
- as a result of the changed current controller sampling time (p0115[0]), the clock cycle time for the Safety Integrated Basic
Functions (r9880) was adapted.
- safety parameters set offline and loaded into the Control Unit.
- a download was made to the SINAMICS, whose firmware versions in monitoring channel 2 did not correspond to the latest
version. The request to switch off the DRIVE-CLiQ component A1007 was present after the download.
- at least one checksum-checked piece of data is defective.
2000: Reference and actual checksum in monitoring channel 2 are not identical (commissioning mode).
- reference checksum on monitoring channel 2 incorrectly entered (p9899 not equal to r9898).
2003: Acceptance test is required as a safety parameter has been changed.
2005: The safety logbook has identified that the safety checksums have changed. An acceptance test is required.
3003: Acceptance test is required as a hardware-related safety parameter has been changed.
9999: Subsequent response of another safety-related fault that occurred when booting that requires an acceptance test.
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1175
SINAMICS alarms
Remedy:
For fault value = 130:
- carry out safety commissioning routine.
For fault value = 1000:
- check the Safety Integrated Basic Functions (r9880) and adapt the reference checksum (p9899).
- again carry out safety commissioning routine.
- Using STARTER, activate the safety parameters for the drive involved (change settings, copy parameters, activate settings).
- switch off and switch on the drive unit and DRIVE-CLiQ components. If A30650 is still present, repeat the download.
- replace the memory card or Control Unit.
For fault value = 2000:
- check the safety parameters on monitoring channel 2 and adapt the reference checksum (p9899).
For fault value = 2003, 2005:
- carry out an acceptance test and generate an acceptance report.
The procedure when carrying out an acceptance test as well as an example of the acceptance report are provided in the
following literature:
SINAMICS S120 Function Manual Safety Integrated
For fault value = 3003:
- carry out the function checks for the modified hardware and generate an acceptance report.
The procedure when carrying out an acceptance test as well as an example of the acceptance report are provided in the
following literature:
SINAMICS S120 Function Manual Safety Integrated
For fault value = 9999:
- carry out diagnostics for the other safety-related fault that is present.
Note:
MM: Motor Module
SI: Safety Integrated
See also: p9799 (SI reference checksum SI parameters (Control Unit)), p9899 (SI reference checksum SI parameters (Motor
Module))
230651
<location>SI P2: Synchronization with Control Unit unsuccessful
Drive object:
HLA, HLA_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive-integrated "Safety Integrated" function requires synchronization of the safety time slices in both monitoring
channels. This synchronization routine was unsuccessful.
Note:
This fault results in a STOP A that cannot be acknowledged.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade the Motor Module/Hydraulic Module software.
- upgrade the Control Unit software.
Note:
MM: Motor Module
SI: Safety Integrated
230652
<location>SI P2: Illegal monitoring clock cycle
Drive object:
HLA, HLA_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Alarms
1176
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Cause:
The Safety Integrated monitoring clock cycle cannot be maintained due to the communication conditions requested in the
system.
Note:
This fault results in a STOP A that cannot be acknowledged.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- if fault F01652 simultaneously occurs, apply the remedy/countermeasure described there.
- upgrade the firmware of the Motor Module/Hydraulic Module to a later version.
Note:
MM: Motor Module
P2: processor 2
SI: Safety Integrated
230655
<location>SI P2: Align monitoring functions
Drive object:
HLA, HLA_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
An error has occurred when aligning the Safety Integrated monitoring functions of both monitoring channels. No common
set of supported SI monitoring functions was able to be determined.
- there is either a DRIVE-CLiQ communication error or communication has failed.
- Safety Integrated software releases on the Control Unit and Motor Module/Hydraulic Module are not compatible with one
another.
Note:
This fault results in a STOP A that cannot be acknowledged.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade the Motor Module/Hydraulic Module software.
- upgrade the Control Unit software.
- check the electrical cabinet design and cable routing for EMC compliance
Note:
CU: Control Unit
MM: Motor Module
SI: Safety Integrated
230656
<location>SI P2: Motor Module parameter error
Drive object:
HLA, HLA_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
When accessing the Safety Integrated parameters for monitoring channel 2 in the non-volatile memory, an error has
occurred.
Note:
This fault results in a STOP A that can be acknowledged.
Fault value (r0949, interpret decimal):
129:
- safety parameters for monitoring channel 2 corrupted.
- drive with enabled safety functions was possibly copied offline using the commissioning tool and the project downloaded.
131: Internal software error on the Control Unit.
255: Internal Motor Module/Hydraulic Module software error.
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1177
SINAMICS alarms
Remedy:
- re-commission the safety functions.
- upgrade the Control Unit software.
- upgrade the Motor Module/Hydraulic Module software.
- replace the memory card or Control Unit.
For fault value = 129:
- activate the safety commissioning mode (p0010 = 95).
- adapt the PROFIsafe address (p9610).
- start the copy function for SI parameters (p9700 = D0 hex).
- acknowledge data change (p9701 = DC hex).
- exit the safety commissioning mode (p0010 = 0).
- save all parameters (p0977 = 1 or "copy RAM to ROM").
- carry out a POWER ON (switch-off/switch-on) for all components.
Note:
MM: Motor Module
SI: Safety Integrated
230657
<location>SI P2: PROFIsafe telegram number invalid
Drive object:
HLA, HLA_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
The PROFIsafe telegram number set in p9811 is not valid.
When PROFIsafe is enabled (p9801.3 = 1), then a telegram number greater than zero must be entered in p9811.
Note:
This fault does not result in a safety stop response.
See also: p9611, p60022 (PROFIsafe telegram selection)
Remedy:
Check the telegram number setting (p9811).
230659
<location>SI P2: Write request for parameter rejected
Drive object:
HLA, HLA_840
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The write request for one or several Safety Integrated parameters in monitoring channel 2 was rejected.
Note:
This fault does not result in a safety stop response.
Fault value (r0949, interpret decimal):
10: An attempt was made to enable the STO function although this cannot be supported.
13: An attempt was made to enable the SS1 function although this cannot be supported.
14: An attempt was made to enable the safe motion monitoring function with the higher-level control, although this cannot
be supported.
15: An attempt was made to enable the motion monitoring functions integrated in the drive although these cannot be
supported.
16: An attempt was made to enable the PROFIsafe communication - although this cannot be supported or the version of the
PROFIsafe driver used on both monitoring channels is different.
18: An attempt was made to enable the PROFIsafe function for Basic Functions although this cannot be supported.
19: For ESR, an attempt was made to enable the delay for pulse suppression, although this cannot be supported.
27: An attempt was made to activate the Basic Functions by controlling via TM54F although this is not supported.
29: An attempt was made to parameterize the fault response for PROFIsafe failure to STOP B although this cannot be
supported.
33: Safety functions without selection are not supported (p9601.5, p9801.5).
See also: r9771 (SI common functions (Control Unit)), r9871 (SI common functions (Motor Module))
Alarms
1178
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Remedy:
For fault value = 10, 13, 14, 15, 16, 18, 19:
- check whether there are faults in the safety function alignment between the two monitoring channels (F01655, F30655)
and if required, carry out diagnostics for the faults involved.
- use a Hydraulic Module that supports the required function.
- upgrade the Hydraulic Module software.
- upgrade the Control Unit software.
For fault value = 29:
- check whether p9612 and p9812 are set; if required, correct the settings.
- use a Hydraulic Module that supports the required function.
- upgrade the Hydraulic Module software.
- upgrade the Control Unit software.
Note:
SI: Safety Integrated
SS1: Safe Stop 1 (corresponds to Stop Category 1 acc. to EN60204)
STO: Safe Torque Off / SH: Safe standstill
230659
<location>SI P2: Write request for parameter rejected
Drive object:
SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The write request for one or several Safety Integrated parameters in monitoring channel 2 was rejected.
Note:
This fault does not result in a safety stop response.
Fault value (r0949, interpret decimal):
10: An attempt was made to enable the STO function although this cannot be supported.
11: An attempt was made to enable the SBC function although this cannot be supported.
13: An attempt was made to enable the SS1 function although this cannot be supported.
14: An attempt was made to enable the safe motion monitoring function with the higher-level control, although this cannot
be supported.
15: An attempt was made to enable the motion monitoring functions integrated in the drive although these cannot be
supported.
16: An attempt was made to enable the PROFIsafe communication - although this cannot be supported or the version of the
PROFIsafe driver used on both monitoring channels is different.
18: An attempt was made to enable the PROFIsafe function for Basic Functions although this cannot be supported.
19: For ESR, an attempt was made to enable the delay for pulse suppression, although this cannot be supported.
27: An attempt was made to activate the Basic Functions by controlling via TM54F although this is not supported.
28: An attempt was made to enable the "STO via terminals at the Power Module" function although this cannot be supported.
29: An attempt was made to parameterize the STOP B as stop response for PROFIsafe failure, although this cannot be
supported.
See also: r9771 (SI common functions (Control Unit)), r9871 (SI common functions (Motor Module))
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1179
SINAMICS alarms
Remedy:
For fault value = 10, 11, 13, 14, 15, 16, 18, 19, 27:
- check whether there are faults in the safety function alignment between the two monitoring channels (F01655, F30655)
and if required, carry out diagnostics for the faults involved.
- use a Motor Module that supports the required function.
- upgrade the Motor Module software.
- upgrade the Control Unit software.
For fault value = 28:
- use the power unit with the feature "STO via terminals at the Power Module".
For fault value = 29:
- use a Motor Module that supports the required function.
- upgrade the Motor Module software.
- upgrade the Control Unit software.
- If required, parameterize the stop response for PROFIsafe failure to STOP A (p9612 = p9812 = 0).
Note:
CU: Control Unit
ESR: Extended Stop and Retract
MM: Motor Module
SBC: Safe Brake Control
SI: Safety Integrated
SS1: Safe Stop 1
STO: Safe Torque Off / SH: Safe standstill
230664
<location>Error while booting
Drive object:
A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, ENC, ENC_840, HLA, HLA_840, HUB, R_INF, S_INF, S_INF_840, SERVO,
SERVO_840, SERVO_AC, TB30, TM120, TM15, TM150, TM15DI_DO, TM17, TM31, TM41, TM54F_MA, TM54F_SL, VECTOR,
VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
An error has occurred during booting.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- upgrade firmware to later version.
- contact Technical Support.
230665
<location>SI P2: System is defective
Drive object:
SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A system defect was detected before the last boot or in the actual one. The system might have been rebooted (reset).
Fault value (r0949, interpret hexadecimal):
2 hex:
- parameters p9500 and p9300 are not the same (if Safety message C30711 is displayed at the same time).
200000 hex, 400000 hex:
- fault in the actual booting/operation.
Additional values:
- defect before the last time that the system booted.
Alarms
1180
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
SINAMICS alarms
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- upgrade firmware to later version.
- contact Technical Support.
For fault value = 2:
- check parameters p9500 and p9300 to see if they are the same (if Safety message C30711 is displayed at the same time).
For fault value = 400000 hex:
- ensure that the Control Unit is connected to the Power Module.
230666
<location>SI Motion P2: Steady-state (static) 1 signal at the F-DI for safe acknowledgment
Drive object:
HLA, HLA_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
-
Reaction:
NONE
Acknowledge:
NONE
Cause:
A logical 1 signal is present at the F-DI configured in p10106 for more than 10 seconds.
If, at the F-DI no acknowledgment was performed for safe acknowledgment, then a steady-state logical and 0 signal must
be present. This avoids unintentional safety-relevant acknowledgment (or the "Internal Event Acknowledge" signal) if a wire
breaks or one of the two digital inputs bounces.
Remedy:
Set the failsafe digital input (F-DI) to a logical 0 signal (p10106).
Note:
F-DI: Failsafe Digital Input
230672
<location>SI P2: Control Unit software incompatible
Drive object:
HLA, HLA_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The existing Control Unit software does not support the safe drive-based motion monitoring function.
Note:
This fault results in a STOP A that cannot be acknowledged.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- check whether there are faults in the safety function alignment between the two monitoring channels (F01655, F30655)
and if required, carry out diagnostics for the faults involved.
- use a Control Unit that supports the safe motion monitoring function.
- upgrade the Control Unit software.
Note:
SI: Safety Integrated
230674
<location>SI Motion P2: Safety function not supported by PROFIsafe telegram
Drive object:
HLA, HLA_840, SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC
Message value:
%1
Reaction:
OFF2
Acknowledge:
POWER ON
Alarms
Diagnostics Manual, 10/2020, 6FC5398-6BP40-6BA4
1181

 

 

 

 

 

 

 