Infiniti M35/M45 Y50. Manual - part 138

 

  Index      Infiniti     Infiniti M35/M45 Y50 - service repair manual 2007 year

 

Search            copyright infringement  

 

 

 

 

 

 

 



 

 

Content   ..  136  137  138  139   ..

 

 

Infiniti M35/M45 Y50. Manual - part 138

 

 

TROUBLE DIAGNOSIS

ATC-103

C

D

E

F

G

H

I

K

L

M

A

B

ATC

Test Reading (VK45DE)

Recirculating-to-discharge Air Temperature Table

Ambient Air Temperature-to-operating Pressure Table

Inside air (Recirculating air) at blower assembly inlet

Discharge air temperature at center ventilator

°

C (

°

F)

Relative humidity

%

Air temperature

°

C (

°

F)

50 - 60

20 (68)

6.0 - 7.4 (43 - 45)

25 (77)

8.9 - 10.6 (48 - 51)

30 (86)

12.5 - 14.6 (55 - 58)

35 (95)

16.7 - 19.4 (62 - 67)

60 - 70

20 (68)

7.4 - 8.7 (45 - 48)

25 (77)

10.6 - 12.2 (51 - 54)

30 (86)

14.6 - 16.7 (58 - 62)

35 (95)

19.4 - 22.1 (67 - 72)

Ambient air

High-pressure (Discharge side)

kPa (kg/cm

2

 , psi)

Low-pressure (Suction side)

kPa (kg/cm

2

 , psi)

Relative humidity

%

Air temperature

°

C (

°

F)

50 - 70

20 (68)

907 - 1,106

(9.3 - 11.3, 131.5 - 160.4)

192 - 238

(2.0 - 2.4, 27.8 - 34.5)

25 (77)

987 - 1,207

(10.1 - 12.3, 143.1 - 175.0)

210 - 262

(2.1 - 2.7, 30.5 - 38.0)

30 (86)

1,072 - 1,312

(10.9 - 13.4, 155.4 - 190.2)

233 - 284

(2.4 - 2.9, 33.8 - 41.2)

35 (95)

1,168 - 1,425

(11.9 - 14.5, 169.4 - 206.6)

258 - 320

(2.6 - 3.3, 37.4 - 46.4)

40 (104)

1,272 - 1,550

(13.0 - 15.8, 184.4 - 224.8)

288 - 356

(2.9 - 3.6, 41.8 - 51.6)

ATC-104

TROUBLE DIAGNOSIS

TROUBLE DIAGNOSIS FOR UNUSUAL PRESSURE

Whenever system’s high and/or low side pressure(s) is/are unusual, diagnose using a manifold gauge. The
marker above the gauge scale in the following tables indicates the standard (usual) pressure range. Since the
standard (usual) pressure, however, differs from vehicle to vehicle, refer to above table (Ambient air tempera-
ture-to-operating pressure table).

Both High- and Low-pressure Sides are Too High

High-pressure Side is Too High and Low-pressure Side is Too Low

Gauge indication

Refrigerant cycle

Probable cause

Corrective action

Both high- and low-pressure sides 
are too high.

The pressure returns to nor-
mal soon after water is 
splashed on condenser.

Excessive refrigerant charge 
in refrigeration cycle.

Reduce refrigerant until speci-
fied pressure is obtained.

Air suction by cooling fan is 
insufficient.

Insufficient condenser cooling 
performance.

1. Condenser fins are clogged.

2. Improper fan rotation of 

cooling fan.

Clean condenser.

Check and repair cooling fan 
as necessary.

Low-pressure pipe is not 
cold.

When compressor is 
stopped high-pressure 
value quickly drops by 
approximately 196 kPa (2 
kg/cm

2

 , 28 psi). It then 

decreases gradually there-
after.

Poor heat exchange in con-
denser
(After compressor operation 
stops, high-pressure 
decreases too slowly.).

Air in refrigeration cycle.

Evacuate repeatedly and 
recharge system.

Engine tends to overheat.

Engine cooling systems mal-
function.

Check and repair each engine 
cooling system.

An area of the low-pres-
sure pipe is colder than 
areas near the evaporator 
outlet.

Low-pressure pipe is 
sometimes covered with 
frost.

Excessive liquid refrigerant 
on low-pressure side.

Excessive refrigerant dis-
charge flow.

Expansion valve is open a 
little compared with the 
specification.

 

Improper expansion valve 
adjustment.

Replace expansion valve.

AC359A

Gauge indication

Refrigerant cycle

Probable cause

Corrective action

High-pressure side is too high and 
low-pressure side is too low.

Upper side of condenser and 
high-pressure side are hot, 
however, liquid tank is not so 
hot.

High-pressure tube or parts 
located between compressor 
and condenser are clogged or 
crushed.

Check and repair or replace 
malfunctioning parts.

Check lubricant for contami-
nation.

AC360A

TROUBLE DIAGNOSIS

ATC-105

C

D

E

F

G

H

I

K

L

M

A

B

ATC

High-pressure Side is Too Low and Low-pressure Side is Too High

Both High- and Low-pressure Sides are Too Low

Gauge indication

Refrigerant cycle

Probable cause

Corrective action

High-pressure side is too low and 
low-pressure side is too high.

High- and low-pressure sides 
become equal soon after com-
pressor operation stops.

Compressor pressure opera-
tion is improper.

Damaged inside compressor 
packings.

Replace compressor.

No temperature difference 
between high- and low-pres-
sure sides.

Compressor pressure opera-
tion is improper.

Damaged inside compressor 
packings.

Replace compressor.

AC356A

Gauge indication

Refrigerant cycle

Probable cause

Corrective action

Both high- and low-pressure sides 
are too low.

There is a big temperature 
difference between liquid 
tank outlet and inlet. Outlet 
temperature is extremely 
low.

Liquid tank inlet and expan-
sion valve are frosted.

Liquid tank inside is slightly 
clogged.

Replace liquid tank.

Check lubricant for contami-
nation.

Temperature of expansion 
valve inlet is extremely low 
as compared with areas 
near liquid tank.

Expansion valve inlet is 
frosted.

Temperature difference 
occurs somewhere in high-
pressure side.

High-pressure pipe located 
between liquid tank and 
expansion valve is clogged.

Check and repair malfunc-
tioning parts.

Check lubricant for contami-
nation.

Expansion valve and liquid 
tank are warm or slightly cool 
when touched.

Low refrigerant charge.

Leaking fittings or compo-
nents.

Check refrigerant for leaks. 
Refer to 

ATC-169, "Checking 

for Refrigerant Leaks"

 .

There is a big temperature dif-
ference between expansion 
valve inlet and outlet while the 
valve itself is frosted.

Expansion valve closes a little 
compared with the specifica-
tion.

1. Improper expansion valve 

adjustment.

2. Malfunctioning expansion 

valve.

3. Outlet and inlet may be 

clogged.

Remove foreign particles by 
using compressed air.

Replace expansion valve.

Check lubricant for contami-
nation.

An area of the low-pressure 
pipe is colder than areas near 
the evaporator outlet.

Low-pressure pipe is clogged 
or crushed.

Check and repair malfunc-
tioning parts.

Check lubricant for contami-
nation.

Air flow volume is not enough 
or is too low.

Evaporator is frozen.

Check intake sensor circuit.
Refer to 

ATC-121, "Intake 

Sensor Circuit"

 .

Replace compressor.

Repair evaporator fins.

Replace evaporator.

Refer to 

ATC-88, "Blower 

Motor Circuit"

 . 

AC353A

ATC-106

TROUBLE DIAGNOSIS

Low-pressure Side Sometimes Becomes Negative

Low-pressure Side Becomes Negative

DIAGNOSIS PROCEDURE FOR INSUFFICIENT COOLING

SYMPTOM: Insufficient cooling

1. 

CHECK POWER SUPPLY FOR ECV (ELECTRONIC CONTROL VALVE)

1.

Disconnect compressor (ECV) connector.

2.

Turn ignition switch ON.

3.

Check voltage between compressor (ECV) harness connector
F34 terminal 2 and ground.

OK or NG

OK

>> GO TO 2.

NG

>> Check power supply circuit and 10A fuse [No. 12, 

located in the fuse block (J/B)]. Refer to 

PG-114, "FUSE 

BLOCK - JUNCTION BOX (J/B)"

 .

If fuse is OK, check harness for open circuit. Repair or replace if necessary.

If fuse is NG, check harness for short circuit and replace fuse.

Gauge indication

Refrigerant cycle

Probable cause

Corrective action

Low-pressure side sometimes 
becomes negative.

Air conditioning system 
does not function and does 
not cyclically cool the com-
partment air.

The system constantly func-
tions for a certain period of 
time after compressor is 
stopped and restarted.

Refrigerant does not dis-
charge cyclically.

Moisture is frozen at expan-
sion valve outlet and inlet.

Water is mixed with refriger-
ant.

Drain water from refrigerant 
or replace refrigerant.

Replace liquid tank.

AC354A

Gauge indication

Refrigerant cycle

Probable cause

Corrective action

Low-pressure side becomes nega-
tive.

Liquid tank or front/rear side of 
expansion valve’s pipe is 
frosted or wet with dew.

High-pressure side is closed 
and refrigerant does not flow.

Expansion valve or liquid tank 
is frosted.

Leave the system at rest until 
no frost is present. Start it 
again to check whether or not 
the malfunction is caused by 
water or foreign particles.

If water is the cause, initially 
cooling is okay. Then the 
water freezes causing a 
blockage. Drain water from 
refrigerant or replace refrig-
erant.

If due to foreign particles, 
remove expansion valve 
and remove the particles 
with dry and compressed air 
(not shop air).

If either of the above meth-
ods cannot correct the mal-
function, replace expansion 
valve.

Replace liquid tank.

Check lubricant for contami-
nation.

AC362A

2 – ground

: Battery voltage

RJIA4213E

 

 

 

 

 

 

 

Content   ..  136  137  138  139   ..